6 - APPLICATION DATA
6.5 - Standard and optional number of water passes
19PV
550
720
800
900
1010
1180
1300
1450
1600
Evaporator
Standard
2
2
2
2
2
2
2
2
2
Evaporator with option 100C
1
1
1
1
1
1
1
1
1
Condenser
Standard
2
2
2
2
2
2
2
2
2
Condenser with option 102C
1
1
1
1
1
1
1
1
1
6.6 - Min water volume and evaporator & condenser water flow rates
These below values are given for standard units. For Evaporator and condenser with option 100C/102C, please refer to the unit
selection program.
19PV
550
720
800
900
1010
1180
1300
1450
1600
Minimum installation volume (l)
Air conditioning application
1770
2310
2570
2890
3240
3790
4170
4640
5130
Industrial process application
3530
4620
5140
5780
6480
7570
8330
9290
10250
Evaporator water flow rate, (m
3
/h)
Minimum
(1)
34
34
34
34
61
61
61
61
61
Maximum
(3)
179
235
257
281
289
286
295
295
329
Condenser water flow rate, (m
3
/h)
Minimum
(2)
21
21
36
36
36
36
36
36
36
Maximum
(3)
245
299
346
486
457
454
428
594
526
(1) Minimum evaporator flow rate based on a water velocity of 0,5 m/s.
(2) Minimum condenser flow rate based on a water velocity of 0,3 m/s.
(3) Maximum flow rate based on a pressure drop of 120 kPa (units with two evaporator passes and two condenser passes).
This volume is necessary for stable operation.
It is often necessary to add a buffer water tank to the circuit in order
to achieve the required volume. The tank must itself be internally
baffled in order to ensure proper mixing of the liquid (water or
brine). Refer to the examples below.
Connection to a buffer tank
Bad
Bad
Good
Good
6.7 - Variable flow evaporator
Variable evaporator flow can be used. The controlled flow rate
must be higher than the minimum flow given in the table of
permissible flow rates and must not vary by more than 10% per
minute.
If the flow rate changes more rapidly, the system should contain
a minimum of 6.5 litres of water per kW instead of 3.25 l/kW.