Fig. 8
RSWT Class 10 motor overload trip profile
PTC resistance - P1, P2 connection
< 500Ω
No Trip
Normal running
> 1000Ω
Trip
Overload alarm (8 flashes) & alarm
relay activated
< 300Ω
Reset
Note: Applies to RSWT 75mm models only.
Number of flashes
9
Alarm
Supply voltage unbalance
Alarm description
The RSWT measures the voltages on all the three phases and if there is a
difference of more than 20% for ≥ 5sec between any of the phases, the RSWT
will trigger the voltage unbalance alarm.
Alarm recovery period
5 minutes
Consecutive alarms for hard reset
4
Action to recover alarm
The alarm will recover automatically after 5 minutes. If manual reset mode is
enabled, press Test/Reset button.
Troubleshooting
•
Check supply voltage level across L1, L2, L3 terminals.
•
Check connections on the L1, L2, L3 terminals.