background image

Contents

PLEASE read this first

.......................................................... 2

Codes and standards........................................................... 2
201GAS burner at-a-glance ................................................ 3

Prepare site •  prepare burner •  mount burner

 .............. 4

Install gas piping .................................................................. 9
Wire burner ......................................................................... 10

Check system  •  start-up burner/appliance

 .................. 11

Perform checkout procedures  •  fill out certificate

..... 13

Maintenance and service procedures ........................... 16
Troubleshooting ................................................................. 17

Dimensions and mounting information

........................... 19

Replacement parts

............................................................. 20

Instruction manual

Ratings

Input

.................................................150,000 to 399,000 Btuh

Fuels

.........................................Natural gas or propane gas

 

Max. supply pressure ..........................14 inches w.c.

 

Min. supply pressure .............................5 inches w.c.

 

Manifold pressure...............................3.5 inches w.c.

Electrical

: Power ...........................................

120V/60 Hz/1-Phase

 Motor.....................................

1/6 or 1/4 HP, 3450 RPM

 Current ...................................

Approx. 2.5 or 4.4 amps

Ignition

........................Carlin Model 41800 solid state ignitor

Control

........

Carlin Model 60200FR microprocessor control

Agencies

:  ..........................................................................UL  Listed  

 

Installer/servicer

 — Except where specifically 

stated otherwise, this manual must be used only by a 

quali-

fied service technician

. (In the state of Massachusetts, this 

product must be installed by a licensed Plumber or Gas Fitter.) 
Failure to comply with this or other requirements in this manual 
could result in severe personal injury, death or substantial 
property damage.

 

User 

— Refer only to 

User’s Information

 booklet for 

information regarding operation of this burner. The burner 

Instruction Manual

 is intended only for your service techni-

cian. The burner and heat exchanger must be inspected and 
started at least annually by your service technician.

70 Maple Street 

East Longmeadow, MA  01028

Ph  413-525-7700 

Fx  413-525-8306

Carlin Combustion Technology, Inc.

T

ech

 

support

   800-989-2275

carlincombustion.com

©

 

Copyright 2011 — Carlin Combustion Technology, Inc.

Содержание 201GAS

Страница 1: ...trol Carlin Model 60200FR microprocessor control Agencies UL Listed Installer servicer Except where specifically stated otherwise this manual must be used only by a quali fied service technician In th...

Страница 2: ...liance service When servicing the burner Disconnect electrical supply to burner before attempting to service to avoid electrical shock or possible injury from moving parts Burner and appliance compone...

Страница 3: ...volts continuous duty rated 11 Primary control Carlin Model 60200FR microprocessor based inter rupted ignition flame supervisory control flame rectification 12 Flame current test jack O F F O N 20100...

Страница 4: ...ate do not vent into a masonry chimney that has one or more sides exposed to the outside Install a listed stainless steel liner to vent the flue products A defective vent system could result in severe...

Страница 5: ...construction is unusually tight see National Fuel Gas Code NFPA 54 ANSI Z223 1 or B149 1 B149 2 Installation Code for Canadian installations for definition you will need to provide air openings into t...

Страница 6: ...ional forced draft flange Failure to comply could result in severe personal injury death or substantial property damage See page 19 for required dimensions and bolt locations 1 Prepare site prepare bu...

Страница 7: ...C 4 11 14 8 10 9 Burners with welded flange have fixed usable tube length UTL Verify length is correct for the application Burners with adjustable flange Usable tube length UTL varies with air tube l...

Страница 8: ...ect redrill gas orifice when required Turn off power to the burner appliance before proceeding Close main manual gas valve in gas line to burner Then disconnect the ground joint union to allow rotatin...

Страница 9: ...ply pressure 14 inches w c Minimum supply pressure 5 inches w c Do not expose the combination gas valve to gas pressure in excess of 14 inches water column Higher pressure could dam age the valve seat...

Страница 10: ...rner requires a 120 vac 60 hz single phase power supply with at least a 10 amp fuse The current draw will be when equipped with typical motor and Carlin 41800 electronic ignitor approximately 2 The 12...

Страница 11: ...s prepurge timing then start the ignitor Approximately one second later the combination gas valve will open The manometer should show almost no pressure because the main manual gas valve is closed 5 A...

Страница 12: ...restart Releasing the button before the LED s turn off will cause the control to remain in latch up The 60200FR control will not reset from lockout or latch up if power is interrupted Power ON Open al...

Страница 13: ...k at flame through appliance observation port The flame should be a soft blue with well defined orange and yellow tips for natural gas or well defined yellow tips for propane gas If you make air or ga...

Страница 14: ...ontinue with normal operation If switch fails to operate correctly replace the switch and retest NEVER attempt to adjust the air pressure switch setting This could allow unsafe operation of the burner...

Страница 15: ...urner from appliance and inspect diffuser plate ignitor electrode and flame rod see Figures 5 and 6 page 8 Remove ignitor electrode flame rod assembly to clean and adjust if necessary To remove assemb...

Страница 16: ...aced remove the two bolts securing the motor to housing 2 Disconnect the motor wires in the burner junction box 3 Loosen the Allen screw securing the blower to the motor shaft and remove the wheel 4 W...

Страница 17: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 17 Where appliance instructions differ from this manual follow the appliance instructions 7 Troubleshooting...

Страница 18: ...on of ignitor electrode per Figures 5 and 6 page 8 Adjust if needed Check primary voltage to ignitor If ignitor receives 120 VAC and doesn t generate spark replace ignitor Airflow Check air band setti...

Страница 19: ...mbers with negative overfire pres sure For pressurized firing you must obtain a burner with a welded flange designed for use with the appliance You can also use the optional Forced draft flange Failur...

Страница 20: ...e 29652 9938440XX Contact factory 10 Blower wheel 28563 11 Motor 1 6 HP 140 WATT PSC 98611 12 Junction box 4 x 4 with grommet lock washer conduit nipple to burner housing and bracket not shown Contact...

Страница 21: ...ffer from this manual follow the appliance instructions 9 Replacement parts continued Burner is shown with welded flange supplied only on burners ordered for specific appliance applications Other burn...

Страница 22: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 22 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 23: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 23 Where appliance instructions differ from this manual follow the appliance instructions...

Страница 24: ...Model 201GAS burner Instruction manual Carlin part number MN201GAS Rev 03 14 11 24 Where appliance instructions differ from this manual follow the appliance instructions...

Отзывы: