71
Problem
Probable Cause
Procedure
5. Unit runs continuously, but with
low performance.
Excessive thermal load.
•
Check project conditions.
Refrigerant lack.
•
Check and fi x leaks. Add
refrigerant if required.
Dirt in the condensers.
•
Check and clean.
Defective compressor.
•
Check compressor pressures and
currents. Replace if required.
Insuffi cient refrigerant supply in the evaporator.
•
Check if there are obstructions
in the dryer fi lter, or in the
lines. Replace or correct.
•
Check expansion valve
obstruction.Replace if necessary.
•
Check the position of the
expansion valve bulb or equalizer
tube. Correct according to
manufacturer specifi cations.
Faulty thermal insulation.
•
Fix or replace.
Air in the system cold water.
•
To take air of the system.
Oil in evaporator.
•
Check and drain.
Compressor runs in reverse rotation.
•
Check suction and discharge
pressures. In case reversion is
detected, invert the terminal power
cables. Check fan rotation.
6. High discharge pressure
Low air fl ow in condenser.
•
Check fan rotation.Fix if necessary.
•
Check motor operation.
Replace if necessary.
•
Check dirt in the coil. Clean
and provide proper fi ltering.
Dirty condenser.
•
Check and clean.
High condensation entering air temperatures.
•
Check condensation air
short circuit or insuffi cient
air intake. To Correct.
•
Check components of the chilled
water installation. To Correct.
Excess of refrigerant.
•
Check and remove excess, setting
subcooling between 8 and 11 °C.
7. Reduced discharge pressure.
Excessive air fl ow in the condenser.
•
Check and adjust.
Refrigerant lack.
•
Check and fi x leaks. Add
refrigerant if required.
Defective compressor.
•
Check suction and discharge
pressures. Replace if necessary.
Compressor runs in reverse rotation.
•
Check suction and discharge
pressures. In case reversion
is detected, invert the
terminal power cables.