A4=5: DOOR SWITCH
By setting A4 = 5 it is possible to control the switch at the store-room door. When the switch is opened the
compressor is switched off. If the IR32C or IR32P versions with S90OEM4PWR are being used, the control
automatically also cuts off the evaporator fan (often positioned above the door), and, if the parameter H1=0
referring to the room light automatically goes on via output AUX. When the door is closed (and also the
Multifunction contact), the equipment resumes the previous operation, delaying any temperature alarm by a
number of hours equivalent to the value of d8. On re-starting the compressor however, any protective time
constraints selected will be respected (see c parameters).  Note: even if the fan is controlled by the fan
controller (see category F), the fans will be shut down.

The table below summarises the functions served by the digital input according to the values assigned to A4
and to the equipment version being used.

Parameter value

Function

M

T (*)

S

X (**)

Y

C

P

0

Input not active

1

Immediate external alarm
Contact open = alarm active
closed = inactive

2

External alarm with delay
Contact open = alarm active
closed = inactive

3

Sensor selection
Contact open = first sensor
closed = second

Direct/Reverse
Contact open = direct
closed = reverse

Ready to defrost
Contact open = defrost
possible
closed = impossible

4

Start of defrost

5

Door switch
Contact open = door open
closed = door closed

Default values

3

0

0

0

0

0

0

Note: (*) T refers to the IR32S version when used in thermostatic operation, i.e. with parameter H1=0.
         (**) X refers to the IR32Y version with time defrost as well as temperature, i.e. with parameter H1=0.

A5: This parameter is not controlled on the versions being considered and must be lept at 0.

Default: A5=0 Refers to models IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.

Note: see the following chapter “Notes for the new release” to a more detailed description of this parameter
functionalities, effective for the instrument with serial number greater than 100,000)

A6: Cut-out of compressor by external alarm

The function of this parameter is similar to that of parameter c4 (duty setting). As well as acting on the
sensor alarm, it acts on the external alarm via the multi-function input (A4=1 or A4=2). When an external
alarm occurs (whether immediate or delayed), the compressor works for a period equivalent to the value
given to parameter A6 (in minutes), while remaining off for a fixed period of 15 minutes. When given two
particular values A6 serves the following functions: A6=0: the compressor always remains off; A6=100: the
compressor always remains on. The fans continue to be controlled by according to the selected parameters
(see category F). If the duty setting for the sensor alarm (parameter c4) is also active, controil uses
the value of c4.
Default: A6=0 (compressor cuts out if there is an external alarm). Available on IR32S, IRDRSE/S0, IR32Y,
IR32P, IR32C and IRDRC.

A7: Delay in registration of external alarm (multi-function input)

Sets the delay (in minutes) in registering the external alarm when A4=2.
Default: A7=0    Available on IR32S, IRDRSE/S0, IR32Y, IR32P, IR32C and IRDRC.

Содержание IR32C

Страница 1: ...ers for the temperature regulation 18 c parameters for the compressor management 19 d parameters for the defrost management 21 A parameters for the alarm control 24 F parameters for controlling evapor...

Страница 2: ...frost You can select the time interval between successive defrost cycles as well as their duration Defrosting will be stopped when the defrost end temperature is reached it is necessary to connect a d...

Страница 3: ...flash in case of external problems relative to the output see Multifunction input or during active current procedures Buzzer All controllers come complete with an alarm buzzer upon request Remote con...

Страница 4: ...rial of the keypad ensure a very high protection index IP65 All controllers come complete with a flat gasket that contributes to increase the protection index of the panel housing the controller Faste...

Страница 5: ...e the decimal part of the degree by modifying the value of the 6 parameter The display will show one of the following values codes depending on the function being performed normal functioning value me...

Страница 6: ...onds together with the button no 9 allows you to enter the C parameters section Configuration if pressed when turning ON the instrument activates the RESET procedure displays and or selects the SET PO...

Страница 7: ...efrost duration 30 minutes and 8 hour intervals between successive defrost cycles The temperature displayed during the defrost cycle will be that acquired before the beginning of the cycle At the end...

Страница 8: ...r sharing routes with power leads As defrost sensors use only guaranteed IP67 sensors place the sensors with the bulb upright in a position to assist drainage of any condensation which may occur Note...

Страница 9: ...r important parameters For all the models As indicated above all Infrared instruments have been programmed to detect both the high and the low temperature alarm In the event of abnormal conditions the...

Страница 10: ...dI Time interval between defrost cycles defrost cycles occur periodically depending on the time intervals hours set through the dl parameter When the time interval is 0 dl 0 the defrosting cycle is ne...

Страница 11: ...word appears confirm pressing the display shows the code of the first modifiable parameter that is C How to modify the parameters Modifying parameters after having displayed the first parameter either...

Страница 12: ...uirements Also the 0 parameter will be displayed thus allowing you to select the type of sensor you want to use NTC or PTC Important after the RESET procedure the values of each single parameter will...

Страница 13: ...5V alkaline batteries type UM 4 AAA IEC R03 Case plastic Dimensions 60x160x18mm Storage 25 70 C Operating temperature 0 50 C Transmission Infrared Weight 80g without batteries Keypad description On th...

Страница 14: ...rameter 1 goes to the next parameter 2 increases the displayed data parameters selection phase AUX activates deactivates the auxiliary output 1 goes to the previous parameter 2 decreases the displayed...

Страница 15: ...press PRG to exit and memorize all modifications press CANCEL to exit without memorizing the previous modifications do not press any button for at least 60 seconds TIME OUT In this way the previous mo...

Страница 16: ...hich intentionally complicates access to Configuration parameters in order to prevent accidental changes or any that might be made by unauthorised persons Type C parameters are in fact those which alt...

Страница 17: ...cal values 4 3 2 1 0 1 2 3 30 25 20 15 10 5 0 5 10 15 20 25 30 Variation of Carel NTC probe Variation of PTC 985 Ohm probe at 25 C It is nevertheless possible to use Infrared equipment with PTC sensor...

Страница 18: ...ensors IR32M IR32Y IR32C IDRDC and IR32P this parameter allows a choice as to whether temperature is regulated by reference to one sensor alone P1 on the IR32M or by reference to a weighted average of...

Страница 19: ...value that can be given to the setpoint Using this parameter prevents the user from fixing a setpoint lower than the value assigned to r1 Default 40 Available on IR32S IRDRSE S0 IR32Y IR32P IR32C and...

Страница 20: ...less than six minutes the compressor will not start up In the case of installations with more than one compressor the parameter A0 can also be used to avoid simultaneous start ups of several compress...

Страница 21: ...s during this phase After this periodic operation commences according to the operating time set under c4 If the sensor defect alarm is signalled while the equipment is defrosting or in continuous cycl...

Страница 22: ...ms are over ridden during defrosting Default 8 hours Available on IR32S IRDRSE S0 IR32Y IR32P IR32C and IRDRC Parameter with direct access from remote control dt SETPOINT for temperature at end of def...

Страница 23: ...tion digital input see parameter A4 Defrosting will be activated when the timer contacts close Where several units are connected to the same timer we suggest to use the parameter d5 to delay the vario...

Страница 24: ...is fitted When the parameter d has been selected pressing will not allow the value to be changed but the value registered by the defrost sensor can be read Available on IR32Y IR32P IR32C and IRDRC Pa...

Страница 25: ...int i e the requested operating temperature that is permitted The low temperature alarm is given as follows Low temperature alarm setpoint value of AL A0 Note that changing the setpoint automatically...

Страница 26: ...y signal see alarm A1 sound the buzzer if so designed and initiates the following actions compressor functions according to values under parameter A6 blocking compressor by external alarm fans continu...

Страница 27: ...ith these installations it is necessary to defrost an island at a time so at anyone moment some islands will be empowered to defrost and others inhibited Another use for this function is to inhibit de...

Страница 28: ...0 0 Note T refers to the IR32S version when used in thermostatic operation i e with parameter H1 0 X refers to the IR32Y version with time defrost as well as temperature i e with parameter H1 0 A5 Th...

Страница 29: ...apter Notes for the new release to a more detailed description of this parameter functionalities effective for the instrument with serial number greater than 100 000 F1 Fan cut out temperature operati...

Страница 30: ...defrosting thus avoiding forcing warm air into the interior of the refrigerator Where the fan controller is in command it is not necessary to select a time for Fd as the controller starts the fans wh...

Страница 31: ...y output for lighting anti mist fan or other on off function or as an alarm output In the first case auxiliary output it is possible to start and stop the item connected by pressing button If the rela...

Страница 32: ...on the rt interval F 50 90 C F These functions are now available on the IR32M model which in addition to the insertion of the Ad delay allows on the version with the infrared receiver the modification...

Страница 33: ...cording to the absolute temperature of the evaporator The F3 parameter is now fully operative Description of the new parameters Type Min Max U M Def F0 Management of fans 0 fans always ON specific pha...

Страница 34: ...t open alarm active 2 external alarm with delay Contact open alarm active Delay see parameter A7 3 enabling of defrost Contact open defrost not enabled 4 start of defrost Defrost is activated when the...

Страница 35: ...diagram for multiple units 4 5 TRF IR32 4 5 IR32 4 5 IR32 TRF TRF INS 4 5 IR32 TRF TRF INS MAIN SER MAIN mains power supply TRF transformer INS TRF insulating transformer earth SER multiple connectio...

Страница 36: ...Cod 030220151 Rel 2 1 04 09 98 35...

Страница 37: ...Cod 030220151 Rel 2 1 04 09 98 36...

Страница 38: ...Cod 030220151 Rel 2 1 04 09 98 37...

Страница 39: ...tors temperature operating set differential etc General remarks made earlier on the state of LEDs should be borne in mind SEQUENCE OF MAIN PHASES For easy reference we give below a diagram showing the...

Страница 40: ...rm ALL EA EE Eb inactive data memorisation error ALL Ed inactive defrost end by time out IR32Y IR32C iRDRC IR32P dF inactive defrost in progress ALL Description of the main alarm signals FLASHING LED...

Страница 41: ...ipment is carrying out a defrost Appears only if parameter d6 0 Note The following pages list some other incorrect operating situations model by model The most likely causes and corrective action are...

Страница 42: ...o short dp interval between defrosting dl 0 in this case defrost will not be activated parameter dP and dl manual defrost not activated and defrost LED flashing compressor protection delays operating...

Страница 43: ...if H1 1 end defrost temperature is too low Suggest checking defrost sensor and temperature reading on evaporator parameter d parameter dt and d defrost sensor manual defrost not activated and defrost...

Страница 44: ...erature alarm given after defrosting alarm delay after defrost too short or alarm threshold too low parameters d8 and AH after changing a value or programming continues to work with old values unit ha...

Страница 45: ...defrosting NTC Carel 10 K a 25 C standard ON PTC 985 Ohms a 25 C upon request Range of operation 40 90 C 40 130 C with PTC Operating conditions 0 60 C with relative humidity less than 80 rH 0 50 C mo...

Страница 46: ...s across insulating parts Long Environmental pollution Normal Heat and fire resistance category D Category surge immunity 1 Software class and structure Class A EN60730 1 Time constant 35 s in forced...

Страница 47: ...0 c2 Minimum compressor off time C 0 15 min 0 c3 Minimum compressor on time C 0 15 min 0 c4 Duty setting compressor safety 0 OFF 100 ON C 0 100 min 0 cc Duration of continuos cycle C 0 15 hrs 4 c6 Al...

Страница 48: ...Duty setting for external alarm 0 OFF 100 ON C 0 100 min 0 A7 External alarm delay A4 2 Multi function input C 0 199 min 0 FAN PARAMETERS Type Min Max Unit Def New F0 Fans under fan regulator 0 no 1...

Страница 49: ...in the table In view of the variation shown by thermistors three resistance values are given in the table for each temperature Rstd the typical resistance value at the temperature indicated Rmin is th...

Страница 50: ...ence impulses of electromagnetic origin the unit may reveal errors in its internal memorisation of data These errors can affect the correct operation of the unit If the microprocessor identifies an er...

Страница 51: ...Cod 030220151 Rel 2 1 04 09 98 50 IR32 DIMENSIONS IR32M IR32S IR32P IR32Y IR32C A 75 75 B 33 33 C 64 72 D 64 64 IRDR and S90RDPW2 S90OEM4PWR IR32...

Страница 52: ...Vac dc IR32M0L000 Panel mounting thermostats with defrost timer IR32S 2 digits 12 24Vac dc IR32S0L000 IR32S 2 digits 12 24Vac dc for remote control with buzzer IR32S0LBR0 IR32S 2 digits 24 240Vac dc I...

Страница 53: ...low temperature IRDRC0 2 digits 12 24Vac dc buzzer optional serial interface 2 digital inputs 4 relay outputs for remote control IRDRC00000 Options Serial output board for IR Din Rail and IR96 IRDRSE...

Страница 54: ...e ambient sensor during an interval which can reach up to 199 hours more than 8 days In any moment it is possible to restart the logging period by pushing a button Refer to parameters rt rH rL next pa...

Страница 55: ...revious state the digital input can be programmed as remote ON OFF In this case the ON OFF button on the front panel is disabled Refer to parameters A4 A5 c2 next pages N O and N C alarm relay On Ir96...

Страница 56: ...250V Alarm output SPDT relay max switching capacity 8A 250V Kind of environmental pollution normal Frontal protection index IP54 Important warning the cables to be connected to the controller contact...

Страница 57: ...see section alarms and signalling if pressed for more than 5 seconds allows access to the frequent parameters selection menu if pressed for more than 5 seconds together with the sel button allows acc...

Страница 58: ...or more than 5 seconds to force a defrosting cycle which will be activated only if the conditions are favourable for example the defrost sensor should be lower than the selected defrost end temperatur...

Страница 59: ...ed 4 confirm by pressing 5 the display shows the code of the first parameter to be modified To modify the parameters see the following section parameters modification Parameters Modification To modify...

Страница 60: ...perature read in the rt interval F 50 90 C F c COMPRESSOR PARAMETERS c0 Compressor start up delay after unit start up C 0 15 min 0 c1 Minimum interval between two compressor start up C 0 15 min 0 c2 M...

Страница 61: ...t on specific phases see parameters F2 F3 and Fd 1 fans controlled by a thermostat according to the difference between ambient temp and evap temp 2 fans controlled by a thermostat according to the eva...

Страница 62: ...en effected Dig In1 if A4 5 or Dig In2 if A5 5 see wiring diagram If H1 1 the fourth relay becomes an alarm output The relay is normally de energised and on alarm condition the contact will close If H...

Страница 63: ...A0 Check parameters AL Ad and A0 The alarm will cease as soon as the temperature returns within the limits selected HI FLASHING high temperature alarm temperature higher than SET AH A0 Check paramete...

Отзывы: