Connection to the Elevator Controls 

 

ISOLATING RELAYS 
 

For safety and system serviceability the access control system should be isolated from the 
power connections of the elevator buttons. An Elevator Interface Relay Box must be used 
for this purpose, to prevent high voltage and high voltage spikes from interfering with the 
access control system. This Elevator Relay Interface Box must be supplied by the elevator 
company to avoid potential liability issues. The Elevator Interface Relay Box must provide 
isolating relays which physically isolate the voltage present on the elevator buttons from the 
H1000 outputs.   

 

  
It is important to understand that the H1000 panel’s output relays (“Form C”) will be 
controlling the coils of the relays in the interface box and that a single shielded single pair 
must be used for each relay connection. Multi-pair cable must not be used as inductive 
voltage spikes will be passed onto the adjacent wires. These voltage spikes can cause the 
access control panel to be intermittent. To eliminate relay coil voltage spikes it is important 
to place a power diode (1N4007) right at the coil connection.  

 

 

SAFETY    

 

If the elevator relay interface box contains 110/220 VAC, it should be labeled outside with 
“DANGER High Voltage Contained Inside”. This is important for the safety of personnel 
doing maintenance.   

 

 

FIRE ALARM  

 

In the event that a building fire alarm occurs it is imperative that all floor selector buttons 
in the cab are operational. When a fire alarm occurs, the fire alarm panel

 

typically operates 

a dry relay contact. In normal operation (No Fire Alarm) this “Form C” relay contact is 
“Closed”. In the event of a fire alarm this “Form C” relay contact goes “Open”. This relay 
is used to automatically bypass the access control system in the event of a fire alarm so that 
all floor selection buttons are operational. 

 

 

SERVICE OVERRIDE SWITCH   

 

It is advisable to have an Elevator Access Controller Bypass Switch present. This allows the 
elevator company an easy means to work on the elevator without requiring the presence of 
the company in charge of maintaining the access control equipment. Similarly, if there is a 
failure with the elevator access control system, the bypass switch will allow elevator 
operation until the access control system is repaired. 

 
 

Содержание H1000

Страница 1: ...H1000 Elevator Control INSTALLATION GUIDE For use with H1000 V1 1 panel and daughter card EX100 V1 1 October 2015...

Страница 2: ...Panel LED Indicators 11 Master Panel Communication LEDS 12 Host Communication LEDs 12 Master EX100 Communication LEDs 12 Slave Panel Communication LEDS 13 Slave EX100 Communication LEDs 13 Connection...

Страница 3: ...ss to unauthorized elevator floors and at the same time allows the building owner to isolate different organizations that cohabit the same building The H1000 controller is a cost effective solution al...

Страница 4: ...olt relays are to be used in the interface box The H1000 output relay contacts will switch the 12 volt coil of the relay in the interface box Under no circumstance is 110 120 or higher voltage to be p...

Страница 5: ...figuration is used when connecting to an elevator system of up to 16 floors This consists of one H1000 control panel See Hurricane Operator Guide for more information Edit Panel Definitions Select 16...

Страница 6: ...itch Settings OPT1 ON OPT2 ON OPT3 OFF OPT4 OFF 1 Dipswitch Settings OPT1 ON OPT2 OFF OPT3 OFF OPT4 OFF 2 Jumper Setting 2 Jumper Setting 3 Address Setting 3 Address Setting Panel address is set to th...

Страница 7: ...nfiguration is used when connecting to an elevator of up to 48 floors This consists of three H1000 control panels designated as a master panel and a two slave panels Master Slave 1 Slave 2 RS485 Commu...

Страница 8: ...per Setting 2 Jumper Setting 3 Address Setting 3 Address Setting Panel address is set to the same as Master Panel Slave 2 Panel 1 Dipswitch Settings OPT1 OFF OPT2 ON OPT3 OFF OPT4 OFF 2 Jumper Setting...

Страница 9: ...sists of four H1000 control panels designated as a master panel and three slave panels Master Slave 1 Slave 3 Slave 2 Master Panel Controls floor 1 to 16 Slave 1 Panel Controls floor 17 to 32 Slave Pa...

Страница 10: ...ss is set to the same as Master Panel Slave 2 Panel Slave 3 Panel 1 Dipswitch Settings OPT1 OFF OPT2 ON OPT3 OFF OPT4 OFF 1 Dipswitch Settings OPT1 ON OPT2 ON OPT3 OFF OPT4 OFF 2 Jumper Setting 2 Jump...

Страница 11: ...ations use a second RS485 communication channel which enables the Master H1000 control panel to communicate to the Slave H1000 control panels There are LEDs associated with this communication channel...

Страница 12: ...Master EX100 Communication LEDs If the Master H1000 panel has been correctly configured as a 32 to 64 floor elevator system the two LEDs on the EX100 daughter board will indicate the RS485 communicat...

Страница 13: ...See previous section which describes the Master H1000 EX100 Communications Slave H1000 RD8 RD7 RD6 LEDs An additional H1000 Slave setup verification is implemented in this firmware Three LEDs are used...

Страница 14: ...intermittent To eliminate relay coil voltage spikes it is important to place a power diode 1N4007 right at the coil connection SAFETY If the elevator relay interface box contains 110 220 VAC it shoul...

Страница 15: ...below to allow easy connection of new panels This eliminates the need to connect 2 wires into one connector The 2 wire RS 485 connections are A and B The shield wire should be connected to GND H1000...

Страница 16: ...H1000 Elevator Control Page 16 of 20 Installation Guide October 2015 Rev 1 7 USING A CLAUSB RS 485 For CLAUSB2 please see Appendix Communication Wiring Using a CLAUSB...

Страница 17: ...N RS 485 Refer to the CanLan Installation Manual for instructions on how to configure the CanLan software NOTE It s recommended to use Option 2 below and connect to a battery backup power source to av...

Страница 18: ...485 RS 485 Please refer to the Air 485 Installation Manual for instructions on how to configure the Air 485 It is recommended that the Air 485 modems are connected to a battery backup power source to...

Страница 19: ...iring The H1000 reader connections are labeled below the reader connectors as shown below The 12 VDC power is supplied to the reader through the reader connector The H1000 reader uses an auto resettab...

Страница 20: ...H1000 Elevator Control Page 20 of 20 Installation Guide October 2015 Rev 1 7 Appendix USING A CLAUSB2 RS 485 Communication Wiring Using a CLAUSB2...

Отзывы: