60
ENG
c.pCO sis
tem
a
+
0300057EN
re
l. 1.2 - 29.05.2017
D
igital inputs I
D
... I
D
H
Type
c.pCO Small...Extralarge optically-isolated; c.pCOmini not optically-isolated
Lmax
30 m, (c.pCOmini 10m)
Voltage-free contacts
no. of optically-isolated inputs at 24
Vac or 24 Vdc
no. of optically-isolated inputs at 24 Vac/
Vdc or 230 Vac - 50/60 Hz
Maximum
number
MINI (only Enhanced/HighEnd)
2
0
0
SMALL
0
8
0
MEDIUM/ BUILT-IN DRIVER/EXTRALARGE
0
12
2
LARGE
0
14
4
Minimum digital input pulse detection time
Normally open (open-closed-open): 200 ms;
Normally closed (closed-open-closed): 400 ms;
Power supply to inputs
c.pCO Small...Extralarge - External - c.pCOmini - Internal
IDH...: 230 Vac (+10/-15%) 50/60 Hz
ID...: 24 Vac (+10/-15%) 50/60 Hz or 28-36 Vdc (+10/-20%)
Classification of measuring circuits (EN 61010-1)
Category I: 24 Vac/Vdc (J5, J7, J20)
Category III: 230 Vac (J8, J19)
Digital input current draw at 24 Vac/Vdc
5 mA
Digital input current draw at 230 Vac
5 mA
Important:
c.pCO SMALL, MEDIUM, BUILT-IN DRIVER, LARGE, EXTRALARGE:
•
separate as much as possible the probe and digital input cables from cables to inductive loads and power cables, so as to avoid possible electromagnetic
disturbance. Never run power cables (including the electrical panel cables) and signal cables in the same conduits;
•
the two 230 Vac or 24 Vac/Vdc inputs on terminals J8 (ID13, ID14) or J19 (ID15, ID16) have the same common pole and must therefore be powered at the same voltage
(230 Vac or 24 Vac/Vdc). There is functional insulation between the two inputs; there is reinforced insulation between the inputs and the rest of the controller;
•
ID1...ID8, ID9 to ID12, ID17, ID18 have functional insulation from the rest of the controller;
•
for DC voltage inputs (24 Vdc) either the + or the - can be connected to common terminal;
•
the rating of the external contact connected to the digital inputs must be at least 5 mA.
c.pCOmini
•
separate as much as possible the probe and digital input cables from cables to inductive loads and power cables, so as to avoid possible electromagnetic
disturbance. Never run power cables (including the electrical panel cables) and signal cables in the same conduits;
•
the rating of the external contact connected to the digital inputs must be at least 5 mA.
A
nalogue outputs
Y
...
MINI
SMALL
MEDIUM / BUILT-IN DRIVER / EXTRALARGE
LARGE
Type
0...10 V no optically-isolated, su Y1, Y2
0...10 V optically-isolated on Y1...Y6
Lmax
10m
30 m
Maximum number
2: Y1, Y2
4: Y1...Y4 a 0...10 V
6: Y1...Y6 a 0...10 V
Power supply
Internal
external: 24 Vac (+10/-15%) o 28...36 Vdc su VG(+), VG0(-) (*)
Precision
Y1, Y2 ± 3% full scale
Y1...Y6: ± 2% full scale
Resolution
8 bit
8 bit
Settling time
Y1,Y2:
da 1 s (slew rate 10 V/s) a 20 s (slew
rate 0,5 V/s) selectable via SW
Y1...Y6: da 1 s (slew rate 10 V/s) a 20 s (slew rate 0,5 V/s) selezionabile via SW
Maximum load
1 kΩ (10 mA)
1 kΩ (10 mA)
Warnings - c.pCO SMALL, MEDIUM, BUILT-IN DRIVER, LARGE, EXTRALARGE
•
for lengths greater than 10 m use a shielded cable with earthed shield;
•
a 0 to 10 Vdc analogue output can be connected in parallel to other outputs of the same kind, or alternatively to an external source of voltage. The higher voltage
will be considered. Correct operation is not guaranteed if actuators with voltage inputs are connected;
•
power the VG-VG0 analogue outputs at the same voltage on G-G0: connect G to VG and G0 to VG0. This applies in case of both alternating or direct current power supplies.
c.pCOmini
•
for lengths greater than 10 m use a shielded cable with earthed shield;
•
a 0 to 10 Vdc analogue output can be connected in parallel to other outputs of the same kind, or alternatively to an external source of voltage. The higher voltage
will be considered. Correct operation is not guaranteed if actuators with voltage inputs are connected;
D
igital outputs
NO
...,
NC
...
c.pCOmini
Maximum connection cable length: less than 30 m
Type
Relay.
Maximum no.
6
Insulation distance
The outputs can be divided into groups: between group 1 and 2 there is basic insulation. Group 3 has reinforced insulation from
the first 2 groups and can be powered at a different voltage.
Relays with same insulation
Group
Composition of groups
Model
1
2
3
MINI
1...2
3, 4, 5
6
Type of relay
Type C Type C
Type D
Number of changeover contacts 1 (relay 6)
Switchable power
Type C
Relay rating
Approval
NO EN 60730-1:
2(1)A (75000 cycles)
UL 60730:
5 A resistive, 250 Vac, 30000 cycles, 105 °C. Defined purpose, 1FLA, 6LRA,
250 Vac, 30000 cycles, 105 °C, pilot duty C300, 250 Vac, 30000 cycles, 105 °C
Type D
Relay rating
Approval
NO EN 60730-1:
1(1)A (100000 cycles), maximum switchable voltage: 250 Vac
UL 60730-1:
1 A resistive, 1 A FLA, 6 A LRA, 250 Vac, D300 pilot duty, 30000 cycles
R2, R5 with SSR assembly: switchable power 15 VA 110/230 Vac or 15 VA 24 Vac according to the model purchased