11.3 Electrical specifi cations of electrical panels UCQ065D100
and UCQ065D200
Power supply
230 Vac ±10%
Power input
3 VA
Operating range
0 to 50 °C
Storage conditions
-10T60 °C, <90 % RH non-condensing
Operating conditions
0T50 °C, <90 % RH non-condensing
Index of protection
IP55
Connections
spring terminals, cross-section 0.2 to 2.5 mm
2
Assembly
wall mounted
Case
plastic
Environmental pollution
normal
Tab. 11.c
11.4 Technical specifi cations of the CAREL IRDRZ4000 humidistat
Power supply
24 Vac ±10%
Power input
3 VA
Operating range
0T50 °C
Resolution
0.1 % RH
Control precision
±0.5% of full scale
Storage conditions
-10T70 °C, <90% RH non-condensing
Operating conditions
0T50 °C, <90% RH non-condensing
Assembly
DIN rail
Case
Plastic
Index of protection
IP40 with panel mounted instrument
Connections
screw terminals with cross-section 0.5 to 1.5 mm2
Inputs (probes with voltage signals)
-0.5 to 1 Vdc
Probe power supply output
10 Vdc, Imax= 30 mA
Switching outputs
2 SPDT relays: Vac max= 250 V, max. switchable power = 2000 VA
maximum peak current = 10 A
Type of action-disconnection
type 1C disconnection (EN 60730-1)
Insulation
the low voltage parts have primary insulation from the very low
voltage parts, and double insulation from the front panel
Environmental pollution
normal
Serial connection
using IRDRSER board
Tab. 11.d
IMPORTANT NOTE:
the cables used must resist up to the maximum operating temperature, that is, to
the maximum room temperature specifi ed, plus the heat produced by the controller, equal to 20°C with
all the outputs at the maximum capacity.
11.5 Technical specifi cations of the UCHUMM0000 mechanical
humidistat
Max contact rating
3 A 250 V
Min contact rating
100 mA 24 V
Range
20 to 90% RH
Time constant (speed in air at 2 m/s)
Approx. 5 min
Differential 6%
RH
Control precision
± 5%
Temperature coeffi cient
+0.5 % RH/K
Calibration humidity
55% RH 23°C
Operating temperature
0 to 40 °C
Protection
IP20 (EN60529) class (IEC 60730)
Fig. 11.a
Fig. 11.b