Getting Started

1

  

Ensure you have the right CAP System Kit for your applica-
tion by confirming the firing rate (in GPH) with the table on 
page 1.

IMPORTANT: If you change the firing rate, pressure  

switches are available separately to convert the CAP  
System after installation. (See instructions for Installing 
Pressure Switch on page 8).

2

   

Ensure that the burner is equipped with a  
Carlin Pro-X 70200 primary control with low voltage 
blocked vent (BV) terminals as shown.  
NOTE: 70200 controls 

manufactured prior  
to Sept. 2018  
are not  
compatible  
with the  
CAP System.

3

  

INSTALLING BACKPLATE

 

(for uncovered burners) 

If installing on a covered burner, skip to Step 4.
•  Mount backplate

2

   in the desired orientation and secure 

to the burner using the mounting bolts and star wash-
ers

9

  provided (as shown). The backplate is reversible to 

accommodate left-hand or right-hand mounting of the air 
inlet. (See step 8 for available inlet mounting configura-
tions.)

•  Reroute any BX cable, wiring harness, etc. through one 

of the circular knockouts in the backplate

2

  . 

4

 

 ROUTE THE OIL LINE

•  Route the oil line through one of the circular knockouts in 

the burner cover backplate

2

  . 

5

  

REMOVE AIR INLET KNOCKOUT

 

•  Remove the 2" x 4" air inlet knockout that corresponds 

to the desired air inlet position (vertical or horizontal) as 
shown in step 8.

Pressure Switch Conversion

Firing Rate GPH

Pressure Switch

0.50-1.00

50806A

1.05-1.45

50806B

1.50-1.90

50806C

CAP System Operation

The CAP System is designed to shut down the burner in the event the outside combustion air supply becomes blocked. At each 
burner startup, the system will check the air intake during pre-purge (Valve Delay On*). If the air is blocked, the control will abort 
ignition and shutdown the burner. If the air intake is not blocked during this startup test, but becomes blocked during normal burner 
operation, the burner will shut down if the air remains blocked for 20 seconds. Following any shutdown, the burner will be permitted 
to recycle 3 times following a 1 minute delay. The system will lock out the burner if the blockage continues throughout 3 recycles 
during any single call for heat.
* If the Burner has no valve, the air intake cannot be checked during pre-purge. In this case, the burner will shut down following the 

20 second blockage described above. For all burners with valves, Valve Delay settings of less than 15 Seconds will be automatically 

changed to 15 Seconds to allow for the prepurge test.

Содержание 51300S

Страница 1: ...hout covers 0 50 2 00 51300AS Low Rate CAP Kit for Carlin burners with covers 0 50 1 00 51300BS Medium Rate CAP Kit for Carlin burners with covers 1 05 1 45 51300CS High Rate CAP Kit for Carlin burner...

Страница 2: ...C A P S Y S T E M K I T C O M P O N E N T S s e e p a g e 3 f o r p a r t d e s c r i p t i o n s 8 13 9 1 14 17 18 20 15 19 16 2 12 3 6 7 4 5 10 11 10a 10b 10c 1b 1a 19a COMPONENTS CONTAINED IN POLYB...

Страница 3: ...ssembled with CAP System Air Inlet above 10a 24 inch Air Flow Switch Wiring Harness 51308A 1 10b 10 14 x 1 2 Phillips Head Screw 50605 2 10c 8 16 x 3 4 Phillips Head Screw 51327 1 11 Connecting Flange...

Страница 4: ...the burner cover backplate 2 5 REMOVE AIR INLET KNOCKOUT Remove the 2 x 4 air inlet knockout that corresponds to the desired air inlet position vertical or horizontal as shown in step 8 Pressure Swit...

Страница 5: ...kplate 2 Secure the filler plate 19 below the burner air tube using the two 5 16 bolts and star washers 14 provided Install the 1 62 split grommet 17 around any BX cable wiring harness etc leaving the...

Страница 6: ...em air inlet 10 onto the 2 x 4 air inlet knockout removed in Step 5 Mounting examples below 9 Slide the connecting flange 11 onto the air inlet 10 until fit is tight Reverse flange when using galvaniz...

Страница 7: ...ng the cover 14 CHECK BURNER SETUP CAP System utilizes outside air for combustion Incoming air temperature will fluctuate by season which can significantly impact combustion Use the table below to set...

Страница 8: ...components in the Burner Seal Kit see Step 6 Make sure that the burner cover screw 1b is tight This also prevents basement air from entering the cover Check that the correct air pressure switch 3 4 5...

Отзывы: