0DLQVFUHHQ
10/03/2000 18:00 SMS
Installation name
oooooo
ooo
oooooo
ooo
o
Row 1
The first row displays the current date and time, in addition the character in the top right indicates the status of the modem (if no
modem is present, no symbol is displayed). The symbols used are:
dd
dialling number for data transmission
Dd
waiting for connection after dialling number for data transmission
Dsm
dialling number to send SMS message by PSTN modem
Dfx
waiting for connection after dialling number to send fax
F
Fax transmission in progress
f
Fax transmission in progress
h disconnecting
i
initialising modem
net
GSM modem only: request network information and signal intensity, and registration
O
Connection between modems, wait for login from data centre
p connecting
R
ring received: waiting for connection
SMS
Sending SMS message, GSM and PSTN
Pn?
GSM modem only: Request PIN status from modem
Pn
GSM modem only: Send PIN
PIN
GSM modem only: PIN error, the modem cannot be used!
W
waiting for call (normal operating status)
Row 2
On the second row, if there are no active alarms, the string “installation name” is displayed, as set by the user during
configuration, or alternatively the text “Active alarms:” followed by a number that represents the number of alarms present.
Rows 3 and 4
The symbols of the peripherals from 1 to 32 indicate:
empty rectangle
periph. on-line without alarms
filled rectangle, flashing
periph. on-line with active alarms
rectangle with x inside
periph. on-line, but the user has disabled the alarms for
maintenance
X
periph. off-line
-
not present in configuration
An empty space separates the symbols into groups of 8, so as to assist in identifying the addresses of the peripherals.
The symbol in the lower right indicates the status of the printer module:
empty rectangle with horizontal line inside
printer module on-line without alarms
filled rectangle, flashing
printer module on-line, but the printer is blocked; this is the
only print alarm managed by PlantWatch, and in fact may be
generated only following a print action that is not satisfied
rectangle with x inside
printer module off-line
If the character “!” is displayed to the side of the empty printer rectangle, the printer is off-line or an error has occurred; this may
be due to no paper, the user having put the printer off-line, the printer being off or the paper being blocked. It is a signal only,
and no data is saved to the event log. In fact, the symbol “!” does not represent an alarm until PlantWatch starts printing, in
which case an alarm is generated. This may be signalled remotely or not, depending on the configuration (see Chap.
$ODUP
PDQDJHPHQW
).