Section 5.3 Circuit Breaker Tables
27
06TR – ELECTRICAL SPECIFICATIONS
COMPRESSOR INFORMATION
RECOMMENDED OVERCURRENT PROTECTION
COMPRESSOR
MODEL
VOLTAGE
HP
MAX MTA
(See Note #1)
LRA
XL
CIRCUIT BREAKER
PART #
MH
MTA
LRA
CARLYLE
FURNAS PART #
(See Note 4)
MH
MTA
RLA
(See Note 3)
06TRC033C
06TRC033B
06TRC033F
575
400/460
208/230
15
33.5
46
90
114
142
286
HH83XA460
HH83XA463
HH83XB626
29
40
78
33.5
46
90
97
150
250
HN76JZ015
HN76JZ022
HN76JZ050
29
40
80
32.5
44.8
89.6
23.2
32
64
06TRD039C
06TRD039B
06TRD039F
575
400/460
208/230
20
39
49
104
138
173
348
HH83XA461
HH83XA424
HH83XB625
33
42
91
38
49
104
124
175
350
HN76JZ022
HN76JZ022
HN76JZ050
34
43
92
38.1
48.2
103
27.2
34.4
73.6
06TRD044C
06TRD044B
06TRD044F
575
400/460
208/230
20
39
49
104
138
173
348
HH83XA461
HH83XA424
HH83XB625
33
42
91
38
49
104
124
175
350
HN76JZ022
HN76JZ022
HN76JZ050
34
43
92
38.1
48.2
103
27.2
34.4
73.6
06TRE048C
06TRE048B
06TRE048F
575
400/460
208/230
25
53
64
128
172
215
433
HH83XA469
HH83XA426
HH83XC509
46
55
110
53
64
127
164
210
420
HN76JZ022
HN76JZ033
HN76JZ075
44
56
114
49.3
62.7
127.7
35.2
44.8
91.2
06TRE054C
06TRE054B
06TRE054F
575
400/460
208/230
25
53
64
128
172
215
433
HH83XA469
HH83XA426
HH83XC509
46
55
110
53
64
127
164
210
420
HN76JZ022
HN76JZ033
HN76JZ075
44
56
114
49.3
62.7
127.7
35.2
44.8
91.2
06TRF065C
06TRF065B
06TRF065F
575
400/460
208/230
30
62
76
154
219
253
611
HH83XB617
HH83XA474
HH83XC573
54
67
134
61
78
154
219
274
611
HN76JZ033
HN76JZ033
HN76JZ075
55
66
136
61.6
73.9
152.3
44
52.8
108.8
06TRG078C
06TRG078B
06TRG078F
575
400/460
208/230
35
72
89
181
258
323
721
HH83XB618
HH83XA475
HH83XC574
63
74
158
72
89
181
258
323
721
HN76JZ033
HN76JZ050
HN76JZ090
64
78
160
71.7
87.4
179.2
51.2
62.4
128
06TRH088C
06TRH088B
06TRH088F
575
400/460
208/230
40
81
101
203
296
370
825
HH83XB619
HH83XA476
HH83XC575
71
88
179
81
101
203
296
370
825
HN76JZ050
HN76JZ050
HN76JZ090
72
90
180
80.6
100.8
201.6
57.6
72
144
06TRK108B
400-3-50
50
114
440
HH83XA477
100
115
439
HN76JZ050
100
112
80
LEGEND
RLA=Rated Load Amps
PW=Part-Winding Start
LRA=Locked Rotor Amps
MH=Must Hold Amps
XL=Across-the-Line Start
MTA=Must Trip Amps
NOTES:
1.
Compressor must trip amps are
maximum
figures. Overcurrent protection must trip at or below this value.
2.
LRA value for PW 2
nd
winding = 1/2 the LRA XL value.
3.
Recommended RLA value = Crt Brk must trip value / 1.4. Use this recommended RLA value to determine minimum contactor sizing and
wiring sizing. See also detail on Compressor Amperage
Ratings on Unit Rating Plate.
4.
Alternate over current protection
device which can be used in place of calibrated circuit breaker.
5.
Carlyle 06TR 400-3-50 units have the same circuit breaker table ratings as 460-3-60. Refer to 460-3-60 data for 50Hz informatio
n.