Legend
P1 — Minimum Pressure Load
T1 — Minimum Temperature Load
P2 — Maximum Pressure Load
T2 — Maximum Temperature Load
* Not available on open drive machines.
Table 4 — Capacity Overrides
Override
Capacity
Control
First Stage Setpoint
Second
Stage
Setpoint
Override
Termination
View/
Modify
on LID
Screen
Default Value
Configurable Range
Value
Value
High
Condenser
Pressure
Equip-
ment
Service1
125 psig (862 kPa)
90 to 200 psig
(620-1379 kPa)
>
Override Set
Point + 4 psid
(28 kPad)
<
Override
Set Point
High Motor
Temperature*
Equip-
ment
Service1
>
200 F (93.3 C)
150 to 200 F
(66 to 93 C)
>
Override Set
Point +10° F
(6° C)
<
Override
Set Point
Low
Refrigerant
Temperature
(Refrigerant
Override
Delta
Temperature)
Equip-
ment
Service1
<
3° F (1.6° C) (Above
Trippoint)
2° to 5° F
(1° to 3° C)
≤
Tri
Override
∆
T –1° F
(0.56° C)
>
Tri
Override
∆
T +2° F
(1.2° C)
High
Compressor
LIft (Surge
Prevention)
Equip-
ment
Service1
Min: T1 – 1.5° F
(0.8° C)
P1 – 50 psid
(345 kPad)
Max: T2 – 10° F
(5.6° C)
P2 – 85 psid
(586 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
0.5° to 15° F
(0.3° to 8.3° C)
30 to 170 psid
(207 to 1172 kPad)
None
Within Lift
Limits Plus
Surge/HGBP
Deadband
Setting
Manual Guide
Vane Target
Control
Algorithm
Maint01
Automatic
0 to 100%
None
Release of
Manual Con-
trol
Motor Load —
Active
Demand Limit
Status01
100%
40 to 100%
≥
5% of Set
Point
2% Lower
Than Set
Point
Содержание 17/19EX
Страница 346: ...Figure 1 17 19EX Identification ...
Страница 347: ...Figure 2 Typical 17EX Installation ...
Страница 348: ...Figure 3 Typical 19EX Installation ...
Страница 349: ...Figure 4 Refrigerant Motor Cooling and Oil Cooling Cycles ...
Страница 350: ...v Figure 5 Hermetic Compressor Lubrication System EX Compressor Shown ...
Страница 351: ...Figure 6 Open Drive 17 Series Lubrication Cycle ...
Страница 352: ...Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page Machine Rear Compressor Side View ...
Страница 353: ...Compressor End View Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page ...
Страница 354: ...Machine Front View Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page ...
Страница 355: ...Motor End View Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page ...
Страница 356: ...Figure 7 17EX Controls and Sensor Locations ...
Страница 357: ...Machine Rear Compressor Side View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 358: ...Compressor End View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 359: ...Machine Rear View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 360: ...Motor End View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 361: ...Figure 8 19EX Controls and Sensor Locations ...
Страница 362: ...Figure 9 Control Center Front View Shown with Options Module ...
Страница 363: ...Figure 10 Control Sensors Temperature ...
Страница 364: ...Figure 11 Control Sensors Pressure Transducer Typical ...
Страница 365: ...Figure 12 Power Panel without Options Open Drive Machine Shown ...
Страница 366: ...Figure 13 Power Panel with Options Hermetic Machine Shown ...
Страница 367: ...Figure 14 LID Default Screen ...
Страница 368: ...Figure 15 LID Service Screen ...
Страница 369: ...Figure 16 17 19EX Menu Structure ...
Страница 370: ...Figure 17 17 19EX Service Menu Structure ...
Страница 371: ...Figure 18 Example of Point Status Screen Status01 ...
Страница 372: ...Figure 19 Example of Time Schedule Operation Screen ...
Страница 373: ...Figure 20 Example of Set Point Screen ...
Страница 374: ...Figure 21 17 19EX Hot Gas Bypass Surge Prevention ...
Страница 375: ...Figure 22 17 19EX with Default Metric Settings ...
Страница 376: ...Figure 23 Example of Attach to Network Device Screen ...
Страница 377: ...Figure 24 Example of Holiday Period Screen ...
Страница 378: ...Figure 25 Control Sequence ...
Страница 379: ...Figure 26 Typical Wet Bulb Type Vacuum Indicator ...
Страница 380: ...Figure 27 Shipping Bolt on Open Drive Motor ...
Страница 381: ...Figure 28 17 19EX Leak Test Procedures ...
Страница 382: ...Figure 29 Dehydration Cold Trap ...
Страница 383: ...Figure 30 Correct Motor Rotation ...
Страница 384: ...Figure 31 Refrigeration Log ...
Страница 385: ...Figure 32 Pumpout Arrangement and Valve Number Locations 12 ft Vessel Shown Figure 32 continued on next page ...
Страница 386: ...Figure 32 Pumpout Arrangement and Valve Number Locations 12 ft Vessel Shown Continued ...
Страница 387: ...Figure 33 Pumpout Unit Wiring Schematic 19EX Shown ...
Страница 388: ...Figure 34 Optional Pumpout Compressor ...
Страница 389: ...Figure 35 Electronic Vane Actuator Linkage ...
Страница 390: ...Figure 36 Compressor Contact Seal Open Drive Machines ...
Страница 391: ...Figure 37 Checking Preliminary Alignment ...
Страница 392: ...Figure 38 Measuring Angular Misalignment in Elevation ...
Страница 393: ...Figure 39 Measuring Angular Misalignment on Brackets ...
Страница 394: ...Figure 40 Alignment Formula ...
Страница 395: ...Figure 41 Adjusting Angular Misalignment in Plan ...
Страница 396: ...Preparation Figure 42 Correcting Parallel Misalignment Figure 42 continued on next page ...
Страница 397: ...Measurement Figure 42 Correcting Parallel Misalignment Figure 42 continued on next page ...
Страница 398: ...Adjustment Figure 42 Correcting Parallel Misalignment ...
Страница 399: ...To Check Angular Alignment Figure 43 Alignment Check Assembled Coupling Figure 43 continued on next page ...
Страница 400: ...To Check Parallel Alignment Figure 43 Alignment Check Assembled Coupling ...
Страница 401: ...Figure 44 Removing the Oil Filter ...
Страница 402: ...Figure 45 Typical Float Valve Arrangement ...
Страница 403: ...Figure 46 Lifting Open Drive Motor ...
Страница 404: ...Figure 47 Controls for Optional Pumpout Compressor ...
Страница 405: ...Figure 48 Oil Differential Pressure Power Supply Module ...
Страница 406: ...Figure 49 PSIO Module LED Locations ...
Страница 407: ...Figure 50 LID Module Rear View and LED Locations ...
Страница 408: ...Figure 51 Processor PSIO Module ...
Страница 409: ...Figure 52 Starter Management Module SMM ...
Страница 410: ...Switch Setting Options Module 1 Options Module 2 S1 S2 6 4 7 2 Figure 53 Options Module ...
Страница 411: ...Figure 54 Model Number Nomenclature for Compressor Size See Figure 1 Also ...
Страница 412: ...Note See Table 17 for dimensions Figure 55 Open Drive Compressor Fits and Clearances Figure 55 continued on next page ...
Страница 413: ...Figure 55 Open Drive Compressor Fits and Clearances Figure 55 continued on next page Note See Table 17 for dimensions ...
Страница 414: ...Figure 55 Open Drive Compressor Fits and Clearances Note See Table 17 for dimensions ...
Страница 416: ...Figure 56 Hermetic Compressor Fits and Clearances ...
Страница 417: ...Figure 57 Electronic PIC Controls Wiring Schematic Hermetic Machine Figure 57 continued on next page ...
Страница 418: ...Figure 57 Electronic PIC Controls Wiring Schematic Hermetic Machine ...
Страница 419: ...Figure 58 Electronic PIC Controls Wiring Schematic Open Drive Machine Figure 58 continued on next page ...
Страница 420: ...Figure 58 Electronic PIC Controls Wiring Schematic Open Drive Machine ...
Страница 421: ...Figure 59 Machine Power Panel Starter Assembly and Motor Wiring Schematic Figure 59 continued on next page ...
Страница 422: ...Figure 59 Machine Power Panel Starter Assembly and Motor Wiring Schematic ...
Страница 423: ...Figure 60 Hermetic Drive Power Panel with Water Cooled Oil Cooler ...
Страница 424: ...Figure 61 Hermetic Drive Power Panel with Motor Cooling Solenoid ...
Страница 425: ...Figure 62 Open Drive Power Panel ...