17
ENG
“ultimateSAM - user” +03U0070EF - rel. 2.0 - 20150301
A complete list of available kits, as well as information on other features, is
provided in Tab.3.b.
2
4
3
5
6
SAKT
xx
x
x 0
x
1
ID prefix
Material:
F =
S =
Iron
SS
Type:
S =
T =
Condensate separator
Trap & strainer assembly
Size:
15 =
20 =
25 =
32 =
40 =
44=
50=
65=
84=
DN 15 flange
DN 20 flange
DN 25 flange
DN 32 flange
DN 40 flange
1” pipe thread
DN 50 flange
DN 65 flange
2” pipe thread
Region:
U =
0 =
North America
Other
---
---
Tab. 3.a
Table 3.b provides a complete listing of all of the traps, strainers, and
other accessories available for the use with the ultimateSAM distributor. In
addition, the table provides information on the size and type of inlet-outlet
connection for each accessory.
Inlet-Outlet Connections
Material, Type, Region Codes
Size
“****FT**0*
****FS**0*
****FT**U*
****ST**U*
SAKT**15*0
Flange DN 15
n/a
n/a
SAKT**20*0
Flange DN 20
n/a
n/a
SAKT**25*0
Flange DN 25
n/a
n/a
SAKT**32*0
Flange DN 32
n/a
n/a
SAKT**40*0
Flange DN 40
n/a
n/a
SAKT**44*0
n/a
1” NPT Female
1”NPT Female
SAKT**50*0
Flange DN 50
n/a
n/a
SAKT**65*0
Flange DN 65
n/a
n/a
SAKT**84*0
n/a
2” NPT Female
2” NPT Female
Tab. 3.b
Before installing an optional flanged trap and strainer kit, be sure that
the flange size matches the flange on the control valve. For an optional
threaded trap and strainer kit, be sure that the kit is properly sized for the
control valve. (Refer to the design manual for more information.)
Table 3.c lists the items and quantity of threaded fittings that are included
in each threaded trap and strainer kit. Flanged trap and strainer kits are
fully integrated. See figure 3.c, and section 9, figure 9.x -Trap, strainer, and
separators kits for more details.
Item List for SAKT*T**U0
Item (NPT)
SAKT*T44*0
SAKT*T84*0
Y-type stainer
1 (1”)
1 (1”)
F&T trap
1 (¾”)
1 (¾”)
Bushing F-M (size)
1 (¾”x1”)
1 (¾”x2”)
Elbow F-M (size)
1 (¾”)
1 (¾”)
Elbow F-F (size)
1 (1”)
1 (2”)
Nipple M-M (size)
2 (¾”x6”)
1 (1”x3”)
1 (1”x6”)
2 (¾”x6”)
1 (2”x3”)
1 (2”x6”)
Tee F-F-F (size)
1 (1”)
1 (2”)
Union F-F (size)
1 (¾”x¾”)
1 (¾”x¾”)
Tab. 3.c
3.3 Inlet drains for distributors connected to
atmospheric steam supplies
When used with an atmospheric humidifier, as shown in (Fig.3.e and Fig.
3.f ), an inlet trap may not be needed on the ultimateSAM distributor. In
a typical installation, the condensate in the connecting hose drains back
to the humidifier. In special situations when the condensate cannot drain
back to the humidifier, an inlet trap may be needed to prevent significant
amounts of condensate from entering the distributor.
Fig. 3.e
20° min.
Fig. 3.f
Note:
The adapters and steam hoses shown above are available as
options. The “P” drains are not provided as part of the ultimateSAM
system.
Содержание ultimateSAM SA 2 Series
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 27: ...27 ENG ultimateSAM user 03U0070EF rel 2 0 20150301 ...
Страница 30: ...30 ENG ultimateSAM user 03U0070EF rel 2 0 20150301 Note ...
Страница 31: ......
Страница 32: ......
Страница 34: ......
Страница 36: ......
Страница 57: ...27 FRE ultimateSAM user 03U0070EF rel 2 0 20150301 ...
Страница 60: ...30 FRE ultimateSAM user 03U0070EF rel 2 0 20150301 Note ...
Страница 61: ......