8
ENG
c.pCO s0300057EN rel. 1.2 - 29.05.2017
A
pplications
When provided with a dedicated application program, the controller can be used
to control different kinds of equipment:
•
chillers and heat pumps;
•
roof-top units;
•
air-conditioners;
•
small/medium-sized air handling units (on request);
•
refrigerated showcases (on request and to specifications);
•
cold rooms (on request and to specifications);
•
curing rooms;
•
compressor racks;
•
universal stage controllers.
1.1 Functional
layout
The figure below shows the functional layout of an air handling unit. Damper
actuators and valve actuators are field devices that communicate through
Fieldbus 1 (ref. C). Fieldbus 2 (ref. E) is the medium through which the serial probes
communicate the values measured, and through which the humidifier control
board and the fans exchange data and receive set points from the controller. The
built-in terminal and the remote terminal, which communicate via pLAN (ref. A),
are used for installing the application program and for commissioning the system.
The PGD touchscreen terminal, intuitive and simple to use, can be used while the
unit is normally working to set switch-on and switch-off times, to enter the main
parameters, to perform other advanced functions of the application program and
to view any alarms triggered. In this case data are exchanged via Ethernet port (ref.
D). In the same network it is possible to connect another c.pCO controller as well
as to communicate with remote cloud service tEra or to BACnet™ supervisor. The
system can be connected to other supervision systems (Konnex®, LON®, etc.) after
installing the relative BMS1 expansion card (ref. B).
5
8
4
S
R
s
u
t
a
t
s
G NX
RS485
+
–
P1
P2
P3
B A Cnet
™
MS/TP
FieldBus 1
BMS 1
J1
J24
J2
J3
J4
J5
J7
J8
J20
J21
J14
J10
J13
J12
J22
J16
J17
J18
J15
J6
J19
Fie l dB u s c a r d
B M S card
J23 FBus2
J11 pLAN
J25 BMS2
J26 FBus2
4
3
2
1
touch screen
pGD1
FieldBus 2
Ethernet
pLAN
A
D
E
C
B
EVD
evolution
c.pCOe
c.pCO mini
tERA cloud
service
Power +
FAN
EVD
Evolution
PC
BELIMO
BELIMO
tDisplay, tService
F
Router
RS485 serial card
FieldBus serial card
Damper
servo-control
Servo-control
valve
Serial probes th-Tune
Access Point
Speed regulator
pGD terminal
Humidifier
control board
Serial probes
Third part
device
interface
interface
interface
interface
BACnet™ RS485
Ethernet™ /BACnet™
LonWorks
®
Konnex
®
Fig. 1.a
Ref. Serial port/Connectors
Connection to:
A
pLAN/J10, J11
up to 3 terminals (e.g. pGD1, pLDPRO)
B
BMS 1 Serial Card
a building automation system, after installing the special BMS card (see par. 1.3)
C
FieldBus 1 Serial Card
sensors, actuators, etc., on a Fieldbus, after installing the special card (see par. 1.4)
D
Ethernet
pGD Touch terminals, c.pCO controllers, Router-->tERA
E
FieldBus 2 / J26 (e J23 in Large, Extralarge models)
sensors, actuators, etc., on a Fieldbus (built-in card)
F
BMS 2 / J25
other devices (built-in card)