201GAS burner at-a-glance

1  Air tube (flange omitted for clarity), with powder coat paint finish
2  Diffuser plate (hole or slot pattern)
3  Gas manifold (concentric cylinders swaged and welded at ends) —  

Gas manifold delivers gas to gas openings on inner wall of manifold 

near the diffuser plate.

4  Ignitor electrode insulator

5  Flame rod insulator

6  Ignitor electrode

7  Flame rod electrode

Gas orifice nipple  — see pages 7 and 8 for orifice sizing requirements

9  Hinged cover plate (for access to blower wheel & electrodes)
10  Ignitor (Carlin Model 41800 solid state electronic ignitor — 9,000 volts, 

continuous duty rated)

11  Primary control — Carlin Model 60200FR microprocessor-based inter

-

rupted ignition flame supervisory control (flame rectification)

12  Flame current test jack

OFF

ON

201003

2

3

4

5

6

7

8

9

10

11

13

12

14

15

16

17

18

19

21

23

1

20

22

13  Burner junction box
14  Motor (with permanently-lubricated bearings and thermal overload 

protection)

15  Blower housing (cast aluminum), with powder coat paint finish

16  Blower wheel

17  Air band  — Only a single adjustment required for setting combustion 

air; see page 7 for starting setting based on input

18  Airflow proving switch — Prevents burner from firing if air is not moving
19  Airflow proving switch sensing line (aluminum) — blower inlet
20  Airflow proving switch sensing line (aluminum) — blower outlet
21  Combination gas valve (with integral gas pressure regulation — set 

for 3½” w.c. outlet pressure)

22  Gas supply entrance — ¾” NPT; 5” w.c. min; 14” w.c. max
23  Flame rod/ignition electrode assembly yoke

Содержание 201GAS

Страница 1: ...trol Carlin Model 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated otherwise this manual must be used only by a quali fied service technician In th...

Страница 2: ...liance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving parts Burner and appliance compone...

Страница 3: ...volts continuous duty rated 11 Primary control Carlin Model 60200FR microprocessor based inter rupted ignition flame supervisory control flame rectification 12 Flame current test jack O F F O N 20100...

Страница 4: ...ate do not vent into a masonry chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe...

Страница 5: ...construction is unusually tight see National Fuel Gas Code NFPA 54 ANSI Z223 1 or B149 1 B149 2 Installation Code for Canadian installations for definition you will need to provide air openings into t...

Страница 6: ...ional forced draft flange Failure to comply could result in severe personal injury death or substantial property damage See page 19 for required dimensions and bolt locations 1 Prepare site prepare bu...

Страница 7: ...C 4 11 14 8 10 9 Burners with welded flange have fixed usable tube length UTL Verify length is correct for the application Burners with adjustable flange Usable tube length UTL varies with air tube l...

Страница 8: ...ect redrill gas orifice when required Turn off power to the burner appliance before proceeding Close main manual gas valve in gas line to burner Then disconnect the ground joint union to allow rotatin...

Страница 9: ...ply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the combination gas valve to gas pressure in excess of 14 inches water column Higher pressure could dam age the valve seat...

Страница 10: ...rner requires a 120 vac 60 hz single phase power supply with at least a 10 amp fuse The current draw will be when equipped with typical motor and Carlin 41800 electronic ignitor approximately 2 The 12...

Страница 11: ...s prepurge timing then start the ignitor Approximately one second later the combination gas valve will open The manometer should show almost no pressure because the main manual gas valve is closed 5 A...

Страница 12: ...restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted Power ON Open al...

Страница 13: ...k at flame through appliance observation port The flame should be a soft blue with well defined orange and yellow tips for natural gas or well defined yellow tips for propane gas If you make air or ga...

Страница 14: ...ontinue with normal operation If switch fails to operate correctly replace the switch and retest NEVER attempt to adjust the air pressure switch setting This could allow unsafe operation of the burner...

Страница 15: ...urner from appliance and inspect diffuser plate ignitor electrode and flame rod see Figures 5 and 6 page 8 Remove ignitor electrode flame rod assembly to clean and adjust if necessary To remove assemb...

Страница 16: ...aced remove the two bolts securing the motor to housing 2 Disconnect the motor wires in the burner junction box 3 Loosen the Allen screw securing the blower to the motor shaft and remove the wheel 4 W...

Страница 17: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Страница 18: ...on of ignitor electrode per Figures 5 and 6 page 8 Adjust if needed Check primary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setti...

Страница 19: ...mbers with negative overfire pres sure For pressurized firing you must obtain a burner with a welded flange designed for use with the appliance You can also use the optional Forced draft flange Failur...

Страница 20: ...e 29652 9938440XX Contact factory 10 Blower wheel 28563 11 Motor 1 6 HP 140 WATT PSC 98611 12 Junction box 4 x 4 with grommet lock washer conduit nipple to burner housing and bracket not shown Contact...

Страница 21: ...ffer from this manual follow the appliance instructions 9 Replacement parts continued Burner is shown with welded flange supplied only on burners ordered for specific appliance applications Other burn...

Страница 22: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 22 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 23: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 23 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 24: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 24 Where appliance instructions differ from this manual follow the appliance instructions...

Отзывы: