23
ENG
"humiFog direct" +0300073EN rel. 1.2 - 02.05.2019
6. ADVANCED CONFIGURATION PARAMETERS AND
OPERATING OPTIONS
6.1 Main menu and overview of functions
When accessing with password 77, the advanced settings button is available
for accessing a series of additional submenus. Each submenu is divided into a
number of screens identified by the index shown at the top right on the display.
The table below provides a complete overview of the screens.
Menu
Index
Description
a. Control
Da01
Set the type of control in zone 1 and the maximum production
Da02
Set the type of control in zone 2 and the maximum production
Da03
(visible if control using two main probes has been enabled)
Set the weight of the zone 1 control probes
Da04
Set the set point and band for the zone 1 main probe
Da05
Set the set point and band for the zone 1 limit probe
Da06
(visible if control using two main probes has been enabled)
Set the weight of the zone 2 control probes
Da07
Set the set point and band for the zone 2 main probe
Da08
Set the set point and band for the zone 2 limit probe
Da09
Maintenance hour counter, reset counter and maintenance warning
Da10
This is shown after 40 operating hours
The oil change counter (warning at 50 h) can be reset
Da11
Unit hour counter (not resettable)
Da12
Set unit operating hours (e.g. after replacing c.phc controller) and maintenance warning
b. Functions
Db01
Enable filling and set the filling time
Db02
Set washing cycle duration and frequency
Db03
Enable management of the external water treatment system
Db04
Management of advance start and delayed stop of blower fans
Db05
Export event log via USB
Db06
Export alarm log via USB
c. Configurations
Dc01
Set the type of signal for the main humidity probe in zone 1, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc02
Set the type of signal for the main temperature probe in zone 1, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc03
Set the type of external signal for zone 1, minimum/maximum signal value, signal offset
Dc04
Set the NO/NC logic for the external on/off contact (humidistat)
Dc05
Set the type of signal for the humidity limit probe in zone 1, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc06
Set the type of signal for the temperature limit probe in zone 1, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc07
Set the type of signal for the main humidity probe in zone 2, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc08
Set the type of signal for the main temperature probe in zone 2, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc09
Set the type of external signal for zone 2, minimum/maximum signal value, signal offset
Dc10
Set the NO/NC logic for the external on/off contact (humidistat)
Dc11
Set the type of signal for the humidity limit probe in zone 2, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc12
Set the type of signal for the temperature limit probe in zone 2, minimum/maximum probe reading, probe offset, enable
disconnected probe alarm and set the alarm delay
Dc13
(visible for single-zone cabinet)
Set wireless probes 1-4: main, limit or absent
Dc14
(visible for single-zone cabinet)
Set wireless probes 5-8: main, limit or absent
Dc15
(visible for two-zone cabinet)
Enable wireless probes 1-4 for the main/limit control function in zone 1/2
Dc16
(visible for two-zone cabinet)
Enable wireless probes 5-8 for main/limit control function in zone 1/2
Dc17
Set the percentage weight of the wireless probes
Dc18
Set humidification load in zone 1/2
Dc19
Set the pressure relief time for zone 1
Dc20
Set the pressure relief time for zone 2
Dc21
(visible for two-zone cabinet)
Set the system anti-drip time
Dc22
Set the anti-pressure return time
Dc23
Set the cabinet pressure probe offsets
d. Network unit
Dd01
Enable the humidifier network using the PRG button (if enabled, the network symbol appears on the main screen)
Dd02
Set the IP address of cabinet 1/2/3/4 in the network and check status, online/offline
Dd03
Set maximum load and grouped/balanced distribution set point
Dd04
Set cabinet rotation time (0 h = rotation disabled)
Dd05
Unit offline alarm timeout
Dd06
Disable network settings for the current unit (if Y, the network symbol is not shown on the main screen)
Dd07
Current unit production request
Dd08
Check status and production % of unit 1/2/3/4 on the network
e. Manual mode
De01
Enable manual zone request, set request % and enable management of individual c.phc outputs to check operation of electro-
mechanical components
De02
Manual management of contactor, fill valve FV, cabinet drain valve DR, bypass valve BYP