ir33+ VCC
+040000058 - rel. 1.2 - 15.02.2018
Always remember the eff ect that parameters
AH
and
AL
have on this control function.
Code
Parameter
Status
rn
Neutral zone
Standard
rr
Reverse diff erential
Standard
H1
AUX1 output confi guration
0: normally energised alarm
8: auxiliary with deactivation when OFF
1: normally de-energised alarm
9: light with deactivation when OFF
2: auxiliary
10: no function
3: light
11: reverse with neutral zone
4: auxiliary evaporator defrost
12: second compressor step
5: pump down valve
13: no function
6: condenser fan
14: condensate drain heater
7: delayed compressor
Set to 11 for
AUX in reverse
control with
neutral zone
r3
Operating mode
0 = Direct with defrost control (cooling)
1 = Direct (cooling)
Tab. 3.g
3.1.10 Second
compressor
A second compressor can be confi gured by setting
H1 = 12
.
The output controls an ON/OFF compressor using the AUX relay.
The control of the variable-speed compressor follows the diagram shown below.
The fi rst compressor is always the variable-speed compressor.
Code
Parameter
Status
H1
AUX1 output confi guration
0: normally energised alarm
8: auxiliary with deactivation when OFF
1: normally de-energised alarm
9: light with deactivation when OFF
2: auxiliary
10: no function
3: light
11: reverse with neutral zone
4: auxiliary evaporator defrost
12: second compressor step
5: pump down valve
13: no function
6: condenser fan
14: condensate drain heater
7: delayed compressor
H1=12
Tab. 3.h
ON
OFF
St
t
rd/2
VCC
ON
OFF
rd/2
AUX
Fig. 3.g
The variable-speed compressor is managed based on the
dedicated parameters. If
H1 = 12
(AUX = second ON/OFF
compressor) then
c1 – c3
are used for ON/OFF protection of the
second compressor.
Parameters
c1 – c3
have no impact on the management of the variable-speed compressor.
Code Parameter
Status
c1
Min. time between successive starts of the second compressor - Note: active for AUX only if H1 =12 Standard
c2
Minimum second compressor off time - Note: active for AUX only if H1 =12
Standard
c3
Minimum second compressor on time - Note: active for AUX only if H1 =12
Standard
c11
Second compressor start delay, if H1 = 7 no temperature control on the AUX compressor
Standard