4.5 Signal Wiring Connections
All signal level wiring connects to
TB1
on the CONTROL BOARD.
Observe the use of shielded cable and
other wiring guidelines detailed in
Section 3.2. Refer to Drawing C11977.
TB1 Terminals 16, 17, 18 Jog Speed
An external Jog Speed
potentiometer, if used, is connected to
terminals 16 (CW), 17 (wiper), and 18
(CCW - common). If an external
potentiometer is not required, a jumper
between terminals 16 and 17 will allow
the Jog Speed to be set by internal
potentiometer P6, Max Jog Speed
(reference section 5.2).
TB1 Terminals 19, 20, 21 Run Speed
An external Run Speed
potentiometer is connected to terminals
19 (CW), 20 (wiper), and 21 (CCW).
The adjustment range of this signal is
determined by internal potentiometers
P8, Max Run Speed, and P10, Min Run
Speed (reference section 5.2).
TB1 Terminals 22, 23
Tachometer
For DC tachometer feedback
connect the 21 VDC /1000 RPM
tachometer to terminals 22 and 23.
These terminals are not polarity
sensitive. The shield should be
connected to terminal 23 (common).
TB1 Terminals 24, 25, 26 Torque
Limit
An external Torque Limit
adjustment potentiometer is connected
to terminals 24 (CW), 25 (wiper), and
26 (CCW - common). If an external
potentiometer is not required, a jumper
between terminals 24 and 25 allows the
maximum torque limit to be set by
internal potentiometer P14, Max Torque
Limit (reference section 5.2).