2.  CABINET INSTALLATION

2.1  Positioning

The cabinet, being IP20, must be installed in a closed compartment, 
sheltered from the rain, water spray and direct sunlight. 
The cabinet must be installed in an environment with a temperature 
between 5 and 40°C.  
Around 1 m clearance must be left in front of the cabinet to allow the 
door to be opened and maintenance to be performed. Around 0.5 m 
clearance needs to be left on both sides of the cabinet to allow space for 
the water connections on the right and electrical connections on the left.

Fig. 2.a

2.1.1 

Wall mounting  

The cabinets can be wall-mounted or floor-standing.  
In the event of wall mounting, it is recommended to use the metal frames 
and screws supplied. See the distances shown in the following image for 
drilling the holes and fastening the brackets.

Fig. 2.b

2.1.2 

Floor-standing installation

For floor-standing installation, the unit needs to rest on a raised platform 
so as to allow connection of the drain hose, located on the bottom of the 
cabinet (see chapter 2.2.3).

min 30 cm

Fig. 2.c

2.2  Cabinet water connections

2.2.1 

Feedwater line

An expansion vessel should always be installed upstream of the cabinet, 
so as attenuate variations in pressure in the feedwater line. It is also 
suggested to install a mechanical filter on the feedwater line to the 
cabinet (P/N ECKVESS050 for the filter vessel and P/N ECKFILT050 for the 
filter cartridge). Finally, an on-off ball valve should be installed on the line 
upstream of the cabinet, so as to allow for any maintenance operations 
on the water circuit downstream. 

Fig. 2.d

A hose with a minimum diameter Ø=1/2” should be connected upstream 
of the cabinet so as to ensure the right flow-rate and pressure to the 
humidifier. The humidifier inlet connection is 3/4” GAS F. The required 
humidifier inlet pressure is at least 3 bars. 
 
 

Содержание humiFog direct DLA02DF000

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT humiFog direct User manual...

Страница 2: ......

Страница 3: ...install and use the product near objects that may be damaged when in contact with water or condensate CAREL Industries declines all liability for direct or indirect damage following water leaks from t...

Страница 4: ...4 ENG humiFog direct 0300073EN rel 1 2 02 05 2019...

Страница 5: ...communication 17 4 7 Alarm relay output 17 4 8 Unit status digital output 17 4 9 Production percentage analogue outputs 18 5 START UP AND USER INTERFACE 19 5 1 Graphic terminal 19 5 2 Start up 19 5 3...

Страница 6: ...6 ENG humiFog direct 0300073EN rel 1 2 02 05 2019...

Страница 7: ...request signal from a probe temperature or humidity or external controller When operation is enabled remote on off and at the same time there is a humidification or cooling request signal the system...

Страница 8: ...lower units differ based on the number of nozzles the type of nozzles the nozzles are already pre assembled in the factory power supply voltage frequency and the direction of spray front or two direct...

Страница 9: ...uge 8 High pressure sensor 9 Temperature controlled safety valve 10 High pressure sensor 11 Temperature sensor 12 Overflow valve 13 Drain solenoid valve 14 Bypass solenoid valve 15 NC fill solenoid va...

Страница 10: ...elivered already assembled in cardboard boxes The user is responsible for removing the blower from the packaging removing the side plastic covers so as to make the water and electrical connections and...

Страница 11: ...tening the brackets Fig 2 b 2 1 2 Floor standing installation For floor standing installation the unit needs to rest on a raised platform so as to allow connection of the drain hose located on the bot...

Страница 12: ...er on the line Contact CAREL for longer water lines 2 3 Cabinet electrical installation The cabinet must be connected to the mains by the user 230 V 50 Hz for cabinet CE version UA DD 01 120 V 60 Hz f...

Страница 13: ...er units must be suitably positioned so as to allow complete absorption of the sprayed water Consequently it is recommended to install the blowers a due distance apart at a sufficient height from the...

Страница 14: ...e plastic covers Remove the blower unit from the steel bracket on the rear Rest the bracket against the wall in the position where the blower will be installed and then drill four holes in the wall us...

Страница 15: ...lower units to the cabinet make sure that the cable glands supplied with the cabinet and the blower units are available All connections to be made by the user cabinet power supply blower unit power su...

Страница 16: ...e optional is used for the auxiliary function to reduce humiFog Direct humidification or cooling capacity when approaching a set humidity or temperature threshold on the display or external controller...

Страница 17: ...eters and sends commands To connect a supervisor the RS485 serial port terminal M12 inputs 1 Tx Rx 2 Tx Rx 3 GND or Ethernet port is used The choice of which port to use depends on the supervisor Modb...

Страница 18: ...by multiplying the number of atomising nozzles in the zone by the flow rate delivered by each nozzle Step 3 10 Select zone 1 control mode from the options ON OFF contact e g humidistat External signal...

Страница 19: ...ue and press the confirm button Title Message Values Default Zone 1 set Zone 2 set Main probe set point 0 100 rH 0 40 C 50 rH 25 C Main probe band 0 10 rH 0 10 C 5 rH 2 C Limit probe set point 0 100 r...

Страница 20: ...centre To view the details of an individual notification press the notification To return to the previous display press To return to the home menu press the HOME icon Fig 5 m 5 3 8 System date and ti...

Страница 21: ...quick menu 5 3 14 Graphs Press the icon to access the function The graphs function is used to view the values of some system analogue and digital variables over a certain time frame Press the zone to...

Страница 22: ...n to change the unit of measure Press the icon to update the display application from a USB pendrive Press the icon to access the configuration wizard or factory data reset Press the icon to access th...

Страница 23: ...e type of signal for the temperature limit probe in zone 1 minimum maximum probe reading probe offset enable disconnected probe alarm and set the alarm delay Dc07 Set the type of signal for the main h...

Страница 24: ...to the request signal if not at the maximum When atomisation stops the pump remains active and the water is recirculated through an internal bypass circuit in the pumping unit rather than being delive...

Страница 25: ...ulated as follows Weighted average S1 p1 S2 p2 p1 p2 where Si is the probe reading and pi the relative weight To calculate the arithmetic average equal weights should be set for example p1 p2 100 6 3...

Страница 26: ...ed for longer than the value of the Delay parameter seconds the main probe broken or disconnected alarm will be activated 6 4 3 External signal setting The type of external signal can be configured on...

Страница 27: ...ean the anti dripping time also needs to be adjusted for two zone systems Always check correct operation of the atomisation on and off phases in PWM modulation mode Ref Display Description Range Def U...

Страница 28: ...markets a switch P N KITSE08000 that can connect a maximum of eight units 8 Ethernet ports If necessary use several KITSE08000 switches with a cascaded arrangement Main technical specifications of the...

Страница 29: ...he maximum capacity go to menu Dd03 The Capacity parameter identifies the maximum production request for the Master Slave system and can therefore be set by the user The Maximum capacity parameter rea...

Страница 30: ...buttons to display the details of all the units 7 4 5 Software backup function in the Master Slave system Master Slave mode can also be used to manage the software backup function if one or more units...

Страница 31: ...server and humiFog Direct communicate directly and there is no need to configure the network parameters subnet mask and gateway The disadvantage is that if adding other devices to the same network wi...

Страница 32: ...s 2 Circuit breaker intervention Al_CircBreaker Active 1 3 High pressure switch intervention Al_HiPSwitch Active 1 4 High pressure Al_HiP Active 1 5 Low pressure Al_LoP Active 1 6 High pressure on byp...

Страница 33: ...l_LimPrb_2 Active R 19 Low pressure trasducer error Al_PressByPass Active R 20 Bypass temperature probe error Al_TempByPass Active R 21 High pressure transducer error Al_Press Active R 22 Missing mode...

Страница 34: ...t can be used P N Model Features Power supply WS01F01M00 SI Probe Temperature humidity for industrial use Battery WS01G01M00 SA probe Room tempera ture humidity Battery WS01AB2M20 Access Point Gateway...

Страница 35: ...d receives power from J3 1 that there are no leaks in the outlet line correct closing of the drain solenoid valve in zone DR1 DR2 and bypass drain valve BYP NO valves 24 Vac to close that filling is e...

Страница 36: ...connected from c pHC or wired incorrectly The c pCOe expansion that controls zone 2 is offline Check that the unit model is exact the alarm goes off if the cabinet is single zone but the c pHC control...

Страница 37: ...control in zone 2 Check probe connections probe access point binding access point power supply Automatic Active Signal Unit 1 alarm ALN01 Alarm on unit no 1 in network Only if network function is act...

Страница 38: ...ocal standards 4 Fill the pump body with SAE 15W40 mineral oil up to the level suggested by the circular marker on the side of the pump the required oil content is around 350 ml 5 Finally close the ye...

Страница 39: ...rs entering the control menu screen Da10 The warning cannot be reset before 40 operating hours 11 5 Notification maintenance warning reset hour counter After 1000 hours of operation humiFog direct gen...

Страница 40: ...ent oil 5024646AXX 7 High pressure gauge scale 0 100 bars radial fitting 1 4 GAS UAKMWHP001 8 Pump high pressure switch calibration 90 bars UAKPSHP000 9 Temperature controlled safety valve 1309549AXX...

Страница 41: ...ODICE DISEGNO DESIGNED MODIFIED BY COLOUR COLORE OTHER MATERIALS ALTRI MATERIALI MATERIAL SPECIFICATION SPECIFICHE MATERIALE DIMENSIONI VEDI TABELLA WEIGHT and EXTERNAL SPACE SIZE INDICATIVE INFORMATI...

Страница 42: ...5A GT 5x20 250V F2 1A T 5x20 250V 2 5A GT 5x20 250V F3 1A T 5x20 250V 2 5A GT 5x20 250V F4 1A T 5x20 250V 2 5A GT 5x20 250V F5 4A T 5x20 250V 4A T 5x20 250V F6 4A T 5x20 250V 4A T 5x20 250V INDICATIVE...

Страница 43: ...CCR Short Circuit Current Rating 5 kA 5 kA Minimum cable size required for blower power supply AWG 14 AWG 14 Tab 12 b WATER CIRCUIT SPECIFICATIONS UA040DD 01 UA080DD 01 Required feedwater quality demi...

Страница 44: ...obe available available Webserver available available Serial communication via Ethernet and or via RS485 Modbus BACnet Modbus BACnet Tab 12 h 12 3 3 CE version blower datasheet Single blower units for...

Страница 45: ...050 AWG 14 with UA050 AWG 12 with UA090 AWG 12 with UA090 Maximum number of blower units connected to one cabinet 12 6 Tab 12 k Double blower units for mounting in centre of corridor UL version DLA04U...

Страница 46: ...46 ENG humiFog direct 0300073EN rel 1 2 02 05 2019 Note...

Страница 47: ......

Страница 48: ...INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency humiFog direct 0300073EN rel 1 2 02 0...

Отзывы: