Carlin part number MNEZ123 Rev. 01/12/10

– 12 –

Model EZ-1/2/3 oil burners — Instruction manual

3.  Prepare burner 

(continued)

Inspect/install fuel supply

  Inspect the oil supply system. Ensure that the fuel lines are 

correctly sized and installed and that the fuel flow is unob-
structed, the oil tank is clean and only # 1 or # 2 heating oil 
are supplied. Failure to supply a reliable oil flow could result 
in loss of heat and potential severe equipment damage.

Nozzle line heater

•  Oil burners often operate in spaces where temperatures tend to be 

cool, typically 60°F or lower. Cool oil has higher viscosity, which can 
affect  atomization,  ignition,  combustion  and  fuel  consumption. The 
nozzle line heater avoids this problem by heating the nozzle line oil to 
between 120°F and 130°F, resulting in smoother ignition and improved 
combustion.

General guidelines:

•  When installing oil lines, use continuous runs of heavy-wall copper 

tubing if possible.

•  Check fuel unit (oil pump) data sheet for recommended line sizing, lift 

limitations and maximum length.

•  Check all connections and joints to ensure they are air-tight.
•  Use flare fittings. Do NOT use compression fittings.
•  Never use pipe sealing tape. Fragments can break off and plug fuel line 

components.

•  Install a shut-off valve at the tank and one near the burner. (Use fusible 

handle design valves when possible or when required by codes.)

•  Install a large capacity fuel filter (rated for 50 microns or less) near the 

burner.

Fuel unit bypass plug

  The  fuel  unit  is  shipped  ready  for  a  one-line  oil  system 

(bypass plug is shipped loose). Install the bypass plug only if 
connecting to a two-line oil system. Operating with the plug 
in place on a one-line system will damage the fuel unit and 
could lead to oil leakage and fire hazard.

  If the fuel line or fuel supply is above burner, never exceed 

psig

 pressure at the fuel unit inlet. Install a suitable OSV to 

reduce the pressure. Operating the fuel unit with higher inlet 
pressure could result in fuel unit seal damage, oil leakage 
and potential fire hazard.

•  The nozzle line heater needs power when the burner is in standby (no 

call for heat from the appliance). Make sure the nozzle line heater is 
powered directly from the 120 

vac

 HOT line, not through the appliance 

operating control circuit. The nozzle line heater wiring should be shown 
on the wiring diagram supplied with the appliance/burner unit.

•  The nozzle line heater is supplied with an electrical disconnect harness, 

allowing removal of the combustion head assembly without discon-
necting wires. Position the heater harness disconnect in the rear of 
the blower housing, above the blower access cover. The wire leads to 
the disconnect route through the side of the housing into the junction 
box.

  When first starting the burner, or after the service switch has 

been off for some time, the heater requires about 15 minutes 
to bring the oil to operating temperature.

One-line fuel system

Figure 11 

One-line fuel system requirements

See Figure 11. The standard burner fuel unit is a single-stage, 3450-RPM 
oil pump. Apply this fuel unit only on one-line systems where the fuel sup-
ply is on the same level with, or higher than, the burner. This ensures oil 
flow by gravity. Also make sure the total lift does not exceed 8 feet (height 
difference from bottom of oil tank to fuel unit). For other conditions, you 
must provide a two-line fuel system. You may also have to change the fuel 
unit to a two-stage type.

Содержание EZ-1

Страница 1: ...in severe personal injury death or substantial property damage Boiler model Burner model Primary control Ignitor Fuel unit Oil valve Motor Air tube welded flange Comb head Air band Carlin model Prepur...

Страница 2: ...ly stated otherwise this manual must be used only by a quali fied service technician Failure to comply with this or other requirements in this manual could result in severe personal injury death or su...

Страница 3: ...nd perform the training outlined below Train the user To properly operate the burner appliance per this manual and the appliance instructions see User s information To keep this manual at or near the...

Страница 4: ...age 4 for an initial nozzle selection for the application Specific applications may require testing more than one nozzle to obtain both clean combustion and a good match of flame shape to the combusti...

Страница 5: ...PH Flame length needed 1 50 1 65 to 1 75 2 00 2 25 2 00 2 25 2 50 Nozzle rating GPH Nozzle rating GPH 1 50 1 65 1 75 2 00 2 25 2 00 2 25 2 50 Delavan Hollow 60 A Delavan Hollow 60 A Medium Solid 60 B...

Страница 6: ...t or 50 cubic feet per MBH of all appliances in the room Example For each 1 GPH oil input the room must have 7 000 cubic feet 875 square feet with an 8 foot ceiling height Minimum combustion ventilati...

Страница 7: ...and any associated instructions in the Burner Cover or 97406 Air Intake System instructions Even if using an optional air intake system make sure the space provides enough ventilation to prevent over...

Страница 8: ...ashpit area or fill ashpit with sand up to 2 inches above the mud ring of a boiler firing through the door Install a lightweight refractory liner on the target wall as in Table 3 Figure C Make sure t...

Страница 9: ...ion chamber Universal adjustable flange burners 1 Verify the flange mounting slots line up with the appliance bolts See Figure 1 2 Slip the adjustable flange onto the air tube 3 Measure the distance f...

Страница 10: ...For pressur ized firing you must obtain a burner with a welded flange designed for use with the specific appliance Failure to comply could result in severe personal injury death or substantial proper...

Страница 11: ...ndition 9 Inspect the ignitor contact clips Clean or replace if necessary to ensure reliable contact with the electrodes Inserting removing combustion head assembly Figure 5 3 Prepare burner Install n...

Страница 12: ...GPH 7 options 0 50 0 60 0 65 0 75 0 85 1 00 1 10 1 25 1 10 1 25 1 35 1 50 1 65 EZ 2 EZ 2 HP 1 50 2 25 GPH 4 options 1 50 1 65 1 75 2 00 2 25 EZ 3 EZ 3 HP 2 00 2 50 GPH 3 options 2 00 2 25 2 50 Adjust...

Страница 13: ...oil system Operating with the plug in place on a one line system will damage the fuel unit and could lead to oil leakage and fire hazard If the fuel line or fuel supply is above burner never exceed 3...

Страница 14: ...n ventilation air openings and vent system Fuel supply line in good condition and sized designed correctly Oil tank has oil and oil line valves are open Wiring installed per burner appliance instructi...

Страница 15: ...h is properly fused for the load To start burner Do not start the burner if the combustion chamber contains oil or oil vapor 1 Turn service switch OFF 2 Perform inspections and checkouts on pages 14 a...

Страница 16: ...Carlin part number MNEZ123 Rev 01 12 10 15 Model EZ 1 2 3 oil burners Instruction manual...

Страница 17: ...nd the line switch is properly fused for the load To start burner Do not start the burner if the combustion chamber contains oil or oil vapor 1 Turn service switch OFF 2 Perform inspections and checko...

Страница 18: ...Carlin part number MNEZ123 Rev 01 12 10 17 Model EZ 1 2 3 oil burners Instruction manual...

Страница 19: ...ake sure the burner and appliance are correctly wired and the line switch is properly fused for the load To start burner Do not start the burner if the combustion chamber contains oil or oil vapor 1 T...

Страница 20: ...Carlin part number MNEZ123 Rev 01 12 10 19 Model EZ 1 2 3 oil burners Instruction manual...

Страница 21: ...voltage reading indicates incorrect wiring that must be corrected before attempting to operate the burner 5 Alarm terminals provide a 24 vac rated dry contact suitable for use with security fire alarm...

Страница 22: ...Carlin part number MNEZ123 Rev 01 12 10 21 Model EZ 1 2 3 oil burners Instruction manual...

Страница 23: ...e personal injury or death Use combustion test equipment to verify that the burner is properly set 5 up for your installation Appliances with positive pressure in the chamber may require a wider air o...

Страница 24: ...s found Verify burner appliance operation Check burner appliance controls operation Test operating and limit controls on appliance as specified in appliance instructions Check operation of the primary...

Страница 25: ...assembly 4 nominal approx 5 3 4 oal EZ 1 only 56804 25 Blower wheel 5 1 16d x 2w 77933 Nozzle line adaptor assembly 5 nominal approx 6 3 4 oal 56820 26 Primary control consult factory for other contro...

Страница 26: ...Carlin part number MNEZ123 Rev 01 12 10 25 Model EZ 1 2 3 oil burners Instruction manual 7 Repair parts continued...

Страница 27: ...replace a component or disassemble any part of the burner for service maintenance perform a complete operational test after reassembly to verify the burner operates correctly Failure to verify operat...

Страница 28: ...ro Burners that fall within the extended warranty period such defective parts should be returned freight prepaid to Carlin The repaired component or replacement part will be provided to the Customer f...

Страница 29: ...at all Never attempt to use gasoline as a fuel for this burner as it is more combustible and could result in a serious explosion Never attempt to burn refuse or use any fuel other than 1 or 2 heating...

Отзывы: