3.4.6 Horizontal Wall Vent Termination type C11
Flue sizing:
Ø100/150 Connector on Appliance for Metaloterm US concentric flue system.
Ø100/150 Adaptor for Poujoulat PGI or Muelink & Grol concentric flue systems.
Ø100/150 Maybe used Through-out
Flue Terminal:
Ø100/150
Maximum pipe extension, for outside wall (H) = 1 X Vertical Pipe Rise (V).
Maximum Permissible run (H) see table below.
Vertical Flue Rise
(V) metres
Max. Horizontal Flue Run, (H) m
for Ø100/150 flue
0.5
0.5
1
1
1.5
1.5
2
2
2.5
2.5
3
3
3.5
3.5
4
4
4.5
4.5
5
5
5.5
5.5
6
6
6.5
6.5
7
7
7.5 and over
7.5
Minimum Vertical Flue Height: 0.5m
3.4.7 Vertical Roof Vent Termination C31
Flue sizing:
Ø100/150 Connector on Appliance for Metaloterm US concentric flue system.
Ø100/150 Adaptor for Poujoulat PGI or Muelink & Grol concentric flue systems.
Ø100/150 Maybe used Through-out
Flue Terminal:
Ø100/150
Minimum Vertical Flue Height:
0.5m
Maximum Vertical Flue Height:
15m
Flue calculations when using elbows (0-90° permissible), total flue length maximum = 15m and each
bend will equate to ½m, Vertical rise (V) must be at least twice the Horizontal run (R), i.e. V=2H (or H/
V≤½).
Содержание Curvation:Siesta
Страница 7: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 7 ...
Страница 8: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 8 ...
Страница 9: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 9 ...
Страница 10: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 10 ...
Страница 26: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 26 Siesta Tall Siesta model with side windows ...
Страница 27: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 27 Appendix 1 Mertik Fault Finding Chart ...
Страница 28: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 28 ...
Страница 29: ...Curvation Siesta Series Manual V2 2 Capital Fireplaces 2017 29 ...