11
Carlo Gavazzi LTD
RSWT
RSWT DS ENG
17/05/2018
Settings
RSWT 45mm
RSWT 75mm
RSWT 120mm
Ramp-up time
1 - 20 s
Ramp-down time
0 - 20 s
Initial torque
Automatically determined by RSWT
FLC range settings
RSWT 12: 6 - 12 A
RSWT 16: 10 - 16 A
RSWT 25: 13 - 25 A
RSWT 32: 20 - 32 A
RSWT 37: 25 - 37 A
RSWT 45: 33 - 45 A
RSWT 55: 43 - 55 A
RSWT 70: 52 - 70 A
RSWT 90: 66 - 90 A
Power Supply
RSWT40..
RSWT60..
Operational voltage range
187 - 440 VACrms
187 - 660 VACrms
Supply current at idle
< 30 mArms
Blocking voltage
1200 Vp
1600 Vp
Rated AC frequency
50/60 Hz (+/- 10%)
Rated insulation voltage
630 VAC
690 VAC
Dielectric withstand voltage:
Supply to input
Supply to heatsink
2.5 kVrms
2.5 kVrms
Integrated varistor
Yes
Environmental
Working temperature
-20°C to +60°C (-4°F to +140°F). Note: for temperatures > 40°C derating applies.
Storage tempreature
-40°C to +80°C (-40°F to +176°F).
Relative humidity
< 95% non-condensing @ 40°C.
Pollution degree
2
Degree of Protection
(control circuit)
IP20 (EN/IEC 60529)
Installation category
III
Installation altitude
1000 m