20
ENG
“SmartCella 3PH” +0500119IE - rel. 1.2 - 10.03.2017
Symbol
Code
Parameter
UOM
Type
Min.
Max.
Def.
d0
Type of defrost
0: heater by temperature
1: hot gas by temperature
2: heater by time (Ed1, Ed2 not shown)
3: hot gas by time (Ed1, Ed2 not shown)
4: heater with thermostat by time (Ed1, Ed2 not shown)
fl ag
C
0
4
0
dI
Maximum time between consecutive defrosts
0= defrost not performed
ore
F
0
250
8
dt1
End defrost temperature probe 2
°C/°F
F
-50
200
4.0
dt2
End defrost temperature probe 3
°C/°F
F
-50
200
4.0
dP1
Maximum defrost duration
min
F
1
250
30
dP2
Maximum aux evaporator defrost duration
min
F
1
250
30
d3
Defrost activation delay
min
C
0
250
0
d4
Defrost at start-up
0: disabled 1: enabled
fl ag
C
0
1
0
d5
Defrost delay at start-up (if d4=1) or from dI
min
C
0
250
0
d6
Display on terminal during defrost
0: temperature alternating with dEF
1: display disabled
2: dEF
-
C
0
2
1
dd
Dripping time after defrost (fans off )
min
F
0
15
2
d8
High temperature alarm bypass time after defrost (and door open)
ore
F
0
250
1
d8d
Alarm bypass time after door open
min
C
0
250
0
d9
Defrost priority over compressor protectors
0: protection times c1, c2 and c3 applied
1: protection times c1, c2 and c3 ignored
fl ag
C
0
1
0
d/1
Display defrost probe 1
°C/°F
F
-
-
-
d/2
Display defrost probe 2
°C/°F
F
-
-
-
dC
Time base for defrost
0: dI in hours, dP1 and dP2 in minutes
1: dI in minutes, dP1 and dP2 in seconds
fl ag
C
0
1
0
d10
Defrost time with Running time
0= function disabled
ore
C
0
250
0
d11
Running time defrost temperature threshold
°C/°F
C
-20
20
1.0
d12
Advanced defrosts
-
C
0
3
0
dn
Nominal defrost duration
-
C
1
100
65
dH
Proportional factor for variation of dI
-
C
0
100
50
A0
Alarm and fan diff erential
°C/°F
C
0.1
20
2.0
A1
Alarm thresholds (AL and AH) relative to the set point or absolute
0: AL and AH thresholds relative to the set point
1: AL and AH absolute thresholds
fl ag
C
0
1
0
AL
Low temperature alarm threshold
°C/°F
F
-50
200
0.0
AH
High temperature alarm threshold
°C/°F
F
-50
200
0.0
Ad
High and low temperature alarm delay
min
F
0
250
120
A4
Confi guration of digital input 1 (DI1)
0: Not active
1: Immediate external alarm
2: Delayed external alarm
3: If model M select probes
3: Other models enable defrost
4: Start defrost
5: Door switch with comp. and fans off
6: Remote ON/OFF
7: Curtain switch
8: Low pressure switch
9: Door switch with fans off
10: Direct/reverse operation
11: Light sensor
12: Activate aux output
13: Door switch with compressor and fans off , light not managed
14: Door switch with fans off and light not managed
-
C
0
14
5
A5
Confi guration of digital input 2 (DI2) / As per A4
-
C
0
14
1
A6
Stop compressor on external alarm
min
C
0
100
0
A7
Digital alarm input delay
min
C
0
250
0
A8
Enable alarms Ed1 and Ed2 (defrost ended by timeout)
0: Ed1 and Ed2 signals enabled
1: Ed1 and Ed2 signals disabled
fl ag
C
0
1
0
A9
Confi guration of digital input 3 (DI3) / As per A4
-
C
0
14
0
Ac
High condenser temperature alarm threshold
°C/°F
C
0.0
200
70
AE
High condenser temperature alarm diff erential
°C/°F
C
0.1
20
10
Acd
High condenser temperature alarm delay
min
C
0
250
0
AF
Light sensor OFF time
s
C
0
250
0
ALF
Frost protection alarm threshold
°C/°F
C
-50
200
-5
AdF
Frost protection alarm delay
min
C
0
15
1
Содержание SmartCella 3PH
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 11: ...11 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Codici WP00B57B20 WP00B47B20 Fig 2 b...
Страница 12: ...12 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Circuito ausiliario Fig 2 c...
Страница 13: ...13 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...
Страница 24: ......
Страница 26: ......
Страница 31: ...11 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Part numbers WP00B57B20 WP00B47B20 Fig 2 b...
Страница 32: ...12 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Auxiliary circuit Fig 2 c...
Страница 33: ...13 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...
Страница 43: ......