Microturbine Start Delay Timer
System Data 1/4
System Config 5/10
MT Start Delay 2/5
1.0 Min
The microturbine start delay timer submenu allows the user to set a delay timer that
determines how long a non-operating turbine will wait before entering a start sequence
when utility power becomes unavailable. The setting is adjustable from 0 to 10.0 minutes.
The initial factory setting is 1.0 minute. Note that the user must be logged in with the
current password to change this setting.
MultiPac Submenu
System Data 1/4
System Config 5/10
MultiPac 3/5
ENABLE
The MultiPac submenu shows the user whether a MicroTurbine is enabled in the MultiPac
or not.
Turbine Number Submenu
System Data 1/4
System Config 5/10
Turbine Number 4/5
3
The main controller MicroTurbine in a MultiPac system is designated as the “Master”, and
must be assigned as number “1”. Other MicroTurbines may be assigned in any order in a
MultiPac system, however, each MT must have a unique turbine number. Note that the
user must be logged in with the current password to change the turbine number.
Auto Restart Submenu
System Data 1/4
System Config 5/10
Auto Restart 5/5
YES
The Auto Restart submenu enables or disables the system’s ability to automatically
attempt to restart the turbine after an incident driven shutdown. Note that the user must be
logged in with the current password to change this setting. The normal setting for a Hybrid
UPS system is YES.