KRPH6WHDP
cod. carel +030221900 rel. 2.0 dated 05/03/01
40
67$5783$1'6+87'2:1
,03257$17:$51,1*6
EHIRUHVWDUWLQJFKHFNWKDWWKHKXPLGLILHULVLQSHUIHFWFRQGLWLRQWKDWWKHUHDUHQRZDWHUOHDNVDQGWKDWWKH
HOHFWULFDOSDUWVDUHGU\
GRQRWFRQQHFWSRZHULIWKHDSSOLDQFHLVGDPDJHGRUHYHQSDUWLDOO\ZHW
:KHQLQVWDOODWLRQLVFRPSOHWHGIOXVKWKHVXSSO\WXELQJIRUDURXQGPLQXWHVE\SLSLQJZDWHUGLUHFWO\LQWRWKH
GUDLQZLWKRXWVHQGLQJLWLQWRWKHKXPLGLILHU
this will eliminate any scale or processing residues that may cause foam
when boiling.
3UHOLPLQDU\FKHFNV
%HIRUHVWDUWLQJWKHKXPLGLILHUWKHIROORZLQJVKRXOGEHFKHFNHG
•
the water, electrical and steam distribution connections have been made according to the instructions contained herein;
•
the water shut-off tap to the humidifier is open;
•
the power fuses are installed and intact;
•
the pair of AB terminals are connected by jumper or alternatively connected to the remote ON/OFF contact and the latter is
closed;
•
the steam pipe is not choked;
•
in case of humidification in ducts, the operation of the humidifier is slaved to the operation of the air fan (instead of or in
series with the remote ON/OFF contact);
•
the condensate return pipe from the distributor is installed and free to drain;
•
the drain tubing is correctly connected and free;
•
the NO contact corresponding to the humidistat, if connected, is closed.
)LUVWVWDUWXS
When starting the unit with the cylinder empty, a significant period must pass (which depends greatly on the conductivity of
the supply water and may even be a few hours long) before the rated production is reached. In fact, to achieve a level of
current sufficient to produce the rated thermal power, the salinity and thus the conductivity of the water must reach a
sufficient level through the repeated evaporation and water filling. This obviously does not occur if the machine is started
with cylinder containing water that already has a sufficient level of conductivity.
6WDUWLQJWKHXQLW
Fig. 6.2.1.1 shows the electrical controls located in the lower right on the frame of the structure.
,
–
switch: start. Button with arrow
:
GUDLQ
.
After having closed the disconnecting switch on the humidifier power
supply line, turn the appliance on by placing the rocker switch in
position
,
(see Fig. 6.2.1.2).
The start-up sequence is thus initiated, which includes an initial phase
followed by the actual operating phase.
The start-up sequence is highlighted by the illumination of the LEDs on
the control panel, as described in
0HDQLQJRIWKH/('VRQWKHIURQWSDQHO
.
0HDQLQJRIWKH/('VRQWKHIURQWSDQHO
/('
SRVLWLRQ
)LJ
PHDQLQJ
green left
power
on
yellow
central
production in progress
red
right
signals and alarms. These events are indicated
by flashes. Please refer to Table 7.1 for details
7DEOH
ON
)LJ
)LJ
)LJ