Reboot Submenu
System Data 1/4
Reboot 10/10
NO
The Reboot submenu allows the user to reboot the system.
If YES is selected, the system will reboot immediately. Note that the user must be logged
in with the current password to reboot the system.
Utility Input Connection Menu
The top-level Utility Input connection menu establishes operation parameters in the Grid
Load Control Module (GLCM). These are primarily the UL 1741 (IEEE 1547) Utility Grid
Connect Protective Relay functions, and their setpoints are displayed here.
Refer to the following reference documents as required:
•
Protective Relay Functions (410033)
The Utility Input submenus are detailed below:
NOTE
In the following submenus, the first line always displays the Grid
Connect top level menu.
WARNING
Do not attempt to change any Grid Connect Protective Relay functions.
Injury to personnel and/or damage to equipment can occur. Contact your
Capstone Authorized Service Provider for additional information.
NOTE
The primary Grid Connect Protective Relay function is to ensure that the
MicroTurbine does not energize utility wires de-energized by the utility.
NOTE
All of the following Protective Relay settings can only be changed by an
Authorized Service Provider using CRMS.
Under Voltage Submenu
Utility Input 2/4
Under Voltage 1/7
422 Vrms
2.00 Sec
The Under Voltage submenu shows the line-to-line voltage and associated delay time. If
the RMS voltage between any phases falls below this setting, the delay timer is started. If
the voltage has not recovered at the end of this time, the system will enter Emergency
Mode. This is adjustable from 352 up to the Over Voltage setpoint in 1 volt increments.
Initial Factory Setting is 422 VAC line-to-line.