15
Essential information
EM24 W1 - Instruction manual | CARLO GAVAZZI Controls SpA
EM24 W1 - Instruction manual | CARLO GAVAZZI Controls SpA
Frame 3
Variable
Data Format
Engineering unit
DIF
[hex]
VIF
[hex]
VIFE#1
[hex]
VIFE#2
[hex]
VIFE#3
[hex]
Current L1
32 bit integer
Ampere*0.001
04
FD
D9
FC
01
Current L2
32 bit integer
Ampere*0.001
04
FD
D9
FC
02
Current L3
32 bit integer
Ampere*0.001
04
FD
D9
FC
03
Voltage L1-N
32 bit integer
Volt*0.1
04
FD
C8
FC
01
Voltage L2-N
32 bit integer
Volt*0.1
04
FD
C8
FC
02
Voltage L3-N
32 bit integer
Volt*0.1
04
FD
C8
FC
03
Frequency
16 bit integer
Hz*0.1
02
FB
2E
Error flag
8 bit integer
01
FD
17
Frame 4
Variable
Data Format
Engineering unit
DIF
[hex]
VIF
[hex]
VIFE#1
[hex]
VIFE#2
[hex]
VIFE#3
[hex]
Total imported active
energy
32 bit integer
Wh*100
04
05
Total exported active
energy
32 bit integer
Wh*100
04
85
3C
Total imported reactive
energy
32 bit integer
kVarh*0.1
04
FB
82
75
Total exported reactive
energy
32 bit integer
kVarh*0.1
04
FB
82
F5
3C
Imported active power
32 bit integer
Watt*0.1
04
2A
Exported active power
32 bit integer
Watt*0.1
04
AA
3C
Imported reactive power
32 bit integer
Var
04
FB
14
Exported reactive power
32 bit integer
Var
04
FB
94
3C
Error flag
8 bit integer
01
FD
17
Notes
:
• the values transmitted - energy, current, voltage, frequency - are instant values, while power values are the average values within the transmission interval
• “error flag” is a diagnostic variable used to communicate an overflow condition which makes the measured data invalid:
Bit
Meaning
Notes
8
[MSb]
7
6
5
4
3
2
1
[LSb]
1P system
3P system
• N.A. (not available): the bit cannot be set because the relevant
measurement is not defined, bit = 0.
•
Frequency out of range is set when occurs an overflow or an under
-
flow of the frequency measured by measuring module.
•
In system 3P, monitored voltages are the L-N voltages referred to a
virtual neutral.
0
0
0
0
0
0
0
0
No error
0
0
0
0
0
0
0
1
V1N overflow
0
0
0
0
0
0
1
0
N.A.
V2N overflow
0
0
0
0
0
1
0
0
N.A.
V3N overflow
0
0
0
0
1
0
0
0
I1 overflow
0
0
0
1
0
0
0
0
N.A.
I2 overflow
0
0
1
0
0
0
0
0
N.A.
I3 overflow
0
1
0
0
0
0
0
0
Frequency out of range
Содержание EM24 W1
Страница 1: ...EM24 W1 USER MANUAL MANUALE D USO BETRIEBSANLEITUNG MANUEL D EMPLOI MANUAL DE USUARIO BRUGERMANUAL ...
Страница 2: ...EM24 W1 Three phase energy analyzer USER MANUAL ...
Страница 19: ...EM24 W1 Analizzatore di energia trifase MANUALE D USO ...
Страница 36: ...EM24 W1 Dreiphasen Energieanalysator BETRIEBSANLEITUNG ...
Страница 53: ...EM24 W1 Analyseur d énergie triphasé MANUEL D EMPLOI ...
Страница 71: ...EM24 W1 Analizador de energía trifásica MANUAL DE USUARIO ...
Страница 88: ...EM24 W1 Trefaset energianalyseapparat BRUGERMANUAL ...