Cannon Fitzroy Inbuilt Power Flue | 15

setting tHe gas PressUre

1.  gas valve layout is as indicated in 

FIG 30

.  

Pressures for ‘Burner high flame’ and ‘Burner low 
flame’ are factory set, however if pressures need to be 
checked or adjusted follow the procedures described 
below. To check outlet pressure at burner ‘high flame’ 
and ‘low flame’ positions remove the plastic cap from 
the regulatior adjustment location as indicated  
in 

FIG 31

.

2.  The pressure point is closed with a captive screw. Turn 

screw 6 revolutions anticlockwise to open the pressure 
point as indicated on 

FIG 32 (a)

 and place manometer 

tube over the test point as per 

FIG 32 (b)

.

3.  Switch the control buttons to ‘High flame’ position. 

Wait for heater to switch to ‘BOOST’ setting (time delay 
on start up). retain screwdriver in position and using 
a spanner adjust the outer nut on the control to give 
a high pressure reading (refer to specification table on 
page 8). 

(Turn clockwise to increase pressure and 

anticlockwise to decrease pressure)

. refer 

FIG 33

.

4.  Switch the control buttons to ‘low flame’ position. 

retain spanner in position and using a screwdriver 
adjust the central screw control to give a low pressure 
reading (refer to specification table on page 8). 

(Turn 

clockwise to increase pressure and anticlockwise 
to decrease pressure)

. refer 

FIG 34

.

5. remove spanner and screwdriver. Switch from high to       
    low to ensure settings are correct.
6.  Switch heater off and remove the manometer tube. 

Tighten pressure test point by turning the captive 
screw fully clockwise.

7.  replace plastic cap. Ensure the little lug is positioned 

towards lower right hand side to clear the controls.

8.  refit the fascia, making sure not to damage the power 

cord or switch cable.

9.  Operate the heater on BOOST, nOrMal and lOW 

settings. The flame should be stable, no lifting from the 
burner and the logs should glow after approximately 
15 minutes of operation on BOOST setting.

If the flame is unstable:
• Check that the burner is located correctly.
•  Check that the glass front is located correctly and is 

against the sealing rope.

• Check that the gas pressure is correctly adjusted
• Check that flue is operating correctly
If the heater still does not operate to specification refer  
to the troubleshooting chart on page 19, or contact  
Sampford IXl in your state.

fig 31

fig 32

(a)

(b)

fig 30

Burner adjustment 
(Burner ‘low flame’)

Plastic Cap

Pressure adjustment 
(Burner ‘High Flame’)

Pressure test 
point with  
captive screw

fig 33

adjust

Hold

fig 34

Hold

adjust

Содержание FITZIB-PMEXB

Страница 1: ...d this manual before installing and using this heater Please leave instruction manual with the owner Distributor This appliance is designed manufactured and distributed by Tel 1300 727 421 Models FITZ...

Страница 2: ...cessories 7 Fitzroy inbuilt POWER FLUE specifications 8 REGULATORY LOCATOR 9 POWER FLUE INSTALLATION INSTRUCTIONS 10 12 Fascia Removal AND Electrical Connection 13 Log Installation GAS CONNECTION 14 S...

Страница 3: ...XL products purchased in Australia from a Sampford IXL Authorised Dealer or Reseller and installed by a qualified person where a Certificate of Compliance in accordance with State Territory laws is pr...

Страница 4: ...d working order Privacy The privacy of your personal information has always been important to us To learn more about how we collect keep and use your personal information please obtain a copy of our p...

Страница 5: ...zard of high surface temperature and should take care to avoid burns or clothing ignition This appliance is not intended for use by persons including children with reduced physical sensory or mental c...

Страница 6: ...OST NORMAL turn the heater on again if there have been several attempts to ignite the heater without success If there is an interruption to the power supply the heater will fail safely and switch off...

Страница 7: ...nents of our instal lation options Install in a shallow recess or an existing fireplace elegant spacers will eliminate any size discrep ancies To enhance your Cannon s appearance add a decorative 3 or...

Страница 8: ...t Power consumption 90 VA maximum Minimum cavity Height Dimensions 605 mm Width 700 mm Depth 485 mm Optional accessories Glass front Remote thermostat Spacer kit 3 sided surround 4 sided surround Cons...

Страница 9: ...WER FLUE HEATER IS FAN ASSISTED SEE COLUMN HIGHLIGHTED a Below eaves balconies and other projections Appliances up to 50 MJ hr input 300 200 Appliances over 50 MJ hr input 500 300 b From the ground ab...

Страница 10: ...ease dispose of packaging appropriately keep away from children Clearances For minimum clearances refer FIG 5 and FIG 6 Note Ensure that the combustion air opening under the heater is not obstructed E...

Страница 11: ...round hole in the external wall To make a template use a sheet of stiff cardboard or mdf medium density fibre board cut to represent the rear of the heater Mark a vertical centre line and an appropria...

Страница 12: ...the flexible pipe from the flue outlet using silicon sealant to seal the join and a hose clamp 3 Fit the pvc tubing and the air inlet to the other flexible tube using a hose clamp 4 Place terminal co...

Страница 13: ...it at correct supply voltage may create unsafe conditions The heater is supplied with a flexible power cord with a plug fitted A 10 Amp switch socket must be located within 1 5m of the heater For inst...

Страница 14: ...ch loom to the fascia switch set 5 Refit the front fascia GAS CONNECTION FIG 24 FIG 25 FIG 27 FIG 26 1 Push the gas inlet access plate into the heater cabinet and slide the heater into the fireplace e...

Страница 15: ...ontrol to give a low pressure reading refer to specification table on page 8 Turn clockwise to increase pressure and anticlockwise to decrease pressure Refer FIG 34 5 Remove spanner and screwdriver Sw...

Страница 16: ...to fault codes on page 19 General 1 Service work MUST be carried out by an authorised service person only 2 Unplug from wall socket or turn off power at main switchboard if heater is hard wired 3 Alw...

Страница 17: ...l To Replace The Combustion Fan Fig 38 The Combustion Fan is accessed from the rear of the heater Therefore to replace the combustion fan the heater must be removed from the fireplace The flue termina...

Страница 18: ...EATHED HIGH TEMP DATA CABLE SWITCH BLUE Y A W 4 Y A W 6 Y A W 3 EARTH RED Y A W 1 C ROOM FAN F3594 240 V MAINS PLUG MODULATING VALVE F3691 COILS E M A L F R O S N E S K R A P S E D O R T C E L E IGNIT...

Страница 19: ...ormal operation 2 1 Heater has attempted to light however it did not sense flame within the allowed time Check the gas supply to the unit is not switched off Check the gas pressures Check the flame an...

Страница 20: ...ater and either listening for the fan or check to see if air is blowing out of the flue pipe Check that the pressure tubes are connected correctly and not pinched or kinked The black tube should run f...

Страница 21: ...Cannon Fitzroy Inbuilt Power Flue 21 Notes...

Страница 22: ...22 Cannon Canterbury Freestanding Notes...

Страница 23: ...Cannon Canterbury Freestanding 23 Notes...

Страница 24: ...ed Compliance Certificate No Installed by COPY RATING LABEL HERE Don t Risk Your Appliance Warranty Only a licensed person will give you a compliance certificate showing that the work complies with al...

Отзывы: