Caple WI152 Скачать руководство пользователя страница 25

 

 

21/23 

Default: high frequency impact noise in capillary Zone. 

 

 

Caused by either reason below:

   

1>. 

The capillary being insert too deep into the evaporator, so when the refrigerant is Jetting, the 

end of vibrating capillary will hit the inside of the evaporator. 

 

2>. 

Vibration from the capillary touching the inside of the cabinet or air duct board, then when 

refrigerant is jetting. 

 

                 

Solutions: 

   

1>. Refer to

(→7.6)

 

2>. If the capillary touch the inner cabinet and the air duct panel, adjust the position of the capillary and 

add the incabloc plastic.   

 

 

       

7.8. 

Oil jammed noise

 

Fault: intermittent and deep jet noise coming from inside of the capillary. 

 

Cause: Compressor oil flowing into the cooling system pipe work probably due to the capillary 
slightly out of alignment during transportation   

 

Solution: Clean the cooling system pipe, vacuumize it and recharge with refrigerant see 

(→7.3) 

 

7.9.   

Evaporator freezing.

   

Because the door seal is not air-proof, or the door is not closed well, cause much water fill in the   
cabinet, and the water got frozen when it encounter the cold air, sometimes the ice is too thick, and 
it will block the fan or broken the fan. 

   

           

The solution: 

1 >. 

Replace the door seal or close the door well. If the door seal is slightly not air-proof, it can be 

repaired by the heat dryer.

 

 

Aiming at the distortion of the seal with the heat dryer, and move up and down until it expand to 
the normal state. When it is cool, check it with the door closed, if there is any distortion, dry it 

again until it fix for the door.

 

(Fig.18)

 

2 >. If the fan is broken, replace the fan.

   

 

Содержание WI152

Страница 1: ...WI152 Caple 15cm wine cabinet Technical information...

Страница 2: ......

Страница 3: ...Cover 1 13 DG3 42 PCB board 1 14 DG13 348 Button gasket 1 15 DG20 258 Display panel 1 16 DG13 130 S Button 4 17 DG23 157 Cabinet door 1 18 DG22 3027 cylinder knop 1 19 M184 027 Gasket 1 20 DG15 139 S...

Страница 4: ......

Страница 5: ...ttempting any cleaning or maintenance this unit MUST be disconnected from the electrical supply to prevent electrical shock Preparation before maintenance Tools 1 Pliers 2 Phillips head screwdrivers 3...

Страница 6: ...ist below Below we list the symbols and explain the danger if ignore it Danger This symbol means that the instance may have the chance to suffer death or a serious wound Warning This symbol means that...

Страница 7: ...the systems and cause blast Exhaust the rest refrigerant in the systems before welding After filling the refrigerant the sealing should be done by using smithing welding nozzle Using the welding mach...

Страница 8: ...place without fire before disusing the refrigerant bottle Don t touch the wine cooler when the cooling pipe damaged don t fie inside the wine cooler keep the windows open to exchange the air Disusing...

Страница 9: ...he pipe sometimes are very hot And the heating or just stop heater is very hot The hot will cause scald Attention the hot parts of the pipe after the welding Attention the refrigerant during charge an...

Страница 10: ...6 23 2 Electrical circuit diagram 3 Cooling system diagram...

Страница 11: ...ess DOWN the setting temp will lower down in 1 5 How to diagnose the fault 5 1 Fault finding by the self check mode The wine cooler is controlled by computer in order to maintain the wine cooler easil...

Страница 12: ...r sensor open circuit Check the wiring and connection between PCB and sensor if it open circuit If the connection and wiring is normal replace the sensor please E2 Inner sensor short circuit Check the...

Страница 13: ...Yes No No Yes Yes Yes No If the inner light can be turn on Check the power source power cord plug socket Display error code Refer to 5 2 The starter have power input The protector have power input Che...

Страница 14: ...helves Remove the air duct board Remove two air duct board fixing screws and remove the air duct board disconnect the fan connector carefully when pulling out the air duct board Fig 2 No Yes No Yes No...

Страница 15: ...and the fan can be removed Fig 3 6 1 4 How to remove the sensor The process remove the shelves remove the air duct board remove the sensor After remove the air duct board loose the sensor fixing screw...

Страница 16: ...PCB The process Remove the shelves remove the control box remove the main PCB After removing the control box press the nail one by one and pull the PCB upward remove the main PCB Fig 5 Diagram and ex...

Страница 17: ...sformer The process of removing the power PCB remove the power PCB cover disconnect the connectors remove the power PCB The process of removing the transformer remove the power PCB cover disconnect th...

Страница 18: ...xplanation of power PCB and connection Fig 10 Fig 8 L Power L N Power N X6 Transformer primary X16 Transformer secondary X3 Compressor X15 Outer fan X12 Main PCB Fig 10 Power PCB cover Transformer Pow...

Страница 19: ...move the cabinet legs remove the compressor fixing screws Release the refrigerant by cutting the process pipe C then heat the suction pipe and separate it by using the plier heat the filter and conden...

Страница 20: ...or Fig 16 Heat the solder joint A D separate them by using the plier Fig 13 Remove the evaporator fixing screws remove the evaporator Fig 16 Fig 13 Fig 15 A A Suction pipe solder joint B Filter and co...

Страница 21: ...e the compressor supporter remove the condenser Refer to the method of remove the compressor after remove the whole compressor and it s supporter separate the compressor and condenser on point E pull...

Страница 22: ...rge pipe if the obvious air pressure from compressor if the current still very high or very low or the discharge pipe with small air pressure the compressor fault replace the compressor please Notice...

Страница 23: ...anti dew pipe another is the damage on the spare parts in the cooling system If it is the inner damage it can not be repaired and if the damage on the spare parts replace them 3 Make sure there is no...

Страница 24: ...e maintained or replaced 6 2 3 2 If compressor s shock absorption rubber is hardening or damaged or fixing screw of compressor is too tight or loose it will cause noise The settlement is to change new...

Страница 25: ...ing system pipe work probably due to the capillary slightly out of alignment during transportation Solution Clean the cooling system pipe vacuumize it and recharge with refrigerant see 7 3 7 9 Evapora...

Страница 26: ...the sensor 6 1 4 1 After turning on the power if the LED display shows the temperature is similar with the ambient temperature it is normal if abnormal or show E1 E2 please remove the control box che...

Страница 27: ...Explanation of display According to requirement there are two different display one is that the LED display show the setting temperature the other is that the LED display show the real inner temperat...

Отзывы: