How to install a Sx2WEB system
26
Example 2:
SX2WEB24 SH2MCG24 SH2RE16A4 SH2RE16A4 SH2MCG24 SH2SSTRI424 SH2MCG24 SH2SSTRI424
Modules
A
and
B
are connected to the Dupline® network
1
.
Module
C
is connected to the Dupline® network
2
.
Module
D
is connected to the Dupline® network
3
.
Since there are no Dupline® terminals on the top of the slave modules, to connect the Dupline® bus
between different rails in a cabinet, the Dupline® transparent module SH1DUPFT has to be used.
The SH1DUPFT simplifies the wiring of a smart-house installation: it has to be connected at the
beginning of a rail row bringing the Dupline® bus from the top and bottom connectors to the internal bus
and vice versa. Internally, the three connectors are short-circuited. This means that the buses
connected to the top and bottom connectors must be in the same Dupline® network.
Network
1
Network
2
Network
3
Module
A
Module
B
Module
C
Module
D
Dupline® bus
Dupline® bus
Dupline® bus