background image

4

1 - INTRODUCTION

The 19PV units are designed to cool water for the air conditioning 
of buildings and industrial processes.  
Prior to the initial start-up of the 19PV units, the people involved 
in the on-site installation, start-up, operation, and maintenance of 
this unit should be thoroughly familiar with these instructions and 

the specific project data for the installation site.

The 19PV liquid chillers are designed to provide a very high level 
of safety during installation, start-up, operation and maintenance. 
They will provide safe and reliable service when operated within 
their application range.
They are designed for an operating life of 15 years by assuming a 
75% utilisation factor; that is approximately 100,000 operating hours.
This manual provides the necessary information to familiarize 
yourself with the control system before performing start-up 
procedures. The procedures in this manual are arranged in the 
sequence required for machine installation, start-up, operation 
and maintenance.
Always ensure that all required safety measures are followed, 
including those in this document, such as: wearing protective 
clothing (gloves, safety glasses and shoes) using appropriate tools, 
employing qualified and skilled technicians (electricians, 
refrigeration engineers) and following local regulations.

To  find  out,  if  these  products  comply  with  European  directives 

(machine safety, low voltage, electromagnetic compatibility, 
equipment under pressure etc.) check the declarations of 
conformity for these products.

1.1 - Installation safety considerations

Access to the unit must be reserved to authorised personnel, 

qualified and trained in monitoring and maintenance. The access 

limitation device must be installed by the customer (e.g. cut-off, 
enclosure).
After the unit has been received, when it is ready to be installed 
or reinstalled, and before it is started up, it must be inspected for 
damage. Check that the refrigerant circuit(s) is (are) intact, 
especially that no components or pipes have shifted (e.g. following 
a shock). If in doubt, carry out a leak tightness check and verify 
with the manufacturer that the circuit integrity has not been 

impaired. If damage is detected upon receipt, immediately file a 

claim with the shipping company.

The manufacturer strongly recommends employing a 

specialised company to unload the machine.
It is compulsory to wear personal protection equipment. 
Do not remove the skid or the packaging until the unit is in 

its final position. These units can be moved with a fork lift 

truck, as long as the forks are positioned in the right place 

and direction on the unit.

The  units  can  also  be  lifted  with  slings,  using  only  the 

designated lifting points marked on the unit.

Use slings or lifting beams with the correct capacity, and always 

follow the lifting instructions on the certified drawings supplied 

with the unit. Do not tilt the unit more than 15°.
Safety is only guaranteed, if these instructions are carefully 

followed. If this is not the case, there is a risk of material 

deterioration and injuries to personnel.
Never cover any protection devices.
This applies to the relief valves (if used) in the refrigerant or 

heat transfer medium circuits, the fuse plugs and the pressure 

switches.

Ensure that the valves are correctly installed, before operating 

the unit.

Classification and control 

In accordance with the Pressure Equipment Directive and 

national usage monitoring regulations in the European Union 

the protection devices for these machines are classified as 

follows:

Safety 

accessory

(1)

Damage limitation 

accessory in case of an 

external fire

(2)

Refrigerant side

High-pressure switch

x

External relief valve

(3)

x

Rupture disk

x

Fuse plug

x

Heat transfer fluid side

External relief valve

(4)

(4)

(1)  Classified for protection in normal service situations.
(2)  Classified for protection in abnormal service situations. These accessories are 

sized for fires with a thermal flow of 10kW/m². No combustible matter should be 

placed within 6.5m of the unit.

(3)  The instantaneous over-pressure limited to 10% of the operating pressure does 

not apply to this abnormal service situation. The control pressure can be higher 
than the service pressure. In this case either the design temperature or the 
high-pressure switch ensures that the service pressure is not exceeded in normal 
service situations.

(4)  The selection of these discharge valves must be made by the personnel 

responsible for completing the hydraulic installation.

If the relief valves are installed on a change-over valve, this 

is equipped with a relief valve on each of the two outlets. Only 

one of the two relief valves is in operation, the other one is 

isolated. Never leave the change-over valve in the intermediate 

position,  i.e.  with  both  ways  open  bring  the  actuator  in 

abutment, front or back according to the outlet to isolate. If 

a relief valve is removed for checking or replacement please 

ensure that there is always an active relief valve on each of 

the change-over valves installed in the unit.
All factory-installed relief valves are lead-sealed to prevent any 

calibration change. 

The external relief valves and the fuses are designed and 

installed to ensure damage limitation in case of a fire. 

In accordance with the regulations applied for the design, the 

European directive on equipment under pressure and in 

accordance with the national usage regulations:

• 

These relief valves and fuses are not safety accessories 

but damage limitation accessories in case of a fire,

• 

The high pressure switches are the safety accessories.

The relief valve must only be removed if the fire risk is fully 

controlled  and  after  checking  that  this  is  allowed  by  local 

regulations and authorities. This is the responsibility of the 

operator.

When  the  unit  is  subjected  to  fire,  safety  devices  prevent 

rupture  due  to  over-pressure  by  releasing  refrigerant.  The 

fluid  may  then  be  decomposed  into  toxic  residues  when 

subjected to the flame:

• 

Stay away from the unit

• 

Set up warnings and recommendations for personnel 

in charge to stop the fire.

Fire extinguishers appropriate to the system and the 

refrigerant type must be easily accessible.

The  external  relief  valves  must  in  principle  be  connected 

to  discharge  pipes  for  units  installed  in  a  room.  Refer  to 

the  installation  regulations,  for  example  those  of  European 

standards EN 378 and EN 13136.

They include a sizing method and examples for configuration 

and  calculation.  Under  certain  conditions  these  standards 

permit connection of several valves to the same discharge 

pipe. Note: Like all other standards these EN standards are 

available from national standards organisations. 

Содержание 19PV550

Страница 1: ...INSTALLATION OPERATION AND M A I N T E N A N C E I N S T R U C T I O N S Original document Original document 19PV Nominal cooling capacity 550 1600 kW 50Hz...

Страница 2: ...mber of water passes 18 6 6 Min water volume and evaporator condenser water flow rates 18 6 7 Variable flow evaporator 18 6 8 Evaporator pressure drop curves 19 7 WATER CONNECTIONS 20 7 1 Operating pr...

Страница 3: ...fer to the 19PV Touch Pilot Control manual CONTENT 12 OPTIONS 28 13 STANDARD MAINTENANCE 29 13 1 Level 1 maintenance 29 13 2 Level 2 maintenance 29 13 3 Level 3 or higher maintenance 29 13 4 Tightenin...

Страница 4: ...ressure switches Ensure that the valves are correctly installed before operating the unit Classification and control In accordance with the Pressure Equipment Directive and national usage monitoring r...

Страница 5: ...own with the liquid line valve closed as liquid refrigerant can be trapped between this valve and the expansion device This valve is situated on the liquid line before the filter drier box Equip the e...

Страница 6: ...ser water flow Check the cut off value Reactivate manually HP switch and reactivate HP soft value Repeat the procedure for each unit compressor CAUTION If the test leads to replacing the pressure swit...

Страница 7: ...sfer station The units must never be modified to add refrigerant removal and purging devices All these devices are provided with the units Please refer to the certified dimensional drawings for the un...

Страница 8: ...or air flow and to ensure access to the components the number of support points is adequate and that they are in the right places the location is not subject to flooding CAUTION Lift and set down the...

Страница 9: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 550 3045 1120 1745 2800 720 3070 1155 1846 28...

Страница 10: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 900 4257 1290 1955 3950 1010 4257 1290 1955 3...

Страница 11: ...positioning of the fixing points weight distribution and centre of gravity coordinates please refer to the dimensional drawings Dimension mm A B C D 19PV 1300 4705 1290 1955 4400 1450 4740 1290 2011...

Страница 12: ...on valves EXV Minimum capacity 15 15 15 10 10 10 10 10 10 Evaporator Flooded multi pipe type Water volume l 115 165 180 285 285 285 330 330 365 Water connections Victaulic in 6 6 8 8 8 8 8 8 8 Drain a...

Страница 13: ...with option 81 A 387 456 565 570 635 753 Maximum start up current Un Standard unit 3 Lower than max current Dissipated power of electrical equipment 1 W 782 1249 1249 1144 1347 1814 1884 2351 2351 1 V...

Страница 14: ...power supply conductors is not provided with the unit 5 The factory installed disconnect switch es circuit breaker s are of a type suitable for power interruption in accordance with EN 60947 3 corres...

Страница 15: ...This is less than the permissible 2 and is therefore acceptable 5 3 Power connection disconnect switch Units Connection points 19PV550 to 800 1 per unit 19PV900 to 1600 1 for circuit A 1 for circuit...

Страница 16: ...selection Note Option 84 and 84R are not included in these values 5 5 Power cable entry The power cables can enter the 19PV control box from above the unit A removable aluminium plate on the upper par...

Страница 17: ...er temperature C Condenser leaving water temperature C 10 20 30 40 50 0 5 10 15 20 6 2 Minimum chilled water flow The minimum chilled water flow is shown in the table in chapter 6 7 If the system flow...

Страница 18: ...ndenser water flow rate m3 h Minimum 2 21 21 36 36 36 36 36 36 36 Maximum 3 245 299 346 486 457 454 428 594 526 1 Minimum evaporator flow rate based on a water velocity of 0 5 m s 2 Minimum condenser...

Страница 19: ...FG H I J Legend 1 19PV550 6 19PV1180 2 19PV720 7 19PV1300 3 19PV800 8 19PV1450 4 19PV900 9 19PV1600 5 19PV1010 6 9 Condensor pressure drop curves Units with two condenser passes standard Pressure dro...

Страница 20: ...the design operating pressures Before any start up verify that the heat exchange fluid is compatible with the materials and the water circuit coating The use of different metals on hydraulic piping co...

Страница 21: ...1 219 1 219 1 219 1 219 1 219 1 7 3 Flow control Evaporator flow switch and chilled water pump interlock IMPORTANT On 19PV units the unit water flow switch must be energised Failure to follow this in...

Страница 22: ...its own water pump If there is only one common pump in cases with variable flow isolation valves must be installed on each unit They will be activated at the opening and closing by the control of eac...

Страница 23: ...mensions clearances are the same as standard 19PV units Unlike in the cooling mode the unit uses the heating setpoint in this configuration The evaporator leaving water control lowest setpoint taken i...

Страница 24: ...ital outputs permitting control of up to eight fan stages 9 3 Configuration of the number of fan stages and the automatic changeover of the fan stages Please refer to the instructions in the Touch Pil...

Страница 25: ...o communicate and control the drycooler The drycooler with option 313 AUX board with the I O OAT sensor to be place in outdoor zone Dry Cooler Leaving Water Temperature factory mounted Water loop Temp...

Страница 26: ...compressor to reduce broadcasting of the noise radiated emissions from the power lines themselves 11 1 6 Fast acting fuses All compressors are fitted with class T fast acting fuses to protect the soli...

Страница 27: ...sm module and an under voltage protection circuit are mounted on the main supply disconnect switch Note The following procedure must be done to lock the main supply disconnect switch Set the motor mec...

Страница 28: ...management system Allows access to multiple unit parameters 0550 1600 Control for low cond temperature 152 Output signal 0 10 V to control the condenser water inlet valve Simple installation for appli...

Страница 29: ...r see chapter 7 Water connections Check the unit operating parameters and compare them with previous values Replace compressor capacitors every 10 years if energized or 5 years if de energized Replace...

Страница 30: ...e flanges 22 Brass fitting TT300 Motor cooling brass fitting 40 Brass fitting TT350 Motor cooling brass fitting 50 Phillips head screw Compressor cover plate 13 H M8 Screw Drier cover 35 H M10 Screw C...

Страница 31: ...Electrical circuit wiring has been sized and installed properly Unit ground wire has been connected Electrical circuit protection has been sized and installed properly All terminals are tight All chil...

Страница 32: ...l kW capacity for air conditioning 6 5 litres nominal kW capacity for process cooling Proper loop volume established Proper loop corrosion inhibitor included litres of Proper loop freeze protection in...

Страница 33: ...33...

Страница 34: ...Carrier SCS Montluel France Manufacturer reserves the right to change any product specifications without notice Printed in the European Union CARRIER participates in the ECP programme for LCP HP Check...

Отзывы: