background image

STUD

STUD

C.L. OF

HEATER

345 mm TO 610 mm

FLUE OPENING

GAS INLET

325 mm

245 mm

44 mm

30 mm

540 mm

FLUE 
OPENING 
DETAIL

METHOD A

600 mm MIN
BETWEEN TOP OF
COWL AND NEAREST
PART OF ROOF

75 mm MAIN
STUD WALL

ADJUSTMENT
STRAP

HEADER

TWIN
SKIN FLUE

TOP PLATE
FLUE SUPPORT

FLUE ADAPTER

FLASHING

FLUE CLAMP

FLUE COWL
APPROVED
TO AG604

ROOF CLADDING

100 mm DIA
FLUE PIPE

MAINTAIN 25 mm
CLEARANCE BETWEEN
FLUE AND WOODWORK

WALL CLADDING

12 mm FROM
BOTTOM OF
WALL CLADDING
TO TOP OF HEATER

MEASURE DISTANCE FROM
FLOOR TO TOP OF HEATER
FLUE OUTLET PLUS 2 mm

COWL

FIT 
3 SCREWS

SMALL DIA
END WITH
SWAGE

TOP PLATE
FLUE SUPPORT

FLUE
ADAPTER

SINGLE
SKIN FLUE

Page 2.

Page 7.

FIG 6.

MOCK FIREPLACE ENCLOSURE RECOMMENDATIONS

FIG 1.

300mm MAX

2400mm MAX

550mm MAX

MAKE SURE THERE IS ADEQUATE VENTILATION IN ROOM.

MOCKKITRA

The enclosure can be fabricated using any standard building 
materials, providing that spacer brackets are fitted to the 
heater to provide adequate clearances to combustible 
materials. (see Fig 5).

The area of the cavity must not exceed our dimensions as 
shown in the diagram. (see Fig1).
If the enclosure is larger than our dimensions allow, a 
separate boxed section around the heater will need to be 
constructed.

The heater must sit on a solid, sealed base and the enclosure 
must be sealed from any draughts and be insulated as 
necessary to eliminate low temperatures.

An enclosure constructed to an existing room with a solid floor 
and ceiling, and any other enclosure must have the same 
characteristics of being sealed from any draughts and suitably 
insulated from low temperatures. Failure to adhere to this 
requirement will result in unreliable operation or failure to 
operate correctly and is not covered by our warranty 
conditions.