1.7 Technical
specifi cations
Specifi cations
WP00B14A10
WP00B24A10
WP00B34A10
WP00B44A10
WP00B47B20
WP00B57B20
Power supply
400V 3~ +N+E 50/60Hz
Max compressor power
5.5HP
7.5HP
Protectors Power
Disconnect
switch
40A
Evaporator, condenser and
defrost protection
Circuit
breaker
10A
16A
Compressor protection
Adjustable
motor
protector
1.6-2.5A
2.5-4A
4-6.3A
6.3-10A
10-16A
Auxiliary circuit protection Circuit
breaker
6A
Inputs
Room temperature probe
ST1
NTC
Defrost probe
ST2
NTC
Door switch (or additional
probe)
MS1
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
S3 (probe 3)
NTC
Confi gurable digital input
(or additional probe) *
DI3
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
NTC
Safety thermostat
yes
Thermal overload evaporator fan
yes
Evaporator / condenser / defrost
protection alarm
yes
Compressor / high pressure switch /
compressor Kriwan protection alarm
yes
Outputs
Evaporator fan
230V 1~+N+E 500W 2.5A AC3
400V 3~+N+E 2kW 3.3A AC3
Condenser fan
230V 1~+N+E 800W 3.9A AC3
230V 1~+N+E 800W 3.9A AC3
Defrost
400V 3~+T 6kW 9A AC1
400V 3~+T 9kW 13A AC1
Light (or AUX, confi gurable)
230V 1~+N+E 800W 3.9A AC3
230V 1~+N+E 800W 3.9A AC3
Solenoid valve
yes
Compressor oil heater
yes
Tab. 1.c
* To be connected directly to terminals 11 and 12 on the electronic board.
1.8 Option part numbers
P/N
Description
IROPZDSP00
remote display interface
IR00XGD000
remote repeater display
IROPZ485S0
RS485 serial card with automatic polarity recognition (+/-)
IROPZKEY00
parameter program. key with extended memory, 12 V
batteries
PSTCON0*B0 repeater display conn. cables (*: 1= 1.5 m; 3= 3 m; 5= 5m)
1.9 Assembly and connections
1.
With reference to the drilling template, drill the four fastening holes
in the wall:
•
Unscrew the six fastening screws on the front panel
•
Remove the front panel
•
Fix the panel to the wall using screws of suitable length, based on
the thickness of the wall
2.
Connect the power cables, the load power cables, the probes and
the remaining inputs/outputs to the terminal block on the panel, as
shown in the wiring diagram (see page 10/11)
3.
Before starting installation, the motor protector should be calibrated
based on eff ective compressor power consumption, with reference
to the compressor’s rated data
4.
Arm the circuit breakers and the motor protector
5.
Close the front panel using the six screws
6.
Power the panel on
7.
Arm the main switch (yellow/red)
Warning
•
separate the power cables (power supply, loads) from the signal cables
(probes, digital inputs) and the serial cable
•
use cables that are suitably sized for the current they carry
•
connect the terminal marked PE to the mains power supply earth
•
after having powered the three-phase expansion, check correct
current draw of the various loads
Содержание SmartCella 3PH
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 11: ...11 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Codici WP00B57B20 WP00B47B20 Fig 2 b...
Страница 12: ...12 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Circuito ausiliario Fig 2 c...
Страница 13: ...13 ITA SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...
Страница 24: ......
Страница 26: ......
Страница 31: ...11 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 1 2 Part numbers WP00B57B20 WP00B47B20 Fig 2 b...
Страница 32: ...12 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 2 2 Auxiliary circuit Fig 2 c...
Страница 33: ...13 ENG SmartCella 3PH 0500119IE rel 1 2 10 03 2017 Fig 2 d...
Страница 43: ......