7
+0500040RU - 1.2 - 07.06.2011
ENG
The versions with valve driver, with or without Ultracap module, have the same number, type and confi guration of I/Os as the
Medium version.
D
igital inputs
type
ID1 to ID18 optically-isolated (voltage contact), B4, B5, B9, B10 non optically-
isolated (free contact)
maximum number voltage inputs optically-
isolated
8: SMALL; 14: MEDIUM & EXTRALARGE ; 18: LARGE. As per combinations shown
below:
no. 24 Vac opto inputs
50/60 Hz o 24 Vdc
no. 24 Vac/Vdc or 230 Vac opto
inputs (50/60 Hz)
total
inputs
SMALL
8
none
8
MEDIUM/
EXTRALARGE
12
2
14
LARGE
14
4
18
maximum number inputs free contact not
optically-isolated
2: SMALL, MEDIUM & EXTRALARGE (B4 and B5);
4: LARGE (B4, B5, B9, B10)
Classifi cation of measurement circuits (IEC EN
61010-1)
Category 1 (J5, J7, J20) 24 Vac/Vdc - Category 3 (J8, J19) 230 Vac
Voltage-free digital input current
(B4, B5, B9, B10)
5 mA
Digital input current with 24 Vac voltage signal
5 mA
Digital input current with 230 Vac voltage signal 5 mA
WARNINGS:
- IDH digital inputs 230 Vac 50/60 Hz (10/-15%) protected by a single 500 mAT fuse;
- the two 230/24 Vac inputs at J8 and J12 have the same common and so both will be either
24 Vac/Vdc or 230 Vac. There is double insulation between the two inputs and the rest of the controller;
- the external contact connected to the digital inputs must have a minimum current of 5 mA;
- for DC digital inputs (Vdc), either the + or the – can be connected to the common (IDC1).
Note:
separate as much as possible the probe signal and digital input cables from the cables to inductive loads and power cables,
to avoid possible electromagnetic disturbance.
F
ast digital input specifi cations (
B
4 and
B
5 voltage-free contact)
When confi gured as fast digital inputs, B4 and B5 can measure a signal with a maximum frequency of 2 KHz and a resolution of ±1
Hz. This is possible as the BIOS provides the application program two pairs of variables that count the zero crossing of the input
signal and the corresponding frequency in Hz.
A
nalogue inputs
analogue conversion
10-bit A/D converter embedded in CPU
type
universal: (inputs B1, B2, B3, B6, B7, B8) CAREL NTC temperature sensor
(-50T90 °C; R/T 10 k
at 25 °C),
NTC HT 0T150 °C, voltage: 0 to 1 Vdc, 0 to 5 V ratiometric or 0 to 10 Vdc, current: 0 to 20 mA or 4
to 20 mA, selectable via software. Input resistance for 0 to 20 mA= 100
passive: (inputs B4, B5, B9, B10) CAREL NTC temp. sensor (see universal
),
PT1000 (-100T200 °C; R/T 1000
at 0°C) or volt.-free digital input (5 mA), selected via software;
maximum number
5: SMALL; 8: MEDIUM & EXTRALARGE; 10: LARGE
time constant for each input
0,5 s
precision
± 0.3 % of full scale
class. of measurement circuits
(IEC EN 61010-1)
Category 1
input impedance
NTC
10 kΩ
4-20 mA
100 Ω
0-1 V
100 kΩ
0-5 V
20 kΩ
0-10 V
12,7 kΩ
PT1000
10 kΩ
WARNING:
the 21 Vdc available at teVdc (J2) can be used to power any active probes; the maximum current is 150 mA,
protected against short-circuits. To power the 0 to 5 Vdc ratiometric probes, use the +5V
REF
(Imax: 60 mA) available at terminal J24.
Only use these voltages to power the active probes connected to pCO