background image

38

ENG

"humiFog direct" +0300073EN rel. 1.4 - 29.03.2022

• 

Check pump oil level. 

To check the level visually, use a mirror that allows a view of side of the 
pump facing to the cabinet wall. There is a small mark behind a circular 
transparent Plexiglas cover. The oil level is correct if, with the unit off , it 
remains around the central circumference. If the level is lower than the 
minimum shown in the fi gure, top up with oil (SAE 15W40) to the correct 
level (oil P/N 5024646AXX).
Generally the oil level should remain constant and periodical top ups 
should not be needed. If oil leaks are found, contact CAREL.

Fig. 13.a

• 

Check the nozzles: make sure the spray cone from the nozzles is 
regular. 

Even when using demineralised water, some particle may at times 
build-up on the nozzle opening, making the spray cone less uniform 
and aff ecting absorption effi

  ciency. If this happens, remove the nozzle 

(unscrew using a 10 mm spanner) and clean it (immersing in acetic acid 
tom remove scale) or replace it (P/N UAKMTP%000). Before assembling 
the nozzle again, remove the residual Tefl on from the thread and the 
small white fi lter at the base of the nozzle, and apply the sealant again to 
ensure water tightness.    

• 

Check the fans

Make sure that all of the fans on the blower units are working. In the 
event of malfunctions, check the power supply wiring. If the wiring is OK, 
replace the fan.  

• 

Check 

that there are no water leaks inside cabinet and on the 

distribution line and fi ttings. 

13.3 Special maintenance 

Special maintenance involves all those operations that are performed 
on a one-off  basis in the event of malfunctions or breakages of certain 
components. 

The following components are those susceptible to breakage:

• 

solenoid valves

• 

pressure reducer

• 

pressure switches

• 

pump motor

• 

pump

• 

electronic controller

• 

fuses

• 

nozzles

• 

nozzle manifold

• 

fans on the blower units

To replace these contact specialist and authorised personnel. 
To fi nd the replacement part number, see the paragraph "Cabinet spare 
parts"   

13.4 Pump maintenance

The pump is the most complex mechanical device inside the cabinet, as 
well as the heart of the high pressure system.It therefore requires regular 
maintenance, involving the operations described below.

Pump
Check/replace

monthly

every 1000 h

check oil level

x

check/change oil

x

check/replace gaskets and valves

x

Tab. 13.a

13.4.1 Oil 

change

Important:

 after the fi rst 50 hours of operation, the oil in the pump needs 

to be changed (P/N 5024646AXX). Failure to change the oil after the fi rst 
50 hours may cause damage to the pump and reduce its working life. 
The fi rst oil supplied, in fact, will accumulate debris due to transport and 
commissioning, and a longer operating time cannot be guaranteed.

Important: 

change the pump oil after the fi rst 50 hours of operation.

Important: 

if there are no leaks or faults, when the "1000 h" check 

warning is shown, the oil change may be postponed.

Under normal operating conditions, except for the fi rst oil change 
after only 50 hours, we recommend an oil change every 3000 hours of 
operation. Every 1000 hours, a notifi cation is generated by the electronic 
controller and the 3000 hours of operation are signalled by the electronic 
controller through an appropriate "request for oil change and parts 
replacement" alarm, which appears on the display.

To change the oil, follow the sequence described below (with the unit off  
and the water line closed):

7. 

Remove the yellow cap on the top of the pump and unscrew the oil 
drain plug attraction the bottom (steel hexagonal plug). 

8. 

Empty the oil into a suitable container. Close the plug. 

9. 

Dispose of the oil in accordance with local standards. 

10. 

Fill the pump body with SAE 15W40 mineral oil, up to the level 
suggested by the circular marker on the side of the pump (the 
required oil content is around 350 ml).

11. 

Finally, close the yellow cap on the top of the pump. 

13.4.2  Gasket and valve replacement

The gaskets and valves must be replaced every 3000 hours, duly 
indicated by the "request for oil change and parts replacement" alarm 
on the display. Nonetheless, in specifi c conditions of stress replacement 
may be needed earlier. Carel recommends to check the pump operation 
every 1000 operating hours (signalled by notifi cation). If the pump makes 
noise, or is not able to reach the required operating pressure (70 bars), the 
gaskets and valves may need to be replaced sooner.  
Valves and gaskets are consumables, and wear does not refl ect a product 
malfunction.

To replace the gaskets, proceed as follows:

1. 

Disconnect the wiring from the high pressure switch, solenoid valve 
BYP and the NTC probe. 

2. 

Disconnect the pump outlet hose (at the top right). 

3. 

Unscrew the eight hex screws that hold the pump head to the guard.

4. 

Remove the gaskets and replace them with new ones (P/N 
UAKVGO1501).

5. 

Tighten the eight hex screws so as to secure the pump head to the 
guard.

6. 

Connect the outlet hose to the pump. 

7. 

Reconnect the pressure switch, solenoid valve and NTC probe   

Содержание DLAQ2DF100

Страница 1: ...NO POWER SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT humiFog direct User manual...

Страница 2: ......

Страница 3: ...om an ext controller 17 6 5 Digital signal from humidistat or external controller 17 6 6 Serial or Ethernet communication 17 6 7 Alarm relay output 17 6 8 Unit status digital output 17 6 9 Production...

Страница 4: ...4 ENG humiFog direct 0300073EN rel 1 4 29 03 2022...

Страница 5: ...al use of the product Do not attempt to open the humidifier in any way other than described in the manual This installation operation and maintenance manual must be kept in paper format in a safe and...

Страница 6: ...be operated with a DC power supply Regularly check that all safety and monitoring devices are working properly Do not remove or disable the safety devices NOTICE Possibility of water leaks due to faul...

Страница 7: ...perature or humidity or external controller When the operation consent is enabled remote ON OFF and at the same time there is a request for humidification or cooling the system opens the delivery sole...

Страница 8: ...lower units differ based on the number of nozzles the type of nozzles the nozzles are already pre assembled in the factory power supply voltage frequency and the direction of spray front or two direct...

Страница 9: ...High pressure sensor 9 Temperature controlled safety valve 10 High pressure sensor 11 Temperature sensor 12 Overflow valve 13 Drain solenoid valve 14 Bypass solenoid valve 15 NC fill solenoid valve 16...

Страница 10: ...already assembled in cardboard boxes The user is responsible for removing the blower from the packaging removing the side plastic covers so as to make the water and electrical connections and then re...

Страница 11: ...ical connections the appliance must be disconnected from the mains power supply and must be prevented from being powered on Electrical disconnection must be verified by measurement NOTE observe the lo...

Страница 12: ...by at least 20 30 cm NOTICE the drain water must be able to flow freely 4 2 4 Blower water supply line With reference to the high pressure hoses provided by CAREL inside diameter 6 3 mm in order to e...

Страница 13: ...r a correct installation see the example or contact Carel for different temperature and humidity conditions 4 3 1 Fuses The following table lists the technical specifications of the fuses supplied for...

Страница 14: ...g drilled the holes in the wall fix the metal support using anchor screws not supplied Then attach the blower to the protrusions on the wall mounting support bracket Fix the blower unit to the bracket...

Страница 15: ...he cables through the cable glands and in accordance with local safety standards Also check that the cable is the right size for the distance and voltages used Carel recommends an AWG14 or AWG12 cable...

Страница 16: ...uts 1 IN a 2 GND 3 12 Vdc on terminal M2 The limit probe optional is used for the auxiliary function to reduce humiFog Direct humidification or cooling capacity when approaching a set humidity or temp...

Страница 17: ...humiFog Direct parameters and sends commands To connect a supervisor the RS485 serial port terminal M12 inputs 1 Tx Rx 2 Tx Rx 3 GND or Ethernet port is used The choice of which port to use depends o...

Страница 18: ...unit Step 1 10 Enter the humidifier model Step 2 10 Enter the humidification load in kg h for zone 1 and if present zone 2 The humidification load can be easily calculated by multiplying the number of...

Страница 19: ...s the HOME icon Fig 7 e 7 3 2 Set point quick menu Press the icon to access the menu The menu is used to modify the set point and proportional control band Press the white number to change the value E...

Страница 20: ...to the previous display press To return to the home menu press the HOME icon Fig 7 l 7 3 7 Notification centre Press the icon to access the notification centre To view the details of an individual not...

Страница 21: ...ss the icon to access the function The same screen is displayed which is also accessible from the input output quick menu 7 3 14 Graphs Press the icon to access the function The graphs function is use...

Страница 22: ...n to change the unit of measure Press the icon to update the display application from a USB pendrive Press the icon to access the configuration wizard or factory data reset Press the icon to access th...

Страница 23: ...Dc08 Set the type of signal for the main temperature probe in zone 2 minimum maximum probe reading probe offset enable disconnected probe alarm and set the alarm delay Dc09 Set the type of external s...

Страница 24: ...nalY selectable from the following options 0 to 1 Vdc 0 to 10 Vdc 2 to 10 Vdc 0 to 20 mA 4 to 20 mA The maximum production Pmax corresponds to the maximum value of the external signal Y and will be th...

Страница 25: ...pump delivers the flow rate for the time defined by the following parameter so as to fill the line before atomisation commences Yes No Yes Duration Line filling time before starting ato misation only...

Страница 26: ...responding to probe faults If a fault is detected for longer than the value of the Delay parameter seconds the main probe broken or disconnected alarm will be activated 8 4 5 Temperature limit probe s...

Страница 27: ...itch Carel markets a switch P N KITSE08000 that can connect a maximum of eight units 8 Ethernet ports If necessary use several KITSE08000 switches with a cascaded arrangement Main technical specificat...

Страница 28: ...et the maximum capacity go to menu Dd03 The Capacity parameter identifies the maximum production request for the Main Secondary system and can therefore be set by the user The Maximum capacity paramet...

Страница 29: ...N buttons to display the details of all the units 9 4 5 Software backup function in the Main Secondary system Main Secondary mode can also be used to manage the software backup function if one or more...

Страница 30: ...etwork parameters subnet mask and gateway The disadvantage is that if adding other devices to the same network with humiFog Direct off and not connected the IP address originally assigned to the unit...

Страница 31: ...iTByPass Active 1 0 1 R 9 Low pressure on bypass Al_LoPByPass Active 1 0 1 R 10 Zone drain valves error Al_Drain Active 1 0 1 R 11 Expansion offline Al_ExpOffline Active 1 0 1 R 12 Warning high temper...

Страница 32: ...High pressure transducer error Al_Press Active 0 1 R 22 Missing model Al_MissModel Active 0 1 R 23 Water treatment system alarm Al_WTS Active 0 1 R 24 31 Wireless probe offline 1 8 Al_WPrb_1 8 Active...

Страница 33: ...for industrial use Battery WS01G01M00 SA probe Room tempera ture humidity Battery WS01AB2M20 Access Point Gateway radio ZigBee RS485 Modbus 12 24 Vac dc 10 100 mA 50 60 Hz Use a Class II safety trans...

Страница 34: ...DR2 zone discharge and BYP bypass discharge solenoid valves NO valves 24Vac to close that filling is enabled with a duration that is appropriate to the length of the water line If necessary replace th...

Страница 35: ...shown in the wiring diagram that c pCOe is powered 24Vac between G G0 on terminal J1 Automatic Active Humidification interrupted Oil change requested ALA13 Pump oil change requested Change pump oil a...

Страница 36: ...tion of probes with access point access point power supply Automatic Active Signal Unit 1 in alarm ALN01 Network unit no 1 in alarm Only if network function is active Perform checks according to the a...

Страница 37: ...nciple the requirements for air humidification according to VDI 6022 1 must be observed All tests and measurements shall be documented in a logbook available for inspection The user is responsible for...

Страница 38: ...irst 50 hours of operation the oil in the pump needs to be changed P N 5024646AXX Failure to change the oil after the first 50 hours may cause damage to the pump and reduce its working life The first...

Страница 39: ...same occurs after 2000 hours of operation After 3000 hours of operation instead humiFog direct generates a non blocking request for oil change and parts replacement alarm In this case the machine mus...

Страница 40: ...oil 5024646AXX 7 High pressure gauge scale 0 100 bars radial fitting 1 4 GAS UAKMWHP001 8 Pump high pressure switch calibration 90 bars UAKPSHP000 9 Temperature controlled safety valve 1309549AXX 10 R...

Страница 41: ...41 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 APPENDIX 14 1 Single zone wiring diagram GA1 Fig 14 a...

Страница 42: ...42 ENG humiFog direct 0300073EN rel 1 4 29 03 2022 14 2 Two zone wiring diagram GA1 Fig 14 b...

Страница 43: ...Rating 5 kA 5 kA Minimum cable size required for blower power supply AWG 14 AWG 14 Tab 14 b WATER CIRCUIT SPECIFICATIONS UA040DD 01 UA080DD 01 Required feedwater quality Feed water temperature deminer...

Страница 44: ...0 20 mA NTC probe Multi probe available available Webserver available available Serial communication via Ethernet and or via RS485 Modbus BACnet Modbus BACnet Tab 14 h 14 3 3 CE version blower datashe...

Страница 45: ...050 AWG 14 with UA050 AWG 12 with UA090 AWG 12 with UA090 Maximum number of blower units connected to one cabinet 12 6 Tab 14 k Double blower units for mounting in centre of corridor UL version DLA04U...

Страница 46: ......

Страница 47: ......

Страница 48: ...INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency humiFog direct 0300073EN rel 1 4 29 0...

Отзывы: