28
06TA – ELECTRICAL SPECIFICATIONS
COMPRESSOR INFORMATION
RECOMMENDED OVERCURRENT PROTECTION
COMPRESSOR
MODEL
VOLTAGE
HP
MAX MTA
(See Note #1)
LRA
XL
CIRCUIT BREAKER
PART #
MH
MTA
LRA
CARLYLE
FURNAS PART #
(See Note 4)
MH
MTA
RLA
(See Note 3)
06TAD033C
06TAD033B
06TAD033F
575
400/460
208/230
20
39
49
104
138
173
348
HH83XA461
HH83XA424
HH83XB625
33
42
91
38
49
104
124
175
350
HN76JZ022
HN76JZ022
HN76JZ050
34
43
92
38.1
48.2
103
27.2
34.4
73.6
06TAE039C
06TAE039B
06TAE039F
575
400/460
208/230
25
53
64
128
172
215
433
HH83XA469
HH83XA426
HH83XC509
46
55
110
53
64
127
164
210
420
HN76JZ022
HN76JZ033
HN76JZ075
44
56
114
49.3
62.7
127.7
35.2
44.8
91.2
06TAF044C
06TAF044B
06TAF044F
575
400/460
208/230
30
62
76
163
202
253
510
HH83XA430
HH83XA478
HH83XC539
50
67
142
58
76
163
168
274
507
HN76JZ033
HN76JZ033
HN76JZ075
52
65
144
58.2
72.8
161.3
41.6
52
115.2
06TAF048C
06TAF048B
06TAF048F
575
400/460
208/230
30
62
76
163
202
253
510
HH83XA430
HH83XA478
HH83XC539
50
67
142
58
76
163
168
274
507
HN76JZ033
HN76JZ033
HN76JZ075
52
65
144
58.2
72.8
161.3
41.6
52
115.2
06TAG054C
06TAG054B
06TAG054F
575
400/460
208/230
35
78
88
182
242
305
610
HH83XA453
HH83XA547
HH83XC532
68
77
158
78
88
182
236
283
590
HN76JZ050
HN76JZ050
HN76JZ090
69
78
162
77.3
87.4
181.4
55.2
62.4
129.6
06TAG065C
06TAG065B
06TAG065F
575
400/460
208/230
35
72
89
181
258
323
721
HH83XB618
HH83XA475
HH83XC574
63
74
158
72
89
181
258
323
721
HN76JZ050
HN76JZ050
HN76JZ090
69
78
161
77.3
87.4
180.3
55.2
62.4
128.8
06TAH078C
06TAH078B
06TAH078F
575
400/460
208/230
40
81
101
203
296
370
825
HH83XB619
HH83XA476
HH83XC575
71
88
179
81
101
203
296
370
825
HN76JZ050
HN76JZ050
HN76JZ090
72
90
180
80.6
100.8
201.6
57.6
72
144
06TAK088C
06TAK088B
06TAK088F*
575
400/460
208/230
50
92
114
230
351
440
974
HH83XB610
HH83XA477
HH83XC576
74
100
200
89
115
230
323
439
979
HN76JZ050
HN76JZ050
HN76JZ050*
78
100
100
87.4
112
112
62.4
80
160
LEGEND
RLA=Rated Load Amps
PW=Part-Winding Start
LRA=Locked Rotor Amps
MH=Must Hold Amps
XL=Across-the-Line Start
MTA=Must Trip Amps
*
To use Furnas overload w/06TAK088F2EA-A00, compressor must be wired for part-winding start and 2 overloads wired in parallel w
ith
2 contactors. Furnas must hold setting = 100. MTA Setting = 112.
NOTES:
1.
Compressor must trip amps are
maximum
figures. Overcurrent protection must trip at or below this value.
2.
LRA value for PW 2
nd
winding = 1/2 the LRA XL value.
3.
Recommended RLA value = Crt Brk must trip value / 1.4. Use this recommended RLA value to determine minimum contactor sizing and
wiring sizing. See also detail on Compressor Amperage
Ratings on Unit Rating Plate.
4.
Alternate over current protection
device which can be used in place of calibrated circuit breaker.
5.
Carlyle 06TA 400-3-50 units have the same circuit breaker table ratings as 460-3-60. Refer to 460-3-60 data for 50Hz informatio
n.