* [LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected
by the operator as an override, alert, or alarm condition. [VALUE] is the actual pressure, temperature,
voltage, etc., at which the control tripped.
Table 8 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
with Troubleshooting Guides
G. Compressor Jumpstart and Refrigerant Protection
Primary Message
Secondary
Message
Alarm Message/Primary
Cause
Additional Cause/Remedy
Unauthorized
Operation
Unit Should Be
Stopped
CA P Emergency: Compres-
sor running without control
authorization.
Compressor is running with
more than 10% RLA and control
is trying to shut it down. Throw
power off to compressor if
unable to stop. Determine cause
before repowering.
Potential Freeze-
up
Evap Press/Temp
Too Low
ERT Emergency: Freeze-up
prevention.
Determine cause. If pumping
refrigerant out of machine, stop
operation and go over pumpout
procedures.
Failure To Stop
Disconnect Power
RUN AUX Emergency: DIS-
CONNECT POWER.
Starter and run and start con-
tacts are energized while control
tried to shut down. Disconnect
power to starter.
Loss Of
Communciation
With Starter
Loss of Communication with
Starter: Check machine.
Check wiring from PSIO to
SMM. Check SMM module trou-
bleshooting procedures.
Starter Contact
Fault
Abnormal 1CR or
RUN AUX
1CR AUX Starter Contact
Fault: Check 1CR/1M aux.
contacts.
Starter run and start contacts
energized while machine was
off. Disconnect power.
Potential Freeze-
up
Cond Press/Temp
Too Low
CRT [VALUE] exceeded limit
of [LIMIT]* Emergency:
Freeze-up prevention.
The condenser pressure trans-
ducer is reading a pressure that
could freeze the water in the
condenser tubes. Check for con-
denser refrigerant leaks, bad
transducers, or transferred
refrigerant. Place the unit in
Pumpdown mode to eliminate
ALARM if vessel is evacuated.
Содержание 17/19EX
Страница 346: ...Figure 1 17 19EX Identification ...
Страница 347: ...Figure 2 Typical 17EX Installation ...
Страница 348: ...Figure 3 Typical 19EX Installation ...
Страница 349: ...Figure 4 Refrigerant Motor Cooling and Oil Cooling Cycles ...
Страница 350: ...v Figure 5 Hermetic Compressor Lubrication System EX Compressor Shown ...
Страница 351: ...Figure 6 Open Drive 17 Series Lubrication Cycle ...
Страница 352: ...Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page Machine Rear Compressor Side View ...
Страница 353: ...Compressor End View Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page ...
Страница 354: ...Machine Front View Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page ...
Страница 355: ...Motor End View Figure 7 17EX Controls and Sensor Locations Figure 7 continued on next page ...
Страница 356: ...Figure 7 17EX Controls and Sensor Locations ...
Страница 357: ...Machine Rear Compressor Side View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 358: ...Compressor End View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 359: ...Machine Rear View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 360: ...Motor End View Figure 8 19EX Controls and Sensor Locations Figure 8 continued on next page ...
Страница 361: ...Figure 8 19EX Controls and Sensor Locations ...
Страница 362: ...Figure 9 Control Center Front View Shown with Options Module ...
Страница 363: ...Figure 10 Control Sensors Temperature ...
Страница 364: ...Figure 11 Control Sensors Pressure Transducer Typical ...
Страница 365: ...Figure 12 Power Panel without Options Open Drive Machine Shown ...
Страница 366: ...Figure 13 Power Panel with Options Hermetic Machine Shown ...
Страница 367: ...Figure 14 LID Default Screen ...
Страница 368: ...Figure 15 LID Service Screen ...
Страница 369: ...Figure 16 17 19EX Menu Structure ...
Страница 370: ...Figure 17 17 19EX Service Menu Structure ...
Страница 371: ...Figure 18 Example of Point Status Screen Status01 ...
Страница 372: ...Figure 19 Example of Time Schedule Operation Screen ...
Страница 373: ...Figure 20 Example of Set Point Screen ...
Страница 374: ...Figure 21 17 19EX Hot Gas Bypass Surge Prevention ...
Страница 375: ...Figure 22 17 19EX with Default Metric Settings ...
Страница 376: ...Figure 23 Example of Attach to Network Device Screen ...
Страница 377: ...Figure 24 Example of Holiday Period Screen ...
Страница 378: ...Figure 25 Control Sequence ...
Страница 379: ...Figure 26 Typical Wet Bulb Type Vacuum Indicator ...
Страница 380: ...Figure 27 Shipping Bolt on Open Drive Motor ...
Страница 381: ...Figure 28 17 19EX Leak Test Procedures ...
Страница 382: ...Figure 29 Dehydration Cold Trap ...
Страница 383: ...Figure 30 Correct Motor Rotation ...
Страница 384: ...Figure 31 Refrigeration Log ...
Страница 385: ...Figure 32 Pumpout Arrangement and Valve Number Locations 12 ft Vessel Shown Figure 32 continued on next page ...
Страница 386: ...Figure 32 Pumpout Arrangement and Valve Number Locations 12 ft Vessel Shown Continued ...
Страница 387: ...Figure 33 Pumpout Unit Wiring Schematic 19EX Shown ...
Страница 388: ...Figure 34 Optional Pumpout Compressor ...
Страница 389: ...Figure 35 Electronic Vane Actuator Linkage ...
Страница 390: ...Figure 36 Compressor Contact Seal Open Drive Machines ...
Страница 391: ...Figure 37 Checking Preliminary Alignment ...
Страница 392: ...Figure 38 Measuring Angular Misalignment in Elevation ...
Страница 393: ...Figure 39 Measuring Angular Misalignment on Brackets ...
Страница 394: ...Figure 40 Alignment Formula ...
Страница 395: ...Figure 41 Adjusting Angular Misalignment in Plan ...
Страница 396: ...Preparation Figure 42 Correcting Parallel Misalignment Figure 42 continued on next page ...
Страница 397: ...Measurement Figure 42 Correcting Parallel Misalignment Figure 42 continued on next page ...
Страница 398: ...Adjustment Figure 42 Correcting Parallel Misalignment ...
Страница 399: ...To Check Angular Alignment Figure 43 Alignment Check Assembled Coupling Figure 43 continued on next page ...
Страница 400: ...To Check Parallel Alignment Figure 43 Alignment Check Assembled Coupling ...
Страница 401: ...Figure 44 Removing the Oil Filter ...
Страница 402: ...Figure 45 Typical Float Valve Arrangement ...
Страница 403: ...Figure 46 Lifting Open Drive Motor ...
Страница 404: ...Figure 47 Controls for Optional Pumpout Compressor ...
Страница 405: ...Figure 48 Oil Differential Pressure Power Supply Module ...
Страница 406: ...Figure 49 PSIO Module LED Locations ...
Страница 407: ...Figure 50 LID Module Rear View and LED Locations ...
Страница 408: ...Figure 51 Processor PSIO Module ...
Страница 409: ...Figure 52 Starter Management Module SMM ...
Страница 410: ...Switch Setting Options Module 1 Options Module 2 S1 S2 6 4 7 2 Figure 53 Options Module ...
Страница 411: ...Figure 54 Model Number Nomenclature for Compressor Size See Figure 1 Also ...
Страница 412: ...Note See Table 17 for dimensions Figure 55 Open Drive Compressor Fits and Clearances Figure 55 continued on next page ...
Страница 413: ...Figure 55 Open Drive Compressor Fits and Clearances Figure 55 continued on next page Note See Table 17 for dimensions ...
Страница 414: ...Figure 55 Open Drive Compressor Fits and Clearances Note See Table 17 for dimensions ...
Страница 416: ...Figure 56 Hermetic Compressor Fits and Clearances ...
Страница 417: ...Figure 57 Electronic PIC Controls Wiring Schematic Hermetic Machine Figure 57 continued on next page ...
Страница 418: ...Figure 57 Electronic PIC Controls Wiring Schematic Hermetic Machine ...
Страница 419: ...Figure 58 Electronic PIC Controls Wiring Schematic Open Drive Machine Figure 58 continued on next page ...
Страница 420: ...Figure 58 Electronic PIC Controls Wiring Schematic Open Drive Machine ...
Страница 421: ...Figure 59 Machine Power Panel Starter Assembly and Motor Wiring Schematic Figure 59 continued on next page ...
Страница 422: ...Figure 59 Machine Power Panel Starter Assembly and Motor Wiring Schematic ...
Страница 423: ...Figure 60 Hermetic Drive Power Panel with Water Cooled Oil Cooler ...
Страница 424: ...Figure 61 Hermetic Drive Power Panel with Motor Cooling Solenoid ...
Страница 425: ...Figure 62 Open Drive Power Panel ...