13
Transfer Refrigerant from Storage Tank Vessel to Chiller
1. Equalize refrigerant pressure.
a. Turn on chiller water pumps, establishing water
flow (assumes vacuum condition in chiller sys-
tem).
b. Close pumpout and storage tank valves 2, 4, 5, 7,
8, 10 (if present open isolation valve 11 and other
isolation valves between cooler and condenser).
Open storage tank valve 6; open chiller valves 1A
and 1B.
c. Gradually open valve 5 to slowly increase chiller
pressure to 35 psig (241 kPa) to reduce the poten-
tial of tube freeze up.
d. Open valve 5 fully after the chiller pressure
reaches 35 psig (241 kPa) or greater. Let chiller
pressure reach 40 psig (276 kPa), then chiller water
pumps can be turned off. Fully close valve 5.
e. Open valve 8 and 10 to let higher pressure in the
recovery tank push liquid refrigerant into the con-
denser float chamber and heat exchangers until the
refrigerant pressure equalizes between the recov-
ery tank and chiller.
2. Push liquid to chiller, them remove remaining vapor from
storage tank:
a. To prepare for liquid, push open valve 4.
b. Ensure pumpout condenser water is off, then turn
on the pumpout compressor in manual mode to
push liquid to chiller. Monitor the storage tank
level until tank is empty of liquid refrigerant.
c. Close charging valves 8 and 10.
d. Turn off the pumpout compressor.
e. To prepare for removal of remaining refrigerant
vapor in storage tank, close pumpout valves 3 and
4 and open valves 2 and 5.
f. Turn on pumpout condenser water.
g. Run pumpout unit in auto until the vacuum switch
is satisfied. This occurs approximately at 15 in Hg
vacuum (48 kPa absolute or 7 psia), removing the
residual refrigerant vapor from the recovery tank
and condensing to a liquid in the chiller.
h. Close valves 1A, 1B, 2, 5, 6.
i. Turn off pumpout condenser water.
Transfer Refrigerant from Chiller to Storage Tank Vessel
1. Equalize refrigerant pressure.
a. Dehydrate the refrigerant storage vessel, and con-
nected hoses/piping so there are no non-condens-
ables mixed with the refrigerant.
b. Locate valves as identified below:
c. Slowly open valve 5 until the refrigerant pressure
reaches 35 psig (241 kPa) in the storage
Fig. 9 — Pumpout Unit
OIL FILL 1/4-IN. FLARE VALVE
a19-2446
FRAME
A
SS
EMBLY
CONTROL
PANEL
VALVE 2
VALVE 4
VALVE 5
VALVE
3
ENTERING
WATER
LEAVING
WATER
CONDEN
S
ER
OIL
S
EPARATOR
OIL
HEATER
COMPRE
SS
OR
a19-
2444
WARNING
During transfer of refrigerant into and out of the 19XR
storage tank, carefully monitor the storage tank level gage.
Do not fill the tank more than 90% of capacity to allow for
refrigerant expansion. Overfilling may result in damage to
the tank and personal injury.
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
C
C
C
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
C
C
C
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
C
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
C
C
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
C
C
C
C
C
C
C
VALVE
1A 1B
2
3
4
5
6
7
8
10
11
CONDITION
C
C
C
C
C
C
Содержание 19XR Series
Страница 19: ......