13 - RECOMMENDED WIRE SECTIONS
Wire sizing is the responsibility of the installer, and depends on
the characteristics and regulations applicable to each installa-
tion site. The following is only to be used as a guideline, and
does not make Carrier in any way liable. After wire sizing has
been completed, using the certified dimensional drawing, the
instal-ler must ensure easy connection and define any modifi-
cations necessary on site.
The connections provided as standard for the field-supplied
power entry cables to the general disconnect/isolator switch
are designed for the number and type of wires, listed in the
table below.
The calculations are based on the maximum machine current
(see electrical data tables).
For the design the following standardised installation methods
are used, in accordance with IEC 364, table 52C:
-
For 30HX units installed inside the building: No.13:
perforated horizontal cable conduit, and No. 41: closed
conduit.
-
For 30GX units installed outside the building: No.17:
suspended aerial lines, and No. 61: buried conduit with a
derating coefficient of 20.
The calculation is based on PVC or XLPE insulated cables
with copper or aluminium core. The maximum temperature is
40°C for 30HX units and 46°C for 30GX units.
The given wire length limits the voltage drop to < 5%.
Unit
Min. (mm
2
)
Wire type
L (m)
Max. (mm
2
)
Wire type
L (m)
by phase
by phase
30HX 080
1 x 35
XLPE Cu
140
1 x 120
PVC Al
260
30HX 090
1 x 50
XLPE Cu
160
1 x 120
PVC Al
260
30HX 100
1 x 50
XLPE Cu
160
1 x 95
XLPE Al
195
30HX 110
1 x 70
XLPE Cu
170
1 x 120
XLPE Al
205
30HX 120/130
1 x 70
XLPE Cu
170
1 x 150
XLPE Al
210
30HX 140
1 x 95
XLPE Cu
180
1 x 185
XLPE Al
220
30HX 155
1 x 95
XLPE Cu
180
1 x 240
XLPE Al
225
30HX 175
1 x 120
XLPE Cu
185
1 x 240
XLPE Al
225
30HX 190
1 x150
XLPE Cu
190
2 x 95
XLPE Al
195
30HX 200 ckt A
1 x 70
XLPE Cu
170
2 x120
PVC Al
325
30HX 230 ckt A
1 x 95
XLPE Cu
180
2 x 120
PVC Al
325
30HX 260 ckt A
1 x 120
XLPE Cu
185
1 x 240
XLPE Al
225
30HX 285 ckt A
1 x 150
XLPE Cu
190
2 x 150
XLPE Al
265
30HX 200 ckt B
1 x 35
XLPE Cu
140
1 x 95
PVC Al
250
30HX 230 ckt B
1 x 35
XLPE Cu
140
1 x 120
PVC Al
260
30HX 260 ckt B
1 x 35
XLPE Cu
140
1 x 120
PVC Al
260
30HX 285 ckt B
1 x 50
XLPE Cu
160
2 x 70
PVC Al
285
30HX 310 ckt A & B
1 x 95
XLPE Cu
180
1 x 240
XLPE Al
225
30HX 345 ckt A & B
1 x 120
XLPE Cu
185
1 x 240
XLPE Al
225
30HX 375 ckt A & B
1 x 150
XLPE Cu
190
2 x 150
XLPE Al
265
30GX 082
1 x 95
XLPE Cu
190
2 x 185
PVC Al
420
30GX 092
1 x 120
XLPE Cu
195
2 x 185
PVC Al
420
30GX 102
1 x 120
XLPE Cu
195
2 x 240
PVC Al
450
30GX 112
1 x 150
XLPE Cu
200
2 x 150
XLPE Al
300
30GX 122
1 x 185
XLPE Cu
205
2 x 185
XLPE Al
315
30GX 132
1 x 185
XLPE Cu
205
2 x 240
XLPE Al
330
30GX 152
1 x 240
XLPE Cu
205
3x 185
XLPE CU
430
30GX 162
2 x 95
XLPE Cu
190
3x 240
XLPE CU
440
30GX 182
2 x 120
XLPE Cu
200
3x 240
XLPE CU
440
30GX 207 ckt A
1 x 185
XLPE Cu
205
3x 185
XLPE Al
445
30GX 227 ckt A
1 x 240
XLPE Cu
205
3x 240
XLPE Al
470
30GX 247/298/328 ckt A
2 x 120
XLPE Cu
225
3x 185
XLPE CU
490
30HX 267/358 ckt A
2 x 150
XLPE Cu
230
3x 240
XLPE CU
505
30GX 207/227/247 ckt B
1 x 95
XLPE Cu
190
2 x 240
PVC Al
560
30HX 267 ckt B
1 x 120
XLPE Cu
200
2 x 185
XLPE AL
395
30GX 298 ckt B
1 x 185
XLPE Cu
205
3x 240
XLPE AL
470
30GX 328 ckt B
2 x 120
XLPE Cu
225
3x 185
XLPE CU
490
30GX 358 ckt B
2 x 150
XLPE Cu
230
3x 240
XLPE CU
505