Capstone Turbine Corporation
Model C65 Hybrid UPS User’s Manual
400027 Rev A (July 2010)
Page
41 of 66
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document without
incurring any obligation either with respect to equipment previously sold or in the process of construction.
Turbine Output Submenu
System Data 1/4
Engine LOAD OK 2/10
68.4 kW Gen
The second line shows the engine generator state, and whether the engine is OK or in a
fault condition (FLT). This submenu also gives individual generator output as “kW Gen” on
the third line. Note that in High Efficiency Mode, engine generator power that is greater
than what is required to support the load output will be export to the Grid LCM and/or
supplied to the DC bus.
The engine state messages are abbreviations of the actual engine states, as summarized
in Table 5.
Table 5. Hybrid UPS Engine State Messages and Description
Hybrid UPS
Engine State
Microturbine
Display
Description
STAND BY
STB
Engine ready to start
LIFT OFF
LIFT
Engine rotation started
LIGHT OFF
LITE
Engine ignition started
ACCEL
ACEL
Engine accelerating to idle
LOAD
LOAD
Engine ready to output power to load
COOLDOWN
CDWN
Stop command issued and engine in cool
down state
WARMDOWN
WDWN
Stop command issued and engine in
warm down state
RELIGHT
RLIT
Engine commanded to light off again
before rotation stops
SETDOWN
SETD
Engine rotation stopped
SHUTDOWN
SDWN
Engine is shutdown and transitioning to
standby state