10
Compressors
Reference
Size
I nom.
MHA
LRA
LRA (Y)
LRA (S) 1 cp.
LRA (S) 2 cp.
06NW2146S7N
39
48
69
344
109
125
-
06NW2174S7N
46
58
83
423
134
154
-
06NW2209S7N
56
71
101
506
160
260
350
06NW2250S7N
66
87
120
605
191
330
400
06NW2300S5N
80
104
144
715
226
370
420
06NW2300S5E
80+
111
165
856
270
385
460
Legend:
06NW
- Compressor for water-cooled units
N
- Non-economized compressor
E
- Economized compressor
INOM
- Average current draw of the compressor at Eurovent conditions
MHA
- Must hold amperes (maximum operating current) at 360 V
LRA
- Locked rotor current with across-the-line start
LRA (Y)
- Locked rotor current at reduced current (star/delta start-up mode)
LRA (S) 1 cp.
- Start-up with reduced current with electronic starter (start-up duration 3 seconds max.) for one compressor per circuit
LRA (S) 2 cp.
- Start-up with reduced current with electronic starter (start-up duration 3 seconds max.) for two compressors per circuit