background image

16

Status Codes

Table 3 shows the status codes flashed by the amber status light.

Most system problems can be diagnosed by reading the status
code as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the

status light. The short flashes indicate the first digit in the status

code, followed by long flashes indicating the second digit of the
error code. The short flash is 0.25 second ON and the long flash

is 1.0 second ON. Time between flashes is 0.25 second. Time
between short flash and first long flash is 1.0 second. Time

between code repeating is 2.5 seconds with LED OFF.
Count the number of short and long flashes to determine the

appropriate flash code. Table 3 gives possible causes and actions
related to each error.

Example:

3 short flashes followed by 2 long flashes indicates a

32 code. Table 3 shows this to be low pressure switch open.

Table 3—Status Codes

OPERATION

FAULT

AMBER LED

FLASH CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for

unit operation

None

On solid, no

flash

Normal operation

Cool/Heat Operation

None

1, pause

Normal operation

System Communica-

tions Failure

16

Communication with user interface lost. Check wiring to UI, indoor

and outdoor units

High Pressure Switch

Open

31

High pressure switch trip. Check refrigerant charge, outdoor fan

operation and coils for airflow restrictions.

Low Pressure Switch

Open

32

Low pressure switch trip. Check refrigerant charge and indoor air

flow

Control Fault

45

Outdoor unit control board has failed. Control board needs to be

replaced.

Brown Out

(24 v)

46

The control voltage is less than 15.5v for at least 4 seconds. Com-

pressor and fan operation not allowed until control voltage is a mini-

mum of 17.5v. Verify control voltage.

Outdoor Air Temp

Sensor Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor

and check wiring

Outdoor Coil Sensor

Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check

wiring

Thermistors out of

range

56

Improper relationship between coil sensor and outdoor air sensor.

Ohm out sensors and check wiring.

Thermal Cutout

72

Compressor voltage sensed after start---up, then absent for 10 con-

secutive seconds while cooling demand exists. Possible causes are

internal compressor overload trip or loss of high voltage to com-

pressor without loss of control voltage.

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor op-

eration exists. Contactor may be stuck closed or there is a wiring

error.

No 230V at Compres-

sor

74

Compressor voltage not sensed when compressor should be start-

ing. Disconnect may be open or contactor may be stuck open or

there is a wiring error.

Thermal Lockout

82

Thermal cutout occurs in three consecutive cycles. Unit operation

locked out for 4 hours or until 24v power recycled.

Low Pressure Lock-

out

83

Low pressure switch trip has occurred during 5 consecutive cycles.

Unit operation locked out for 4 hours or until 24v power recycled.

High Pressure Lock-

out

84

High pressure switch trip has occurred during 5 consecutive cycles.

Unit operation locked out for 4 hours or until 24v power recycled.

25H

PA

Содержание 25HPA Performance Series

Страница 1: ...ements 3 Step 4 Operating Ambient 3 Step 5 Elevate Unit 3 Step 6 Install TXV 3 4 Step 7 Make Piping Connections 5 7 Step 8 Make Electrical Connections 7 8 Step 9 Compressor Crankcase Heater 8 Step 10...

Страница 2: ...h a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from wi...

Страница 3: ...23 3 4 36 1 2 X 40 9 5 8 6 13 16 28 3 4 A05177 Fig 3 Tiedown Knockout Requirements On rooftop applications locate unit at least 6 in above roof surface STEP 4 Operating Ambient The minimum outdoor ope...

Страница 4: ...R 22 Indoor Coil 1 Pump system down to 2 psig and recover refrigerant 2 Remove coil access panel and fitting panel from front of cabinet 3 Remove TXV support clamp using a 5 16 in nut driver Save the...

Страница 5: ...or coil are exposed to atmosphere they must be evacuated to 500 microns to eliminate contamination and moisture in the system Table 1 Accessory Usage Accessory REQUIRED FOR LOW AMBI ENT APPLICATIONS B...

Страница 6: ...ilure to follow this caution may result in equipment damage or improper operation Service valves must be wrapped in a heat sinking material such as a wet cloth while brazing CAUTION UNIT DAMAGE HAZARD...

Страница 7: ...tdoor unit has not shifted during shipment Ensure tubes are not rubbing against each other or any sheet metal Pay close attention to feeder tubes making sure wire ties on feeder tubes are secure and t...

Страница 8: ...contact with tubing sheet metal etc STEP 9 Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater...

Страница 9: ...properly start up system 1 After system is evacuated fully open liquid and vapor service valves 2 Unit is shipped with valve stem s closed and caps installed Replace stem caps after system is opened...

Страница 10: ...vice port 3 Measure liquid line temperature by attaching an accurate thermistor type or electronic thermometer to liquid line near outdoor coil 4 Refer to unit rating plate for required subcooling tem...

Страница 11: ...ing Operation This product utilizes either a standard indoor thermostat or Infinity communication User Interface With a call for cooling the outdoor fan reversing valve and compressor are energized Wh...

Страница 12: ...ater than or equal to 100 deg F S Fifteen second delay at termination of defrost before the auxiliary heat W2 is de energized S Twenty second delay at termination of defrost before the outdoor fan is...

Страница 13: ...ches on the unit control board or in the Infinity control if used The Infinity Control selection overrides the control board dip switch settings Auto defrost is available with Infinity communicating c...

Страница 14: ...he wiring label diagram This is a 24vac output that is energized whenever the compressor is energized It closes in the compressor off mode to prevent refrigerant migration into the unit through the li...

Страница 15: ...cooling continues the control will energize the compressor contactor every 15 minutes If the thermal protector closes at the next 15 minute interval check the unit will resume operation If the therma...

Страница 16: ...ir flow Control Fault 45 Outdoor unit control board has failed Control board needs to be replaced Brown Out 24 v 46 The control voltage is less than 15 5v for at least 4 seconds Com pressor and fan op...

Страница 17: ...89 84 342 100 95 90 85 349 102 97 92 87 356 103 98 93 88 363 105 100 95 90 370 106 101 96 91 377 107 102 97 92 384 109 104 99 94 391 110 105 100 95 Liquid Pressure at Service Valve Required Subcooling...

Страница 18: ...with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible...

Отзывы: