closure which thereby increases or decreases the amount 

of combustion air required for proper burning.
Model 801CRD is supplied with separate low fire and high 

fire air shutters. The low fire air shutter has an adjusting 

screw which should be adjusted to get a clean, low fire. 

The high fire air shutter is not adjustable and moves with 

the linkage that is preset at the factory.

* When field conditions are unusual or if the load requires it, the low fire and 

high fire may be altered such that the low fire is increased and the high fire de-
creased as needed. The low lire air shutter adjusting screw will require turning 
to the revised nozzle sizes.

*"A"–See Figs. 7 and 8, Page 4.

NOZZLE SPECIFICATIONS

The nozzles shown in Tables 5 and 6 are standard and 

usually provide the best fire. Substitutions are not normally 

recommended.
Other makes of nozzles may or may not prove satisfactory.
For special applications. other specifications might provide 

a more desirable pattern.

FORCED DRAFT FIRING

Due to the back pressure in forced draft units the maxi-

mum firing rate of a burner is reduced. The greater the 

pressure, the lower the maximum GPH capability becomes. 

Table 7 shows this. Note that the Table stops at 0.50 inches 

W.C.: the maximum recommended back pressure for these 

models

.

The combustion head settings for forced draft firing would 

be somewhat greater than those shown in Tables 5 and 6 

which are for zero pressure or natural draft.

FUEL UNITS AND OIL LINES

Standard burners are provided with a two-stage 3450 rpm 

fuel unit set at 150 PSI. 
A single-pipe system is recommended whenever the bot-

tom of the fuel tank is above the burner or is at the same 

level as the burner. This includes outdoor fuel tanks that 

are at such levels. The length of run should not exceed 

100 ft. and the vacuum should not exceed 12" mercury 

(5.9 PSI). Be sure the by-pass plug has been removed for 

single-pipe systems.
A two-pipe system is recommended when the fuel tank is 

below the level of the burner and the fuel unit must pull (lift) 

the fuel up to the burner. The vacuum reading should not 

exceed 12" mercury (5.9 PSI). For two-pipe installations the 

by-pass plug must be installed. 
Table 8 shows, for the standard two-stage fuel unit, the al-

lowable lift and lengths of 1/2" and 5/8" OD tubing for both 

suction and return lines in two-pipe systems.

TABLE 5  701CRD

NOZZLE DATA AND COMBUSTION HEAD SETTINGS

Nozzle Specifications 

Hago Products Corp.

Oil Delivery Rate 

GPH @ 150 PSI

“A”* 

Approximate 

Retention 

Ring Setting 

On Scale

Low Fire 

Air 

Shutter

1st Stage

2nd Stage

Spray

Low Fire

High Fire

3.00

2.00

60°H

3.60

6.00

1/16"

1/8"

3.25

2.25

60°H

3.90

6.60

3/16"

1/8"

3.25

2.75

60°H

3.90

7.20

1/4"

1/8"

3.50

3.00

60°H

4.20

7.80

5/16"

1/4"

3.50

3.50

60°H

4.20

8.40

3/8"

1/4"

3.75

3.75

60°H

4.50

9.00

7/16"

3/8"

4.00

4.00

80°H

4.80

9.60

1/2"

1/2"

4.00

4.50

60°H

4.80

10.20

9/16"

1/2"

4.50

4.50

60°H

5.40

10.80

5/8"

5/8"

4.50

5.00

60°H

5.40

11.40

3/4"

3/8"

5.00

5.00

45°H

6.00

12.00

7/8"

3/4"

5.00

5.50

45°H

6.00

12.60

1

1

16

"

3/4"

5.00

6.00

45°H

6.00

13.20

1

1

4

"

3/4"

TABLE 6  801CRD

NOZZLE DATA AND COMBUSTION HEAD SETTINGS

Nozzle Specifications 

Hago Products Corp.

Oil Delivery Rate 

GPH @ 150 PSI

“A”* 

Approximate 

Retention 

Ring Setting 

On Scale

Low Fire 

Air 

Shutter

1st Stage

2nd Stage

Low Fire

High Fire

5.50

4.00

6.60

11.40

1/16"

1/4"

5.50

4.50

6.60

12.00

1/16"

1/4"

5.50

5.00

6.60

12.60

1/48"

1/4"

5.50

5.50

6.60

13.20

3/16"

1/4"

6.00

5.50

7.20

13.80

1/4"

3/8"

6.00

6.00

7.20

14.40

5/16"

3/8"

6.00

6.50

7.20

15.00

3/8"

3/8"

6.50

6.50

7.80

15.60

7/16"

1/2"

6.50

7.00

7.80

16.20

1/2"

1/2"

6.50

7.50

7.80

16.80

3/8"

1/2"

6.50

8.00

7.80

17.40

3/4"

1/2"

6.50

8.50

7.80

18.00

7/8"

1/2"

7.00

8.50

8.40

18.60

1"

5/8"

7.00

9.00

8.40

19.20

1

1

8

"

5/8"

7.00

9.50

8.40

19.80

1

1

4

"

5/8"

TABLE 7

MAXIMUM FIRING RATES (GPH)–FORCED DRAFT

Burner

Model

Combustion Chamber Pressure

0.00

0.10

0.20

0.30

0.40

0.50

INS.

W.C.

701CRD

13.20 12.70 12.30 11.80 11.30 10.90

801CRD

19.80 19.40 19.00 18.60 18.20 17.80

TABLE 8

MODEL 701CRD & MODEL 801CRD 

TWO-STAGE UNITS–TWO-PIPE SYSTEMS (150 PSI)

Length of Tubing (feet)

Lift (feet)

1/2" OD

5/8" OD

0
2
4
6
8

10
12
14
15

100

88
78
69
59
49
39
29
24

100
100
100
100
100
100
100

82
68

Содержание 701CRD

Страница 1: ...led by a damper motor It s end switch energizes the second stage valve as the air shutter ap proaches a wide open position Due to the low high low feature of these burners they are very versatile and...

Страница 2: ...low fire the auxiliary end switch in the damper motor opens and de energizes the high fire valve 4 If the demand exceeds low fire the high fire operating control would again call for more heat as in...

Страница 3: ...9 5 9 5 9 5 9 5 10 0 10 0 10 5 10 5 11 0 11 0 11 0 11 0 11 0 11 5 11 5 11 5 11 5 TABLE 4 801CRD MINIMUM DIMENSIONS RECOMMENDED BOILERS FIRED WITHOUT COMBUSTION CHAMBERS Inches 1 High Fire Oil Deliver...

Страница 4: ...E 70lCRD firing at 11 40 GPH high fire A column setting reads 1 4 1 Turn adjusting screw counterclockwise until zero on scale is aligned with rear of housing A equals zero see Fig 8 2 Now turn adjusti...

Страница 5: ...ow the level of the burner and the fuel unit must pull lift the fuel up to the burner The vacuum reading should not exceed 12 mercury 5 9 PSI For two pipe installations the by pass plug must be instal...

Страница 6: ...to achieve a smooth cleaner transition If the swing from low re to high re is rough i e bangs or rumbles or is extremely smoky the internal end switch of the damper motor is possibly not set correctly...

Страница 7: ...ut out 4 PSI Operation 1 Call for heat cold start Bunier starts on low and goes to high fire 2 When pressure rises to 4 PSI the burner goes to low fire 3 lf pressure drops to 3 PSl burner returns to h...

Страница 8: ...ology Inc T E C H S U P P O R T H O T L I N E 8 0 0 9 8 9 2 2 7 5 Carlin Combustion Technology Inc 126 Bailey Road North Haven CT 06473 Phone 203 680 9401 Fax 203 764 1714 e mail us at info carlincomb...

Отзывы: