Model 201GAS burner — Instruction manual

Carlin part number MN201GAS Rev.  03/14/11

– 13 –

Where appliance instructions differ from this manual, follow the appliance instructions.

5.  Perform checkout procedures   •   fill out certificate

Installer/servicer

Please check off and fill in certificate

  Should overheating or an emergency occur, immediately:

 

•  Shut off main manual gas valve.

 

•  Shut off control switch to burner.

 

Under some circumstances power should remain on for 

circulating  blowers  or  other  equipment.  Determine  proper 

response before attempting start-up. If appliance fails ignition 
on several attempts, close gas valve and use burner blower 
to purge appliance before restart.

Preparation before checkout

  Burner/appliance installed per appliance instruction manual?

  Burner components verified against Table 1, page 7?

  Burner/appliance installed per all applicable codes?

  Installation site has adequate ventilation openings and vent system?

  Gas supply line in good condition and sized correctly?

  All gas line joints sealed with pipe dope listed for use with liquefied 

petroleum gases?

  Gas supply pressure to combination gas valve checked?

  Regulator installed if pressure can exceed 14 inches w.c.? 

  Air purged from gas line?

  Gas piping checked for leaks?

  Wiring installed per burner manual  and appliance instructions?

  Burner inspected and primary control flame failure lockout checked?

  Start-up sequence performed (page 12)?

Make final burner adjustments

Check for leaks in gas piping

  Smell around burner to make sure there is no gas leak in near-burner 

piping. Verify integrity of gas line joints between combination gas 

valve and burner gas inlet tapping using soap suds mixture.

Check/adjust gas valve outlet pressure

  With burner running, check manometer reading for combination gas 

valve outlet pressure. Adjust valve regulator if necessary so the read-

ing is 3.5 inches w.c. for either natural gas or propane gas.

Make final burner adjustments 

(continued)

Inspect flame

  Look at flame through appliance observation port. The flame should 

be a soft blue with well-defined orange and yellow tips for natural 

gas, or well-defined yellow tips for propane gas. (If you make air or 

gas pressure changes later, inspect the flame again.)

Check the firing rate

  Natural gas only — Turn off all other gas appliances connected to 

the gas meter. Use a stopwatch to time the number of seconds for a 

flow of one cubic foot of gas (two revolutions for a one half cubic foot 

per revolution dial, for example). You will also need to know the gas 

heat content in Btu per cubic foot. Determine the actual input from:  

INPUT = (3600 x Btu per cubic foot) ÷ (number of seconds for one cubic 

foot), for firing rate in Btuh. For example, for 1050 Btu per cubic foot 

natural gas, with meter timed at 15.1 seconds for one cubic foot of 

gas: INPUT example = (3600 x 1050) ÷ (15.1) = 250,500 Btuh. Firing 

rate should be within ± 5% of rated input for the appliance. Adjust 

the combination gas valve pressure regulator if necessary to obtain 

the correct firing rate. Valve outlet pressure must not be lower than 

3.2 inches w.c. nor higher than 3.8 inches w.c.

  For propane gas, contact your propane supply for procedure to verify 

firing rate.

Check combustion using instruments

  Insert test probe into appliance vent outlet to sample flue products. 

The results should show CO

2

 or O

2

 as follows:

  If the combustion results are outside the range above, and the firing 

rate of the burner is within 5% of rated input, open or close the air 

band until the CO

2

 (or O

2

) are acceptable.

  After CO

2

 (O

2

) tests are completed satisfactorily, measure 

flue products for carbon monoxide (CO) concentration. The 

CO must not exceed 50 ppm adjust to “air free”, or other if 

specified by local codes.

  Check pressure overfire in appliance. Refer to appliance manual for 

recommended reading and barometric damper instructions for proper 

setting of damper.

  Do not attempt to confirm combustion simply by inspecting 

the flame visually. You must use combustion test instruments. 

Failure  to  properly  verify/adjust  combustion  could  allow 

unsafe operation of the burner, resulting in severe personal 
injury, death or substantial property damage.

Содержание 201GAS

Страница 1: ...trol Carlin Model 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated otherwise this manual must be used only by a quali fied service technician In th...

Страница 2: ...liance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving parts Burner and appliance compone...

Страница 3: ...volts continuous duty rated 11 Primary control Carlin Model 60200FR microprocessor based inter rupted ignition flame supervisory control flame rectification 12 Flame current test jack O F F O N 20100...

Страница 4: ...ate do not vent into a masonry chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe...

Страница 5: ...construction is unusually tight see National Fuel Gas Code NFPA 54 ANSI Z223 1 or B149 1 B149 2 Installation Code for Canadian installations for definition you will need to provide air openings into t...

Страница 6: ...ional forced draft flange Failure to comply could result in severe personal injury death or substantial property damage See page 19 for required dimensions and bolt locations 1 Prepare site prepare bu...

Страница 7: ...C 4 11 14 8 10 9 Burners with welded flange have fixed usable tube length UTL Verify length is correct for the application Burners with adjustable flange Usable tube length UTL varies with air tube l...

Страница 8: ...ect redrill gas orifice when required Turn off power to the burner appliance before proceeding Close main manual gas valve in gas line to burner Then disconnect the ground joint union to allow rotatin...

Страница 9: ...ply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the combination gas valve to gas pressure in excess of 14 inches water column Higher pressure could dam age the valve seat...

Страница 10: ...rner requires a 120 vac 60 hz single phase power supply with at least a 10 amp fuse The current draw will be when equipped with typical motor and Carlin 41800 electronic ignitor approximately 2 The 12...

Страница 11: ...s prepurge timing then start the ignitor Approximately one second later the combination gas valve will open The manometer should show almost no pressure because the main manual gas valve is closed 5 A...

Страница 12: ...restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted Power ON Open al...

Страница 13: ...k at flame through appliance observation port The flame should be a soft blue with well defined orange and yellow tips for natural gas or well defined yellow tips for propane gas If you make air or ga...

Страница 14: ...ontinue with normal operation If switch fails to operate correctly replace the switch and retest NEVER attempt to adjust the air pressure switch setting This could allow unsafe operation of the burner...

Страница 15: ...urner from appliance and inspect diffuser plate ignitor electrode and flame rod see Figures 5 and 6 page 8 Remove ignitor electrode flame rod assembly to clean and adjust if necessary To remove assemb...

Страница 16: ...aced remove the two bolts securing the motor to housing 2 Disconnect the motor wires in the burner junction box 3 Loosen the Allen screw securing the blower to the motor shaft and remove the wheel 4 W...

Страница 17: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Страница 18: ...on of ignitor electrode per Figures 5 and 6 page 8 Adjust if needed Check primary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setti...

Страница 19: ...mbers with negative overfire pres sure For pressurized firing you must obtain a burner with a welded flange designed for use with the appliance You can also use the optional Forced draft flange Failur...

Страница 20: ...e 29652 9938440XX Contact factory 10 Blower wheel 28563 11 Motor 1 6 HP 140 WATT PSC 98611 12 Junction box 4 x 4 with grommet lock washer conduit nipple to burner housing and bracket not shown Contact...

Страница 21: ...ffer from this manual follow the appliance instructions 9 Replacement parts continued Burner is shown with welded flange supplied only on burners ordered for specific appliance applications Other burn...

Страница 22: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 22 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 23: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 23 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 24: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 24 Where appliance instructions differ from this manual follow the appliance instructions...

Отзывы: