3. INSTALLATION
3.1 Positioning
• The compactSteam unit is designed for wall-mounting;
• to ensure correct steam distribution, position the humidifi er near the
point of steam distribution steam;
• make sure the humidifi er is vertical, leaving the minimum clearances
(see Fig.3.a and Tab. 3.a for the installation of the duct model and Fig.
3.b and Tab. 3.b for the room model) to ensure safety and allow for the
necessary maintenance operations.
Duct steam distribution
A
B
C
D
E
F
Millimetres
Inches
A
150 mm
6“
B
150 mm
6“
C
150 mm
6“
D
150 mm
6“
E
600 mm
24“
F
max. 0.2
Tab. 3.a
Fig. 3.a
Direct room distribution
C
D
A
B
Millimetres
Inches
A
150 mm
6“
B
1500 mm
60“
C
1800 mm
72“
D
600 mm
24“
Tab. 3.b
Fig. 3.b
Dimensions of the unit (for all models):
A
B
C
Millimetres
Inches
A
341 mm
13.4”
B
204 mm
8.1”
C
600 mm
23.7”
kg
lb
Empty weight
8 kg
18 lib
Packaged
weight
10 kg 22 lib
Weight in-
s water
12 kg 26 lib
Tab. 3.c
Fig. 3.c
3.2 Mounting
Removing the front cover
The front cover is fastened to the body unit using four Phillips head screws
located in the four corners of the unit. Use a screwdriver to unscrew the
four screws on the cover as shown in Fig. 3.d, then remove the cover
by simply pulling it outwards (Fig. 3.e). To replace the cover, perform the
same operations in the reverse order.
Be careful not to over-tighten the screws.
Fig. 3.d
Fig. 3.e
Содержание compactSteam
Страница 2: ......
Страница 3: ...3 ITA compactsteam 0300092IE rel 1 3 16 08 2021 Manuale d uso ...
Страница 6: ......
Страница 8: ...8 ITA compactsteam 0300092IE rel 1 3 16 08 2021 ...
Страница 31: ...3 ENG compactsteam 0300092IE rel 1 3 16 08 2021 User manual ...
Страница 34: ......
Страница 36: ...8 ENG compactsteam 0300092IE rel 1 3 16 08 2021 ...
Страница 59: ......