background image

6

Be sure that all oil line connections are absolutely air 

tight. Check all connections and joints. Flared fittings are 

required. Do not use compression fittings.
Open the air-bleed valve and start the burner. For clean 

bleed. slip a 1/16"" ID hose over the end of the bleed 

valve and bleed into a container. Continue to bleed for 15 

seconds after oil is free of air bubbles. Stop the burner and 

close the bleed valve.

LIGHT-OFF AND ADJUSTMENT

NOTE:  WHEN STARTING THIS BURNER THE FIRST TIME 

OR AFTER CHANGING NOZZLES, THE FLAME 

MAY GO OUT DURING THE SWING FROM LOW 

TO HIGH. BE READY TO SHUT THE BURNER 

DOWN JUST AFTER THE FLAME GOES OUT. 

REPEAT THIS UNTIL THE AIR IS PURGED OUT OF 

THE HIGH FIRE OIL LINE.

Before starting the burner, pre-set the retention ring posi-

tion for the particular firing rate according to Table 5 for the 

701CRD or Table 6 forthe 8O1CRD.
If the fire is a little too rich, move the combustion head 

forward by increasing dimension "A" (Fig. 7 and 8). At the 

lower inputs, a very slight change is usually enough. DO 

NOT ALTER THE LINKAGE. IT IS PRE-SET AT THE FAC-

TORY.
Model 701CRD is provided with a low fire air shutter ad-

justing screw. This adjusting limits the amount of shutter 

closure which thereby increases or decreases the amount 

of combustion air required for proper burning.
Model 801CRD is supplied with separate low fire and high 

fire air shutters. The low fire air shutter has an adjusting 

screw which should be adjusted to get a cIean, low fire. 

The high fire air shutter is not adjustable and moves with 

the linkage that is pre-set at the factory.
Adjust draft to 0.02 to 0.04 inches W.C. over the fire for 

natural draft units.
Run a smoke test. Strive for zero or a trace. Each time 

further adjustment of retention ring is made, reset the draft 

to 0.02 to 0.04 inches W.C. over the fire.
Check CO

2

. This should be 12 to 12

1

2

 percent, and will 

often be over 13 percent, in a welI-sealed unit.
Check for good ignition and clean cut-off. If cut-off con-

tinues to be poor, look for air leaks in the suction line and 

correct them.
For different boiler applications, it is sometimes necessary 

to have the high-fire pull in earlier or later than normal dur-

ing the swing to achieve a smooth, cleaner transition.
If the swing from low-fire to high-fire is rough, i.e. bangs or 

rumbles or is extremely smoky, the internal end switch of 

the damper motor is possibly not set correctly. The high-

fire should pull in as the air shutter, NOT THE DAMPER 

ARM, is about half way through its swing.
If the fire is lean all the way to high-fire, the high-fire valve 

should be energized earlier. lf during the swing, the fire 

gets very smoky, then cleans up again, the high-fire valve 

should be energized later.
To adjust the damper end switch, remove the damper 

motor cover. This will expose a white plastic gear with 

notches. With the burner off, use the end of a small bladed 

screwdriver inserted into one of the notches of the white 

gear. Turn the gear one notch clockwise if a later pull-in is 

required, or counter clockwise for an earlier pull-in.
The linkage between the damper motor arm and the air 

shutter crank is set at the factory and should only need 

adjustment if the damper motor or damper rod is replaced. 

With the burner in high-fire. there should be minimal play in 

the connecting rod.

WIRING FOR LOW-HIGH-LOW STEP  

MODULATION

In order to take full advantage of the energy savings poten-

tial of these bumers they should be wired to operate with 

low-high-low cycles. Hence the firing cycle would be much 

longer by going from low to high to low once or several 

times before shutting off.
In the following illustrations are two examples: 1. Water 

Boiler. 2. Steam Boiler. ln each case, we have a limit circuit 

which starts and stops the burner and a high fire control 

which brings the high fire on and off.
Also, prewired and built into the burner is a manual high fire 

switch which enables the installer or operator to hold the 

burner on low fire if so desired.
Refer to the appropriate example for your installation.

Example: Water Boiler
Operating Range 170°-190°F
2. Set Safety Hi Limit: Cut in 200 / Cut out 21O
3. Set Operating Limit: Cut in 180 / Cut out 190
4. Set Hi Fire Control: Cut in 170 / Cut out 180

Operation:
1.  Call for heat: cold start. Burner starts on low and goes to 

high fire.

2.  When the temperature rises to 130°F, the burner goes to 

low fire.

3. If temperature drops to 170°, burner returns to high fire.
4. If temperature rises to 190°, burner shuts off.

NOTE: Since the calibrations on the limit controls are 

seldom exact, it will be necessary to readjust the settings 

during operation. 

Содержание 701CRD

Страница 1: ...led by a damper motor It s end switch energizes the second stage valve as the air shutter ap proaches a wide open position Due to the low high low feature of these burners they are very versatile and...

Страница 2: ...low fire the auxiliary end switch in the damper motor opens and de energizes the high fire valve 4 If the demand exceeds low fire the high fire operating control would again call for more heat as in...

Страница 3: ...9 5 9 5 9 5 9 5 10 0 10 0 10 5 10 5 11 0 11 0 11 0 11 0 11 0 11 5 11 5 11 5 11 5 TABLE 4 801CRD MINIMUM DIMENSIONS RECOMMENDED BOILERS FIRED WITHOUT COMBUSTION CHAMBERS Inches 1 High Fire Oil Deliver...

Страница 4: ...E 70lCRD firing at 11 40 GPH high fire A column setting reads 1 4 1 Turn adjusting screw counterclockwise until zero on scale is aligned with rear of housing A equals zero see Fig 8 2 Now turn adjusti...

Страница 5: ...ow the level of the burner and the fuel unit must pull lift the fuel up to the burner The vacuum reading should not exceed 12 mercury 5 9 PSI For two pipe installations the by pass plug must be instal...

Страница 6: ...to achieve a smooth cleaner transition If the swing from low re to high re is rough i e bangs or rumbles or is extremely smoky the internal end switch of the damper motor is possibly not set correctly...

Страница 7: ...ut out 4 PSI Operation 1 Call for heat cold start Bunier starts on low and goes to high fire 2 When pressure rises to 4 PSI the burner goes to low fire 3 lf pressure drops to 3 PSl burner returns to h...

Страница 8: ...ology Inc T E C H S U P P O R T H O T L I N E 8 0 0 9 8 9 2 2 7 5 Carlin Combustion Technology Inc 126 Bailey Road North Haven CT 06473 Phone 203 680 9401 Fax 203 764 1714 e mail us at info carlincomb...

Отзывы: