26
ENG
"humiFog direct" +0300073EN rel. 1.4 - 29.03.2022
8.4.2
Main temperature probe setting
The main probe can be confi gured on screen index Dc02 for the single-
zone and Dc08 for two-zone cabinets.
Index Description Parameter
Dc02
Dc08
Main probe
Main probe confi guration
Default: Enable: Enabled (depending on the type of
control)
Type: 0-10 V
Minimum: 0°C - Maximum: 60°C
Off set: 0
En. Al (enable alarms): Yes
Del: 60 seconds
Possible settings:
Type 0-10 V/0-1 V/NTC/4-20 mA/0-20 mA/2-10 V
Minimum: 0-60°C - Maximum: 0-100°C
Off set: 0
En. Al (enable alarms): Yes
Del: 0-600 seconds
Tab. 8.g
For each probe, after having specifi ed the type, the minimum and maximum
values readable can be defi ned, as well as an “off set” to compensate for any
imprecisions in the value read (example: off set = 3% rH corresponds to a
3 percent increase in the humidity value read by the probe). The "En. Al."
parameter enables the alarms corresponding to probe faults. If a fault is
detected for longer than the value of the "Delay" parameter (seconds), the
"main probe broken or disconnected" alarm will be activated.
8.4.3
External signal setting
The type of external signal can be confi gured on screen index Dc03 for
the single-zone and Dc09 for two-zone cabinets.
Index Description Parameter
Dc03
Dc09
Main probe Main probe confi guration
Default: Enable: Enabled (depending on the type of
control)
Type: 0-10 V
Minimum: 0 - Maximum: 100
Off set: 0
En. Al (enable alarms): Yes
Del: 60 seconds
Possible settings:
Type 0-10 V/0-1 V/4-20 mA/0-20 mA/2-10 V
Minimum: 0-100 - Maximum: 0-100
Off set: 0
En. Al (enable alarms): Yes
Del: 0-600 seconds
Tab. 8.h
8.4.4
Humidity limit probe setting
The limit probe can be confi gured on screen index Dc05 for the single-
zone and Dc11 for two-zone cabinets.
Index Description Parameter
Dc05
Dc11
Main probe Main probe confi guration
Default: Enable: Enabled (depending on the type of
control)
Type: 0-10 V
Minimum: 0% rH - Maximum: 100% rH
Off set: 0
En. Al (enable alarms): Yes
Del: 60 seconds
Possible settings:
Type 0-10 V/0-1 V/NTC/4-20 mA/0-20 mA/2-10 V
Minimum: 0-100% rH - Maximum: 0-100% rH
Off set: 0
En. Al (enable alarms): Yes
Del: 0-999 seconds
Tab. 8.i
For each probe, after having specifi ed the type, the minimum and maximum
values readable can be defi ned, as well as an “off set” to compensate for any
imprecisions in the value read (example: off set = 3% rH corresponds to
a 3 percent increase in the humidity value read by the probe). The "En. Al."
parameter enables the alarms corresponding to probe faults. If a fault is
detected for longer than the value of the "Delay" parameter (seconds), the
"main probe broken or disconnected" alarm will be activated.
8.4.5
Temperature limit probe setting
The limit probe can be confi gured on screen index Dc06 for the single-
zone and Dc12 for two-zone cabinets.
Index Description
Parameter
Dc06
Dc12
Main probe
Main probe confi guration
Default: Enable: Enabled (depending on the type of
control)
Type: 0-10 V
Minimum: 0°C - Maximum: 60°C
Off set: 0
En. Al (enable alarms): Yes
Del: 60 seconds
Possible settings:
Type 0-10 V/0-1 V/NTC/4-20 mA/0-20 mA/2-10 V
Minimum: 0-60°C - Maximum: 0-100°C
Off set: 0
En. Al (enable alarms): Yes
Del: 0-600 seconds
Tab. 8.j
For each probe, after having specifi ed the type, the minimum and
maximum values readable can be defi ned, as well as an “off set” to
compensate for any imprecisions in the value read (example: off set =
3% rH corresponds to a 3 percent increase in the humidity value read by
the probe). The "En. Al." parameter enables the alarms corresponding to
probe faults. If a fault is detected for longer than the value of the "Delay"
parameter (seconds), the "main probe broken or disconnected" alarm will
be activated.
8.4.6
Pressure relief time setting
In the event of poor atomisation quality or dripping in the fi nal
atomisation phase after a modulation period (Ton), the pressure relief
time can be adjusted, increasing it as much as necessary. The required
delay increases according to the length of the high pressure water line.
Increasing this time may mean the anti-dripping time also needs to be
adjusted, for two-zone systems. Always check correct operation of the
atomisation on and off phases in PWM modulation mode.
Ref.
Display
Description
Range
Def. UoM
Dc19
Dc20
Pressure relief
time
Line pressure dissipation
when atomisation off
0-30
5
s
Tab. 8.k
8.4.7
Anti-dripping time setting
For two-zone cabinets poor atomisation quality in the initial atomisation
phase after a modulation period (Toff ), the anti-dripping time can be
adjusted, increasing it as much as necessary. The required delay increases
according to the length of the high pressure water line and the setting of
the pressure relief parameter.
Ref.
Display
Description
Range
Def. UoM
Dc21 Anti-dripping
time
Fill line
when starting
atomisation
0-30
0
s
Tab. 8.l
8.4.8
Anti-pressure return time setting
In the event of alarm ABA05: high bypass pressure, slightly increase
the anti-pressure return time to allow better pressure dissipation in the
cabinet.
Ref.
Display
Description
Range
Def. UoM
Dc22 Anti-pressure
return
Dissipation of
cabinet pressure
0.2-30
1.7
s
Tab. 8.m
Содержание DLAQ2DF100
Страница 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT humiFog direct User manual...
Страница 2: ......
Страница 4: ...4 ENG humiFog direct 0300073EN rel 1 4 29 03 2022...
Страница 41: ...41 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 APPENDIX 14 1 Single zone wiring diagram GA1 Fig 14 a...
Страница 42: ...42 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 2 Two zone wiring diagram GA1 Fig 14 b...
Страница 46: ......
Страница 47: ......