5
+030220575 - 1.1 - 04.12.2014
ENG
Fig. 1.a
1.1 Smooth lines on MPXPRO: how it works
The main target of the Smooth lines function, available on MPXPRO version 3.2 and higher, is to keep the
control temperature very stable around the set point, avoiding frequent ON/OFF cycles of cooling request.
The parameters involved in the Smooth lines confi guration are listed in the following table:
Parameter name
Menu
Description
Visibility
St
CtL
Control set point
PVPRO & User interface
rd
CtL
Control diff erential
PVPRO & User interface
P3
Eud
Superheat set point
PVPRO & User interface
PHS
Eud
Positive SH off set
PVPRO & User interface
PLt
Eud
Off set below set point for cut-off
PVPRO & User interface
PSI
Eud
Integral time
PVPRO & User interface
PSM
Eud
Enable function
PVPRO & User interface
PSP
Eud
Proportional coeffi
cient
PVPRO & User interface
PSd
-
Derivative time
PVPRO
TSH
-
Superheat threshold
PVPRO
FSt
-
Superheat averaging time window
PVPRO
Tab. 1.a
The function works as follows: when the control temperature reaches the set point + half of the diff erential,
the control is not stopped, and a special PID algorithm increases the working superheat set point in order
to modulate the expansion valve. This special algorithm works until the control temperature exceeds St –
PLt.
1. INTRODUCTION