•if the Password is a number between “1 and 255”, the configuration data
are entirely protected against undesired accesses;
It is possible to reset the Password by entering the number 768.
•All programming/configuration steps of LDI35 are shown in the
flow chart in the centre of this manual. The flow chart has been
conceived to make the operator better understand the program-
ming structure of LDI35 indicating the position of the current
function with regards to the others. The flow chart also makes
more easily understandable the commands to be used in the
configuration phase.
•See the chapter “Front panel description” for information regard-
ing the use of the key-pad and the relevant main functions.
•Glossary of displayed symbol:
(the symbols like
PAS
in a black background belong to the main menu;
the symbols like AC in a white background belong to the secondary menu).
PAS
: access key to programming
inP
: menu to select measuring inputs
For LDI35.AV2 only:
AC : AC voltage/current measurements;
dC : DC voltage/current measurements.
For LDI35.CF only:
rtd : thermoresistance/Ohm measurements;
tC
: thermocouple measurements
r1 , r2 , r3 , r4 , r5 : range selection (see table “inP” in the
flow chart).
SCA
: menu to program the scaling parameters