CAREL Industries HQs
Via dell’Industria, 11 - 35020 Brugine - Padova (Italy)
Tel. (+39) 0499716611 – Fax (+39) 0499716600 – www.carel.com – e-mail: [email protected]
+0500142EZ - rel. 1.0 - 03.07.2018
CAREL
保留在未事先通知的情况下对产品进行变更的权利。
CAREL reserves the right to modify its products without notice.
IMPORTANT WARNINGS
The CAREL product is a state-of-the-art product, whose operation is specifi ed in the
technical documentation supplied with the product or can be downloaded, even prior to
purchase, from the website www.carel.com. - The client (builder, developer or installer
of the fi nal equipment) assumes every responsibility and risk relating to the phase of
confi guration the product in order to reach the expected results in relation to the specifi c
fi nal installation and/or equipment. The lack of such phase of study, which is requested/
indicated in the user manual, can cause the fi nal product to malfunction of which CAREL can
not be held responsible. The fi nal client must use the product only in the manner described
in the documentation related to the product itself. The liability of CAREL in relation to its own
product is regulated by CAREL’s general contract conditions edited on the website www.
carel.com and/or by specifi c agreements with clients.
拆卸
/ Dismantling
1
Fig. 4
更换
Replacing
如需更换用户终端,为避免发生故障:
1.
关掉该装置的电源;
2.
更换用户终端;
3.
重新启动装置。
In case of replacing the user terminal, to
avoid malfunctions:
1. switch off (unplug) the unit;
2. replace the user terminal;
3. restart the unit.
NFC/
蓝牙通讯
NFC/BLE communication
近场通信(
NFC
)简单快速,可在与控
制器通信时使用。更多信息,请参阅
MPXone
系统手册
+0300086EN
。
NFC (Near Field Communication) is
simple and fast and can be used when
commissioning the controller. For further
information, see the MPXone system
0300086EN.
300086_028_R01
Fig. 5
(1)符合“微功率短距离无线电发射设备目录和技术要求”的具体条款和使用场
景,采用的天线类型和性能,控制、调整及开关等使用方法;
(2)不得擅自改变使用场景或使用条件、扩大发射频率范围、加大发射功率(包括
额外加装射频功率放大器),不得擅自更改发射天线;
(3)不得对其他合法的无线电台(站)产生有害干扰,也不得提出免受有害干扰保
护;
(4)应当承受辐射射频能量的工业、科学及医疗(ISM)应用设备的干扰或其他合
法的无线电台(站)干扰;
(5)如对其他合法的无线电台(站)产生有害干扰时,应立即停止使用,并采取措
施消除干扰后方可继续使用;
(6)在航空器内和依据法律法规、国家有关规定、标准划设的射电天文台、气象雷
达站、卫星地球站(含测控、测距、接收、导航站)等军
民用无线电台(站)、机场等的电磁环境保护区域内使用微功率设备,应当遵守电
磁环境保护及相关行业主管部门的规定;
(7)禁止在以机场跑道中心点为圆心、半径5000米的区域内使用各类模型遥控器;
(8)微功率设备使用时温度和电压的环境条件。
电气接线图
/ Electrical connections
用户终端
User terminal
J8
J4 BMS
J3
J2
J5 FBus
S1 S3 5V
S2
Y2
Y1
ID1
ID2
ID3
ID5
ID4
S4
S6 +V
VL
S5
to user terminal
ACS00CB0000** cable
远程显示
Remote display
GND
Rx+/Tx+
Power supply
Rx-/Tx-
J1
J7
NO4
C
G0 G
J6
NO2
NO3
C
NO1
J2
J3
J4 BMS
J5 FBus
S1 S3 5V
S2
Y2
Y1
ID1
ID2
ID3
ID5
ID4
S4
S6 +V
VL
S5
p y
Fig. 6
报警表
当报警发生时,
ALARM
图标变为红色,用户终端显示相应报警代
码。
代码
说明
rE
控制探头
E1
S1
探头故障
E2
S2
探头故障
E3
S3
探头故障
E4
S4
探头故障
E5
S5
探头故障
E6
S6
探头故障
E11
S11
串行探头未更新
E12
S12
串行探头未更新
E13
S13
串行探头未更新
E14
S14
串行探头未更新
LO
低温
HI
高温
LO2
低温2
HI2
高温2
IA
外部触点瞬时报警
dA
外部触点延迟报警
dor
门开启过长
Etc
实时时钟未更新
LSH
低过热
LSA
低吸气温度
MOP
高蒸发温度
LOP
低蒸发温度
bLo
阀门阻塞
Edc
与步进驱动器的通讯误差
EFS
步进电机损坏/未接通
HA HA
型
HACCP
报警
HF HF
型
HACCP
报警
MA
与主机通信误差(仅在从机上)
u1...u9
与从机通信误差(仅在主机上)
n1...n9
网络中装置
1... 9
的报警
GPE
自定义气体参数误差
技术规范
电源
13 Vdc ± 10% ACU
控制器电源;
最大电流
250 mA.
控制器连接推
荐电源:
SELV
或
PELV
接头
(
内置式
) JST
4-
针
ZH P/N S4B-ZR-SM4A-TF
控制器连接电缆
最大长度:
10
米。
B
如果其长度
超过
2
米,且没有内置设备,那
么使用屏蔽电缆。
尺寸
: AWG: 26
连接器:
• 终端侧:
JSTZH 4
条引线;
外壳:
ZHR-4
;终端
SZH-
002T-P0.5
• 控制侧:
–
用户终端:
JSTXH 4
路,
外壳:
XHP-4
,终端
SXH-
002T-P0.6
–
远程显示:线对线
蜂鸣器
所有机型均配备
温度传感器
内置
壳体
聚碳酸酯材料
尺寸:见图纸
组装
面板安装
显示
3
位数字、小数点及多功能图标
操作温度
-20T60°C
操作湿度
<90%rH
无冷凝
储存温度
-35T70°C
储存湿度
<90%rH
无冷凝
NFC
最大距离:
10
毫米,可根据使用
的移动设备进行调整。
低功耗蓝牙
最大长度:
10
米,根据使用的移
动设备确定
防护等级
IP65
前端
, IP20
后端
环境污染等级
3
球压试验
125°C
额定冲击电压
0.8 kV
启动和断开类型
1.Y
控制设备的结构
设备将进行整合
防电击等级
整合为
1
类或
2
类器械
串行接口
RS485
以上的
Modbus
通讯协议
软件类和结构
A
类
前端清洁
只能使用柔软、非研磨抹布和中
性洗涤剂或水
认证
CE, UL
电气安全:
EN60335-1, UL60335-1,
EN60730-1, UL60730-1
电磁兼容性:
EN61000-6, EN61000-3, EN55014-1,
EN61000-4, EAC
Alarm table
When an alarm occurs, the LED on the controller turns red and the user
terminal displays the code corresponding to the alarm
Code
Description
rE Control
probe
E1 Probe
S1
E2 Probe
S2
E3 Probe
S3
E4 Probe
S4
E5 Probe
S5
E6 Probe
S6
E11
Serial probe S11 not updated
E12
Serial probe S12 not updated
E13
Serial probe S13 not updated
E14
Serial probe S14 not updated
LO Low
temperature
HI High
temperature
LO2 Low
temperature
HI2 High
temperature
IA
Immediate alarm from external contact
dA
Delayed alarm from external contact
dor
Door open for too long
Etc
Real time clock not updated
LSH Low
superheat
LSA
Low suction temperature
MOP
Max evaporation pressure
LOP
Low evaporation pressure
bLo Valve
blocked
Edc
Communication error with stepper driver
EFS
Stepper motor broken/not connected
HA
HACCP type HA
HF
HACCP type HF
MA
Communication error with the Master (only on Slave)
u1...u9
Communication error with the Slave (only on Master)
n1...n9
Alarm on unit 1 ... 9 in the network
GPE
Error in the custom gas parameters
Technical specifi cations
Power supply
13 Vdc ± 10% supplied by ACU
controller; max current 250 mA.
Power supply recommended for the
connected controller: SELV or PELV
Connector (built-in)
JST 4 pin ZH P/N S4B-ZR-SM4A-TF
Controller connection
cable
Max length: 10m. If of lengths longer
than 2m and device not uilt-in, use
shielded cable.
Size: AWG: 26
Connectors:
• terminal side: JST ZH 4 pin; housing
ZHR-4; terminal SZH-002T-P0.5
• control
side:
– user terminal: JST XH 4 way,
housing XHP-4, terminal SXH-
002T-P0.6
– remote display: wires to wire
Buzzer
Available on all models
Temperature sensor
Built-in
Casing
Polycarbonate material
Dimensions: see fi gures
Assembly
Panel mounting
Display
3 digits, decimal point and
multifunction icons
Operating temperature
-20T60°C
Operating humidity
<90% RH non-condensing
Storage temperature
-35T70°C
Storage humidity
<90% RH non-condensing
NFC
Max distance 10 mm, variable
according to the mobile device used
Bluetooth Low Energy
Max length 10m, depend on the
used mobile device
Index protection
IP65 at front,
IP20 at rear
Environmental pollution
3
Ball pressure test
125°C
Rated impulse voltage
0.8 kV
Type of action and disconnection
1.Y
Construction of the control
device
Device to be incorporated
Classifi cation according to
protection against electric shock
To be incorporated in class 1 or 2
appliances
Serial interface
Modbus over RS485
Software class and structure
Class A
Cleaning the front side
Only use a soft, non-abrasive cloth
and neutral detergents or water
Certifi cations
CE, UL
Electrical safety:
EN60335-1, UL60335-1,
EN60730-1, UL60730-1
Electromagnetic compatibility:
EN61000-6, EN61000-3, EN55014-1,
EN61000-4, EAC
The complete user manual ( +0300086EN) for the
product can be downloaded at www.carel.com
under the “Services / Documentation” section
or via QR Code.
Disposal of the product
The appliance (or the product) must be disposed of separately in
compliance with the local standards in force on waste disposal.
重要警告
CAREL
始终致力于为您提供最先进的产品和服务,相关操作方法已在产品随附的技
术文档中加以说明,也可以在购买前从
www.carel.com
网站下载。客户(制造商、开
发商或最终设备的安装人员)承担与产品配置有关的所有责任和风险,旨在实现与
特定最终装置和/或设备有关的预期结果。如果未能完成用户手册中要求/指明的此
类操作,可能会导致最终产品出现故障;在这种情况下,
CAREL
不承担任何责任。
客户须按照与产品有关的文档中所述的方式使用本产品。
CAREL
的通用合同条款规
定了
CAREL
公司对其产品的责任,该条款可从
www.CAREL.com
网站和
/
或与客户达成
的特定协议中获得。
有关本产品的用户手册完整版(代码
+0300086EN
)可从
www.carel.com
网站中
的